{"id":22665,"date":"2026-11-18T10:19:53","date_gmt":"2026-11-18T02:19:53","guid":{"rendered":"https:\/\/www.wehopower.com\/news\/rtd-self-heating-excitation-budget\/"},"modified":"2026-11-18T10:19:53","modified_gmt":"2026-11-18T02:19:53","slug":"rtd-self-heating-excitation-budget","status":"publish","type":"news","link":"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/","title":{"rendered":"RTD Self-Heating: Separate Excitation Error from Process Heat"},"content":{"rendered":"<div class=\"weho-blog\">\n<div class=\"key-takeaways\"><strong>Key Engineering Takeaways<\/strong><\/p>\n<ul>\n<li>An RTD dissipates I\u00b2R power from its measuring current, so the element can run warmer than the process.<\/li>\n<li>Estimate self-heating with the probe&#8217;s dissipation data for its actual installation medium.<\/li>\n<li>Reducing current changes the measurement signal as well as heating; verify the complete error budget.<\/li>\n<li>Do not assume the ordered TX4-W exposes an adjustable excitation-current setting.<\/li>\n<\/ul>\n<\/div>\n<figure class=\"article-figure hero\" data-asset=\"F08-hero\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/es\/product\/tx4-series-tx4-w-economic-dual-display-pid-temperature-controller\/\" aria-label=\"TX4-W details\"><img fetchpriority=\"high\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/dc1746a7538df850-tx4-w-application.webp\" alt=\"RTD Self-Heating: Separate Excitation Error from Process Heat  title=\" width=\"1200\" height=\"675\" loading=\"eager\" decoding=\"async\" rtd self-heating: separate excitation error from process heat title =\"\"><\/a><figcaption>AI-assisted application illustration of TX4-W. The retained display belongs to the source image; no excitation setting or enclosure IP test is shown. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/c76124328a2bc272-application-master.png\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<nav class=\"table-of-contents\" aria-label=\"Article contents\">\n<details open>\n<summary>On this page<\/summary>\n<ol>\n<li><a href=\"#why-a-stable-display-may-still-be-biased\">Why a stable display may still be biased<\/a><\/li>\n<li><a href=\"#define-electrical-heating-and-thermal-removal-separately\">Define electrical heating and thermal removal separately<\/a><\/li>\n<li><a href=\"#calculate-a-hypothetical-current-and-medium-budget\">Calculate a hypothetical current-and-medium budget<\/a><\/li>\n<li><a href=\"#build-an-evidence-budget-instead-of-a-blanket-offset\">Build an evidence budget instead of a blanket offset<\/a><\/li>\n<li><a href=\"#verify-self-heating-without-assuming-current-is-adjustable\">Verify self-heating without assuming current is adjustable<\/a><\/li>\n<li><a href=\"#ask-weho-for-the-input-details-that-close-the-budget\">Ask WEHO for the input details that close the budget<\/a><\/li>\n<li><a href=\"#engineering-faq\">Engineering FAQ<\/a><\/li>\n<\/ol>\n<\/details>\n<\/nav>\n<div id=\"ez-toc-container\" class=\"ez-toc-v2_0_89 counter-hierarchy ez-toc-counter ez-toc-grey ez-toc-container-direction\">\n<div class=\"ez-toc-title-container\">\n<p class=\"ez-toc-title\" style=\"cursor:inherit\">Tabla de contenido<\/p>\n<span class=\"ez-toc-title-toggle\"><a href=\"#\" class=\"ez-toc-pull-right ez-toc-btn ez-toc-btn-xs ez-toc-btn-default ez-toc-toggle\" aria-label=\"Alternar tabla de contenidos\"><span class=\"ez-toc-js-icon-con\"><span class=\"\"><span class=\"eztoc-hide\" style=\"display:none;\">Palanca<\/span><span class=\"ez-toc-icon-toggle-span\"><svg style=\"fill: #999;color:#999\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" class=\"list-377408\" width=\"20px\" height=\"20px\" viewbox=\"0 0 24 24\" fill=\"none\"><path d=\"M6 6H4v2h2V6zm14 0H8v2h12V6zM4 11h2v2H4v-2zm16 0H8v2h12v-2zM4 16h2v2H4v-2zm16 0H8v2h12v-2z\" fill=\"currentColor\"><\/path><\/svg><svg style=\"fill: #999;color:#999\" class=\"arrow-unsorted-368013\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" width=\"10px\" height=\"10px\" viewbox=\"0 0 24 24\" version=\"1.2\" baseprofile=\"tiny\"><path d=\"M18.2 9.3l-6.2-6.3-6.2 6.3c-.2.2-.3.4-.3.7s.1.5.3.7c.2.2.4.3.7.3h11c.3 0 .5-.1.7-.3.2-.2.3-.5.3-.7s-.1-.5-.3-.7zM5.8 14.7l6.2 6.3 