Key Engineering Takeaways
- Size the 12 V supply from the worst-case current of every camera (IR, heater and PTZ motion on), not from daytime current.
- Check each branch: Vdrop = I × 2L × R, using the outbound and return conductor.
- At 1.0 A and a 1.2 V drop budget, 18 AWG copper reaches only about 29 m one way.
- Read the model’s derating curve at the real enclosure temperature before accepting the rating.
Why 12V CCTV Runs Fail When the Supply Looks Big Enough
A central 12 V supply can have ample wattage and still leave the farthest camera under-voltage. At night, IR illuminators, heaters and PTZ motors raise current, and the cable converts that current into lost volts. The result is a camera that works during the day and reboots after dark.
The fix is two separate checks: a load check at the supply terminals and a voltage check at each camera. The sections below work through both with numbers you can recalculate.
This article sizes a regulated 12.0 V LRS system and calculates cable distance from published copper resistance. For a multi-camera design that starts from a 13.8 V main output, a separate charging branch, backup runtime and the split between direct low-voltage and PoE, see CCTV supply selection for multi-camera systems.
Step 1: Size the Supply From Worst-Case Camera Current
Use the maximum current from each camera datasheet, with every load that can be on at the same time. The numbers below are a worked example: camera currents are assumed values, not measurements of a specific camera.
- 8 fixed IR bullets × 0.5 A = 4.0 A
- 2 IR domes × 0.6 A = 1.2 A
- 2 PTZ cameras with heater × 2.0 A = 4.0 A
- Total continuous current = 9.2 A, or 9.2 A × 12 V = 110.4 W
This example chooses an 80% design load ratio, so the rated current must be at least 9.2 A ÷ 0.8 = 11.5 A. The 80% figure is a design choice for this example, not a general WEHO rule. The LRS-200-12 12 V 17 A enclosed supply is rated 0–17 A, so the calculated load is 9.2 ÷ 17 = 54% of rating.
Next, check temperature. The LRS-200 derating curve for 12–48 V outputs (horizontal mounting) shows 100% load up to 50 °C and 50% at 70 °C. At 70 °C the LRS-200-12 therefore allows 8.5 A, which is below the 9.2 A load. Between 50 °C and 70 °C, read the published curve rather than estimating.
Finally, check start-up. If both PTZ cameras could draw an assumed 3.0 A peak at the same moment, the total becomes 4.0 + 1.2 + 6.0 = 11.2 A. That is within the 17 A rating up to 50 °C, but above the 8.5 A allowed at 70 °C, so confirm the camera’s real start-up current and duration. The LRS-200 datasheet describes its overload protection as “110%~150% cut off the output, automatic recovery”.
Step 2: Check Voltage Drop on Every Camera Branch
Low-voltage DC current flows out on the positive conductor and back on the negative conductor, so the loop length is twice the one-way distance.
Vdrop = I × 2 × L × R
Vcamera = Vsupply − Vdrop
Here I is the branch current in amperes, L is the one-way length in meters and R is conductor resistance in ohms per meter. The resistance values are the published 20 °C values in NIST Handbook 100, Table 11 (standard annealed copper, solid wire). Stranded and copper-clad aluminum (CCA) cable will differ, so use the cable maker’s datasheet when it is available.
Using the same example, with the supply set to 12.0 V and an assumed camera minimum of 10.8 V:
- Bullet, 0.5 A, 40 m of 18 AWG: 0.5 × 80 × 0.0210 = 0.84 V drop, 11.16 V at the camera. Pass.
- Dome, 0.6 A, 55 m of 18 AWG: 1.39 V drop, 10.61 V. Fail. With 16 AWG: 0.87 V drop, 11.13 V. Pass.
- PTZ, 2.0 A, 60 m of 16 AWG: 3.17 V drop, 8.83 V. Fail. With 12 AWG: 1.25 V drop, 10.75 V. Fail, just below the assumed 10.8 V minimum.
- PTZ fed by a local LRS-50-12 with 5 m of 18 AWG: 0.42 V drop, 11.58 V. Pass.
Conductor resistance also rises with temperature. In the NIST table, 18 AWG rises from 21.0 Ω/km at 20 °C to 23.4 Ω/km at 50 °C, about 11% more drop on hot outdoor runs.
Maximum 12V Cable Distance by Wire Gauge
The table gives the longest one-way run that keeps the calculated loop drop at 1.2 V, which is 10% of 12 V. It assumes solid copper at 20 °C and ignores connector resistance, so treat it as an upper bound. If your camera accepts a lower minimum voltage, recalculate with that budget.
| Copper size | Resistance (Ω/km) | 0.5 A load | 1.0 A load | 2.0 A load |
|---|---|---|---|---|
| 22 AWG | 53.2 | 22.6 m | 11.3 m | 5.6 m |
| 20 AWG | 33.2 | 36.1 m | 18.1 m | 9.0 m |
| 18 AWG | 21.0 | 57.1 m | 28.6 m | 14.3 m |
| 16 AWG | 13.2 | 90.9 m | 45.5 m | 22.7 m |
| 14 AWG | 8.28 | 144.9 m | 72.5 m | 36.2 m |
| 12 AWG | 5.21 | 230.3 m | 115.2 m | 57.6 m |
Maximum distance is inversely proportional to current: a 2 A PTZ draws four times the current of a 0.5 A bullet, so it needs about four times the copper area for the same run. When a branch needs conductors heavier than about 14 AWG, a local supply near the cameras is often the simpler option. Check the terminal wire range of both the camera and the supply before choosing heavy cable.
