{"id":23431,"date":"2026-11-21T10:17:17","date_gmt":"2026-11-21T02:17:17","guid":{"rendered":"https:\/\/www.wehopower.com\/news\/sensor-relay-clamp-release-time\/"},"modified":"2026-11-21T10:17:17","modified_gmt":"2026-11-21T02:17:17","slug":"sensor-relay-clamp-release-time","status":"publish","type":"news","link":"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/","title":{"rendered":"Proximity Sensor Relay Loads: Check Clamp and Release Time"},"content":{"rendered":"<div class=\"weho-blog\">\n<div class=\"key-takeaways\"><strong>Key Engineering Takeaways<\/strong><\/p>\n<ul>\n<li>A relay coil needs an approved drive and suppression arrangement, not merely a matching nominal voltage.<\/li>\n<li>Suppression affects both switch voltage stress and the coil&#39;s current-decay time.<\/li>\n<li>Coil current crossing a threshold does not equal completed relay-contact release.<\/li>\n<li>Verify the exact sensor output, coil, clamp and contact response together before approving the interface.<\/li>\n<\/ul>\n<\/div>\n<figure class=\"article-figure hero\" data-asset=\"F18-hero\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/product\/lja18-long-cylindrical-inductive-proximity-switch\/\" aria-label=\"LJA18 details\"><img fetchpriority=\"high\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/92adbb31fafb907a-lja18-application.webp\" alt=\"LJA18 product installed in an industrial application scene with original housing and label details.\" width=\"1200\" height=\"675\" loading=\"eager\" fetchpriority=\"high\" decoding=\"async\" title=\"\"><\/a><figcaption>AI-assisted application illustration of LJA18. No particular output suffix, measured target response or relay load is established by the illustration. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/8b7d97dc79ebe6e3-application-master.png\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<nav class=\"table-of-contents\" aria-label=\"Article contents\">\n<details open>\n<summary>On this page<\/summary>\n<ol>\n<li><a href=\"#define-the-complete-sensor-to-relay-interface\">Define the complete sensor-to-relay interface<\/a><\/li>\n<li><a href=\"#understand-why-suppression-changes-release\">Understand why suppression changes release<\/a><\/li>\n<li><a href=\"#compare-a-declared-ideal-coil-model\">Compare a declared ideal coil model<\/a><\/li>\n<li><a href=\"#measure-the-contact-event-that-matters\">Measure the contact event that matters<\/a><\/li>\n<li><a href=\"#approve-the-combination-not-an-isolated-component\">Approve the combination, not an isolated component<\/a><\/li>\n<li><a href=\"#send-weho-the-coil-and-timing-requirements\">Send WEHO the coil and timing requirements<\/a><\/li>\n<li><a href=\"#frequently-asked-questions\">Frequently asked questions<\/a><\/li>\n<\/ol>\n<\/details>\n<\/nav>\n<div id=\"ez-toc-container\" class=\"ez-toc-v2_0_89 counter-hierarchy ez-toc-counter ez-toc-grey ez-toc-container-direction\">\n<div class=\"ez-toc-title-container\">\n<p class=\"ez-toc-title\" style=\"cursor:inherit\">Table of Contents<\/p>\n<span class=\"ez-toc-title-toggle\"><a href=\"#\" class=\"ez-toc-pull-right ez-toc-btn ez-toc-btn-xs ez-toc-btn-default ez-toc-toggle\" aria-label=\"Toggle Table of Content\"><span class=\"ez-toc-js-icon-con\"><span class=\"\"><span class=\"eztoc-hide\" style=\"display:none;\">Toggle<\/span><span class=\"ez-toc-icon-toggle-span\"><svg style=\"fill: #999;color:#999\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" class=\"list-377408\" width=\"20px\" height=\"20px\" viewBox=\"0 0 24 24\" fill=\"none\"><path d=\"M6 6H4v2h2V6zm14 0H8v2h12V6zM4 11h2v2H4v-2zm16 0H8v2h12v-2zM4 16h2v2H4v-2zm16 0H8v2h12v-2z\" fill=\"currentColor\"><\/path><\/svg><svg style=\"fill: #999;color:#999\" class=\"arrow-unsorted-368013\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" width=\"10px\" height=\"10px\" viewBox=\"0 0 24 24\" version=\"1.2\" baseProfile=\"tiny\"><path d=\"M18.2 9.3l-6.2-6.3-6.2 6.3c-.2.2-.3.4-.3.7s.1.5.3.7c.2.2.4.3.7.3h11c.3 0 .5-.1.7-.3.2-.2.3-.5.3-.7s-.1-.5-.3-.7zM5.8 14.7l6.2 6.3 6.2-6.3c.2-.2.3-.5.3-.7s-.1-.5-.3-.7c-.2-.2-.4-.3-.7-.3h-11c-.3 0-.5.1-.7.3-.2.2-.3.5-.3.7s.1.5.3.7z\"\/><\/svg><\/span><\/span><\/span><\/a><\/span><\/div>\n<nav><ul class='ez-toc-list ez-toc-list-level-1 ' ><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-1\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Define_the_complete_sensor-to-relay_interface\" >Define the complete sensor-to-relay interface<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-2\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Understand_why_suppression_changes_release\" >Understand