6.2-6.3c.2-.2.3-.5.3-.7s-.1-.5-.3-.7c-.2-.2-.4-.3-.7-.3h-11c-.3 0-.5.1-.7.3-.2.2-.3.5-.3.7s.1.5.3.7z\"\/><\/svg><\/span><\/span><\/span><\/a><\/span><\/div>\n<nav><ul class='ez-toc-list ez-toc-list-level-1' ><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-1\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Why_a_stable_display_may_still_be_biased\" >Why a stable display may still be biased<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-2\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Define_electrical_heating_and_thermal_removal_separately\" >Define electrical heating and thermal removal separately<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-3\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Calculate_a_hypothetical_current-and-medium_budget\" >Calculate a hypothetical current-and-medium budget<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-4\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Build_an_evidence_budget_instead_of_a_blanket_offset\" >Build an evidence budget instead of a blanket offset<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-5\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Verify_self-heating_without_assuming_current_is_adjustable\" >Verify self-heating without assuming current is adjustable<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-6\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Ask_WEHO_for_the_input_details_that_close_the_budget\" >Ask WEHO for the input details that close the budget<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-7\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Engineering_FAQ\" >Engineering FAQ<\/a><ul class='ez-toc-list-level-3' ><li class='ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-8\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Does_an_RTD_measure_its_own_temperature_or_the_surrounding_process\" >Does an RTD measure its own temperature or the surrounding process?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-9\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Does_doubling_RTD_measuring_current_double_self-heating\" >Does doubling RTD measuring current double self-heating?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-10\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Can_I_use_a_water-bath_dissipation_value_for_still_air\" >Can I use a water-bath dissipation value for still air?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-11\" href=\"https:\/\/www.wehopower.com\/es\/news\/rtd-self-heating-excitation-budget\/#Can_I_reduce_TX4-W_excitation_current_from_its_front_panel\" >Can I reduce TX4-W excitation current from its front panel?<\/a><\/li><\/ul><\/li><\/ul><\/nav><\/div>\n<h2 id=\"why-a-stable-display-may-still-be-biased\"><span class=\"ez-toc-section\" id=\"Why_a_stable_display_may_still_be_biased\"><\/span>Why a stable display may still be biased<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>An OEM compares two RTD readouts in the same bath and finds a repeatable difference. Replacing the sensor or adding an offset may hide the symptom without explaining whether the element is being heated by the measurement itself. Separate excitation power, thermal dissipation and actual process temperature before changing calibration records.<\/p>\n<p>El <a href=\"https:\/\/www.wehopower.com\/es\/product\/tx4-series-tx4-w-economic-dual-display-pid-temperature-controller\/\">TX4-W temperature-controller reference<\/a> provides the product context for this review. The front display cannot reveal measuring current, probe dissipation or the actual temperature error. Those quantities require the ordered controller documentation and the installed probe&#39;s evidence.<\/p>\n<h2 id=\"define-electrical-heating-and-thermal-removal-separately\"><span class=\"ez-toc-section\" id=\"Define_electrical_heating_and_thermal_removal_separately\"><\/span>Define electrical heating and thermal removal separately<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>An RTD requires excitation to convert resistance into a measurable electrical signal. NI&#39;s <a href=\"https:\/\/www.ni.com\/docs\/en-US\/bundle\/ni-dmm\/page\/resistance-temperature-detector-rtds_7.html\" target=\"_blank\" rel=\"noopener\">RTD measurement documentation<\/a> identifies self-heating as a measurement concern and relates temperature rise to dissipated power and a dissipation constant. The relevant constant describes the probe&#39;s ability to transfer heat into its surroundings.