Central or Local Supply: Choosing an LRS Model
A central supply simplifies maintenance and battery backup; local supplies shorten the low-voltage runs. In the example, the bullets and domes stay on a central supply, while each PTZ camera needs a local supply, because even 12 AWG leaves its branch below 10.8 V.
With the PTZs moved to local supplies, the central load drops to 8 × 0.5 + 2 × 0.6 = 5.2 A. That is 31% of the LRS-200-12 rating and within its 8.5 A limit at 70 °C.
| Modelo | Rated output and AC input | Load allowed at 70 °C | Role in example |
|---|---|---|---|
| LRS-50-12 | 12 V, 0–4.2 A; 85–264 VAC | 230 VAC curve: 60% (2.52 A). 115 VAC: to be confirmed | Local supply for one PTZ (2.0 A) |
| LRS-200-12 | 12 V, 0–17 A; 90–132 / 180–264 VAC by switch | 50% (8.5 A) | Central supply for 8 bullets and 2 domes (5.2 A) |
| LRS-350-12 | 12 V, 0–29 A; 90–132 / 180–264 VAC by switch | 60% (17.4 A) | Not needed here; for larger central loads |

For a local PTZ position, the LRS-50-12 12 V 4.2 A enclosed supply carries 2.0 A at 48% of rating. Its datasheet lists no IP or waterproof rating, so it needs a suitable enclosure and an AC feed at the pole or junction box. Its 70 °C curve is drawn for 230 VAC input; on 115/120 VAC sites, measure the pole-box temperature and ask WEHO engineering for the 115 VAC value.
The assumed 3.0 A PTZ start-up peak is above the 2.52 A allowed at 70 °C on the 230 VAC curve, so confirm the start-up current against the curve at the enclosure temperature.
If a larger central load must stay in one hot enclosure, the LRS-350-12 12 V 29 A enclosed supply allows 17.4 A at 70 °C on its curve. The LRS-200 and LRS-350 use an input selector switch, so set it to the site voltage before power-up.
If you are still deciding the DC voltage itself, compare options in our 12V vs 24V CCTV selection guide. For runtime during outages, see 12V CCTV power supply with battery backup.
The LRS output is adjustable by ±10%. Raising it to offset drop is only appropriate on a dedicated branch: on the 12 AWG PTZ branch set to 13.2 V, the camera sees about 11.9 V at 2.0 A but about 12.9 V at an assumed 0.5 A idle current. Confirm that value against the camera’s maximum input first.
Commissioning Checks Before Handover
- Record the camera schedule: model, maximum current, one-way length and conductor size for each branch. Verify it against the calculation above.
- Measure voltage at the supply terminals and at the farthest camera with IR, heaters and PTZ motion active. Record both values; the camera-end value must meet the camera datasheet minimum.
- Measure enclosure air temperature near the supply under load. Compare it with the derating curve of the exact model.
- Power-cycle the whole system and record whether any camera reboots or any supply enters overload protection.
AC-side wiring and protective earth connections should be completed and checked by a qualified electrician with the circuit isolated.
Send Your Camera Schedule for a Model Check
If you are specifying a project, send WEHO your camera list, worst-case currents, cable gauge and one-way length per branch, enclosure temperature and AC input through the WEHO project enquiry form. Ask us to check whether an LRS model and its derating curve fit that load before you order samples.
Preguntas frecuentes
How do I calculate voltage drop on a 12V CCTV cable?
Multiply the branch current by twice the one-way length and by the conductor resistance per meter. For 1.0 A over 30 m of 18 AWG copper, the drop is 1.0 × 60 × 0.0210 = 1.26 V, leaving 10.74 V from a 12.0 V supply.
What is the maximum cable distance for a 12V camera?
There is no single maximum; it depends on current, gauge and the camera’s minimum voltage. With a 1.2 V budget, a 0.5 A camera on 18 AWG copper reaches about 57 m one way, but a 2.0 A PTZ reaches only about 14 m.
Can I raise the supply voltage to make up for voltage drop?
Only on a dedicated branch, and only after checking the camera’s maximum input. The camera sees a higher voltage when its current falls, so a setting that is correct at full load can be too high at idle.
Should I use one central supply or several local supplies?
Use a central supply when every branch passes the voltage-drop check at its worst-case current. Where a branch fails even with heavier cable, a local supply near that camera group is usually the simpler fix.
Sources: NIST Handbook 100, Copper Wire Tables (1966), Table 11; WEHO LRS-50, LRS-200 and LRS-350 datasheets with curves, dated 2026-11-13, downloadable from the product pages linked above.