why suppression changes release<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-3\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Compare_a_declared_ideal_coil_model\" >Compare a declared ideal coil model<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-4\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Measure_the_contact_event_that_matters\" >Measure the contact event that matters<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-5\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Approve_the_combination_not_an_isolated_component\" >Approve the combination, not an isolated component<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-6\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Send_WEHO_the_coil_and_timing_requirements\" >Send WEHO the coil and timing requirements<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-7\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Frequently_asked_questions\" >Frequently asked questions<\/a><ul class='ez-toc-list-level-3' ><li class='ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-8\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Does_matching_coil_voltage_establish_sensor_compatibility\" >Does matching coil voltage establish sensor compatibility?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-9\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Is_a_lower_clamp_voltage_always_preferable\" >Is a lower clamp voltage always preferable?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-10\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Does_current_reaching_the_chosen_threshold_prove_the_contact_opened\" >Does current reaching the chosen threshold prove the contact opened?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-11\" href=\"https:\/\/www.wehopower.com\/ar\/news\/sensor-relay-clamp-release-time\/#Can_a_replacement_relay_socket_change_the_result\" >Can a replacement relay socket change the result?<\/a><\/li><\/ul><\/li><\/ul><\/nav><\/div>\n<h2 id=\"define-the-complete-sensor-to-relay-interface\"><span class=\"ez-toc-section\" id=\"Define_the_complete_sensor-to-relay_interface\"><\/span>Define the complete sensor-to-relay interface<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>A proximity sensor that can signal an electronic input is not automatically approved to drive a relay coil. The coil presents an inductive load, and its turn-off behavior depends on the drive and suppression circuit. Procurement must obtain the applicable limits before treating a nominal output-current rating as compatibility evidence.<\/p>\n<p>For the <a href=\"https:\/\/www.wehopower.com\/product\/lja18-long-cylindrical-inductive-proximity-switch\/\">WEHO LJA18 family<\/a>, identify the exact output suffix and circuit first. The family photograph does not establish an NPN or PNP configuration, permissible coil load or clamp voltage. No direct-coil connection is approved by the application image.<\/p>\n<p>State what the relay must accomplish after the sensor changes state. A requirement may concern contact opening, a downstream input transition or another defined process event. A coil waveform alone cannot prove that the complete event happened within the required time.<\/p>\n<h2 id=\"understand-why-suppression-changes-release\"><span class=\"ez-toc-section\" id=\"Understand_why_suppression_changes_release\"><\/span>Understand why suppression changes release<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>When coil current is interrupted, the inductance resists the current change and produces a voltage determined by the available path. A suppression arrangement limits that voltage, but it also controls how the stored magnetic energy decays. The result must be evaluated with the switching device&#39;s actual electrical limits.<\/p>\n<p>TI&#39;s <a href=\"https:\/\/www.ti.com\/document-viewer\/lit\/html\/slvaf04\" target=\"_blank\" rel=\"noopener\">inductive-load application brief<\/a> explains the tradeoff between clamping voltage and current discharge time. Its example driver includes particular internal paths that affect decay. Those details are a reason to examine the actual circuit rather than assume that every transistor output behaves like a bare switch.<\/p>\n<p>A low-voltage recirculation path can extend current decay compared with a higher reverse voltage across the coil. A higher permitted reverse voltage can increase the stress seen by the switching device. Neither observation supplies a universal clamp recommendation because topology, tolerance and transient conditions determine the actual limits.<\/p>\n<p>TE Connectivity&#39;s <a href=\"https:\/\/www.te.com\/en\/products\/relays-and-contactors\/electromechanical-relays\/intersection\/coil-suppression-relay-life.html\" target=\"_blank\" rel=\"noopener\">coil-suppression application note<\/a> also discusses effects on armature motion and contact switching. Current decay, mechanical release and contact behavior are related but different observations. A successful electrical-stress check therefore does not finish the contact-timing assessment.<\/p>\n<figure class=\"article-figure product\" data-asset=\"F18-product\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/product\/lja18-long-cylindrical-inductive-proximity-switch\/\" aria-label=\"LJA18 details\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/03b545a0daba8275-lja18-product-reference.webp\" alt=\"LJA18 product reference preserving original housing, model identification and visible connection details for comparison.\" width=\"800\" height=\"800\" loading=\"lazy\" decoding=\"async\" title=\"\"><\/a><figcaption>Product reference for LJA18; original visible identity is retained. No particular output suffix, measured target response or relay load is established by the illustration. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/429bc73583cd6e7c-product-original.jpg\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<h2 id=\"compare-a-declared-ideal-coil-model\"><span class=\"ez-toc-section\" id=\"Compare_a_declared_ideal_coil_model\"><\/span>Compare a declared ideal coil model<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Consider a <strong>hypothetical analytical example<\/strong>, not an LJA18 circuit design or a relay qualification. Assume a 24 V supply, a fixed 300 \u03a9 coil resistance, an ideal 0.40 H inductance and an initial current of 0.080 A. The steady-state relationship is consistent: 24 V \u00f7 300 \u03a9 = 0.080 A.<\/p>\n<p>For illustration, calculate the time for current to fall to 0.020 A after turn-off. This chosen threshold is not a published relay release current. Assume the suppression imposes a constant reverse voltage Vc across the coil and that the electrical model remains fixed during the interval.<\/p>\n<p>The model obeys L \u00d7 di\/dt = \u2212Ri \u2212 Vc. Integrating from initial current I\u2080 to the chosen threshold Ir gives t = (L\/R) \u00d7 ln[(RI\u2080 + Vc)\/(RIr + Vc)]. This model includes winding resistance but excludes moving-armature effects, parasitic behavior and component tolerances.<\/p>\n<p>For Vc = 0.7 V, t = (0.40\/300) \u00d7 ln[(24 + 0.7)\/(6 + 0.7)] = approximately 1.740 ms. For Vc = 24 V, the same calculation gives (0.40\/300) \u00d7 ln[48\/30] = approximately 0.627 ms. The higher illustrative reverse voltage produces a shorter modeled current-decay interval.<\/p>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">Hypothetical reverse coil clamp<\/th>\n<th scope=\"col\">Modeled time to 20 mA<\/th>\n<th scope=\"col\">Ideal low-side switch voltage<\/th>\n<th scope=\"col\">What remains unresolved<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>0.7 V<\/td>\n<td>1.740 ms<\/td>\n<td>24 + 0.7 = 24.7 V<\/td>\n<td>Actual stress, motion and contact timing<\/td>\n<\/tr>\n<tr>\n<td>24 V<\/td>\n<td>0.627 ms<\/td>\n<td>24 + 24 = 48 V<\/td>\n<td>Actual stress, motion and contact timing<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<figure class=\"article-figure technical\" data-asset=\"F18-technical\">\n<div class=\"diagram-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering diagram\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/dcf074ffcbd7e608-coil-clamp-stress-decay-comparison.svg\" alt=\"Ideal coil comparison showing the tradeoff between reverse clamp voltage, switch stress and current-decay time.\" width=\"1200\" height=\"675\" loading=\"lazy\" decoding=\"async\" title=\"\"><\/div><figcaption>Conceptual Engineering Diagram. A hypothetical fixed 0.40 H, 300 \u03a9 coil decays from 80 mA to a chosen 20 mA threshold. These analytical times are not relay-contact release times or approved LJA18 clamp values. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/dcf074ffcbd7e608-coil-clamp-stress-decay-comparison.svg\" target=\"_blank\" rel=\"noopener\">Open full-size diagram<\/a><\/figcaption><p class=\"figure-help\">Swipe horizontally on a small screen, or open the full-size diagram.<\/p>\n<\/figure>\n<p>The switch-voltage column assumes a particular ideal low-side arrangement, where the turn-off node rises above the supply by the reverse coil clamp. It is not the voltage across every suppression component in every topology. Actual overshoot and maximum supply voltage would need separate evaluation.<\/p>\n<p>The 48 V result illustrates why \u201ca 24 V relay on a 24 V system\u201d is incomplete evidence for driver stress. It does not authorize a 24 V clamp on a WEHO output. No allowable LJA18 switch voltage or avalanche capability has been established by this example.<\/p>\n<p>Stored magnetic energy at the assumed initial condition is \u00bd \u00d7 0.40 H \u00d7 (0.080 A)\u00b2 = 0.00128 J. That total ideal energy does not by itself specify a suppressor&#39;s pulse rating or repetitive thermal capability. The actual circuit divides dissipation among paths, and component selection must follow the approved design analysis.<\/p>\n<h2 id=\"measure-the-contact-event-that-matters\"><span class=\"ez-toc-section\" id=\"Measure_the_contact_event_that_matters\"><\/span>Measure the contact event that matters<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>A coil-current trace can identify electrical decay, while the relay contact may move later and exhibit bounce. Define which edge or stable contact condition ends the timing interval. Without that definition, two \u201crelease time\u201d results can refer to different events.<\/p>\n<p>OMRON&#39;s <a href=\"https:\/\/www.ia.omron.com\/product\/cautions\/36\/safety_precautions.html\" target=\"_blank\" rel=\"noopener\">general-purpose relay precautions<\/a> state that suppression can lengthen release time and call for checking actual application operation. Use the exact relay&#39;s documented timing conditions and the selected suppression arrangement. Do not substitute the unsuppressed catalogue timing for a differently configured assembly.<\/p>\n<p>The acceptance record should connect the sensor output transition, driver-node behavior, coil current and relevant contact event on a common time reference. Use suitable instrumentation and an approved test fixture. The goal is to evaluate a documented arrangement, not to remove suppression and create an unprotected comparison.<\/p>\n<p>If the relay contact feeds a PLC, retain the receiver&#39;s input delay as another boundary. If it switches power, retain the actual load type and switching duty separately from the coil-side assessment. Neither an acceptable sensor output nor a quick coil decay establishes the relay contact&#39;s load-switching capability.<\/p>\n<h2 id=\"approve-the-combination-not-an-isolated-component\"><span class=\"ez-toc-section\" id=\"Approve_the_combination_not_an_isolated_component\"><\/span>Approve the combination, not an isolated component<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>The <a href=\"https:\/\/www.wehopower.com\/news\/how-to-integrate-inductive-proximity-sensors-with-plc-based-control-systems\/\">WEHO sensor-to-PLC integration guide<\/a> addresses the receiving-interface task. A coil-driven interface adds inductive energy and release dynamics to that review. Identify whether an approved interface module is required when the sensor&#39;s documented output does not cover the proposed load.<\/p>\n<p>A change in relay socket can also change the circuit if suppression or indicator components are built into the socket. Include the complete relay and socket order codes. A visually similar replacement can preserve coil voltage while altering the current-decay path.<\/p>\n<ol>\n<li><strong>Identify every interface part.<\/strong> Record sensor suffix, output circuit, relay coil, socket and suppression components. Accept the document set only when the exact supplied combination is identifiable.<\/li>\n<li><strong>Check electrical limits.<\/strong> Compare coil demand and the approved turn-off stress with applicable output and component limits. Record tolerances and conditions; unresolved limits prevent approval of the proposed arrangement.<\/li>\n<li><strong>Define the process event.<\/strong> State the required contact or receiver transition and timing window. Retain the observation points so current decay cannot be mistaken for completed mechanical release.<\/li>\n<li><strong>Validate the documented circuit.<\/strong> Record driver stress, coil behavior and the relevant contact event under the agreed operating matrix. Judge each result against its own requirement, using suitable instrumentation and an approved procedure.<\/li>\n<li><strong>Control replacements.<\/strong> Retain accepted part codes, suppression identity and results with the equipment revision. Repeat affected checks when the sensor, relay, socket, supply range or required timing changes.<\/li>\n<\/ol>\n<h2 id=\"send-weho-the-coil-and-timing-requirements\"><span class=\"ez-toc-section\" id=\"Send_WEHO_the_coil_and_timing_requirements\"><\/span>Send WEHO the coil and timing requirements<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>For an <a href=\"https:\/\/www.wehopower.com\/product\/lja18-long-cylindrical-inductive-proximity-switch\/\">LJA18 interface inquiry<\/a>, provide the full sensor label, relay and socket documentation, proposed suppression circuit and required event time. Request confirmation of the applicable output limits or a supported interface approach. Preserve the exact circuit in the approval record before purchasing production quantities.<\/p>\n<h2 id=\"frequently-asked-questions\"><span class=\"ez-toc-section\" id=\"Frequently_asked_questions\"><\/span>Frequently asked questions<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<h3 id=\"does-matching-coil-voltage-establish-sensor-compatibility\"><span class=\"ez-toc-section\" id=\"Does_matching_coil_voltage_establish_sensor_compatibility\"><\/span>Does matching coil voltage establish sensor compatibility?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Coil current, output circuit, turn-off stress and the approved suppression arrangement must also agree. Use the exact sensor suffix and relay assembly documentation before approving a connection.<\/p>\n<h3 id=\"is-a-lower-clamp-voltage-always-preferable\"><span class=\"ez-toc-section\" id=\"Is_a_lower_clamp_voltage_always_preferable\"><\/span>Is a lower clamp voltage always preferable?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Lower electrical stress can come with slower current decay, while a higher clamp can exceed the switch&#39;s limits. Evaluate both requirements within an approved circuit rather than choosing from voltage alone.<\/p>\n<h3 id=\"does-current-reaching-the-chosen-threshold-prove-the-contact-opened\"><span class=\"ez-toc-section\" id=\"Does_current_reaching_the_chosen_threshold_prove_the_contact_opened\"><\/span>Does current reaching the chosen threshold prove the contact opened?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Armature motion and contact behavior require their own observation and timing definition. The hypothetical calculation describes only current decay in a simplified fixed electrical model.<\/p>\n<h3 id=\"can-a-replacement-relay-socket-change-the-result\"><span class=\"ez-toc-section\" id=\"Can_a_replacement_relay_socket_change_the_result\"><\/span>Can a replacement relay socket change the result?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>Yes. A socket can contain suppression or indicator components that alter the coil circuit. Retain its exact order code and reassess affected stress and timing requirements after substitution.<\/p>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>Compare relay-coil clamp stress and current decay before approving a sensor output. Send WEHO your LJA18 suffix, coil, socket and release-time requirement.<\/p>","protected":false},"author":2,"featured_media":22234,"parent":0,"menu_order":22,"comment_status":"","ping_status":"","template":"","format":"standard","meta":{"_acf_changed":false,"_joinchat":[],"footnotes":""},"news_category":[284],"class_list":["post-23431","news","type-news","status-publish","format-standard","has-post-thumbnail","hentry","news_category-product-articles","entry"],"acf":[],"post_mailing_queue_ids":[],"_links":{"self":[{"href":"https:\/\/www.wehopower.com\/ar\/wp-json\/wp\/v2\/news\/23431","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.wehopower.com\/ar\/wp-json\/wp\/v2\/news"}],"about":[{"href":"https:\/\/www.wehopower.com\/ar\/wp-json\/wp\/v2\/types\/news"}],"author":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/ar\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/ar\/wp-json\/wp\/v2\/comments?post=23431"}],"version-history":[{"count":0,"href":"https:\/\/www.wehopower.com\/ar\/wp-json\/wp\/v2\/news\/23431\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/ar\/wp-json\/wp\/v2\/media\/22234"}],"wp:attachment":[{"href":"https:\/\/www.wehopower.com\/ar\/wp-json\/wp\/v2\/media?parent=23431"}],"wp:term":[{"taxonomy":"news_category","embeddable":true,"href":"https:\/\/www.wehopower.com\/ar\/wp-json\/wp\/v2\/news_category?post=23431"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}