<\/p>\n<p>For a steady approximation, use P = I\u00b2 \u00d7 R and \u0394T = P \/ E. P is the element power, I is the actual measuring current, R is the element resistance at the operating point, and E is the dissipation constant. If P is expressed in milliwatts, E must be expressed in milliwatts per degree Celsius.<\/p>\n<p>Some manufacturers instead state a self-heating coefficient in degrees Celsius per milliwatt. That coefficient multiplies power rather than dividing it; its numerical value is the reciprocal of E under the same conditions. Check the units before importing a supplier value into the calculation.<\/p>\n<figure class=\"article-figure product\" data-asset=\"F08-product\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/es\/product\/tx4-series-tx4-w-economic-dual-display-pid-temperature-controller\/\" aria-label=\"TX4-W details\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/69cdae9f05db9d05-tx4-w-product-reference.webp\" alt=\"RTD Self-Heating: Separate Excitation Error from Process Heat  title=\" width=\"1000\" height=\"1000\" decoding=\"async\" rtd self-heating: separate excitation error from process heat title =\"\"><\/a><figcaption>Product reference for TX4-W; original visible identity is retained. The retained display belongs to the source image; no excitation setting or enclosure IP test is shown. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/33297cd7cf244510-product-original.png\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<p>A dissipation figure measured in moving liquid does not automatically apply to still air or a loosely fitted thermowell. Probe construction, insertion, contact and local flow influence the thermal path. Record the test medium and installation condition beside the figure so that a catalog number does not become a universal correction.<\/p>\n<p>El <a href=\"https:\/\/www.ti.com\/lit\/an\/sbaa275a\/sbaa275a.pdf\" target=\"_blank\" rel=\"noopener\">Texas Instruments RTD measurement guide<\/a> discusses the tradeoff between excitation signal and self-heating. That design principle does not establish the excitation circuit or configurable options of a WEHO controller. Obtain those details separately for the exact ordered unit.<\/p>\n<h2 id=\"calculate-a-hypothetical-current-and-medium-budget\"><span class=\"ez-toc-section\" id=\"Calculate_a_hypothetical_current-and-medium_budget\"><\/span>Calculate a hypothetical current-and-medium budget<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Assume a probe has R = 148 \u03a9 at the operating point. For illustration only, use E = 2.0 mW\/\u00b0C in one qualified liquid installation and E = 0.4 mW\/\u00b0C in a second air installation. These invented thermal values are not TX4-W specifications or ratings of any particular probe.<\/p>\n<p>At 1.0 mA, P = (0.001 A)\u00b2 \u00d7 148 \u03a9 = 0.000148 W, or 0.148 mW. The estimated rise is 0.148 \/ 2.0 = 0.074\u00b0C in the first installation. In the second installation, the same electrical power gives 0.148 \/ 0.4 = 0.370\u00b0C.<\/p>\n<p>Doubling current to 2.0 mA produces 0.592 mW, four times the original power. The corresponding rises become 0.296\u00b0C and 1.480\u00b0C. Halving current to 0.5 mA gives 0.037 mW, yielding 0.0185\u00b0C and 0.0925\u00b0C respectively.<\/p>\n<p>Suppose the project allocates at most 0.10\u00b0C to steady self-heating at this point. Under these assumptions, the 1.0 mA liquid case fits that allocation while the 1.0 mA air case does not. This is only a component of an uncertainty budget; meeting it does not establish total measurement accuracy.<\/p>\n<figure class=\"article-figure technical\" data-asset=\"F08-technical\">\n<div class=\"diagram-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering diagram\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/c09832126de598b2-rtd-self-heating-engineering-example.svg\" alt=\"RTD Self-Heating: Separate Excitation Error from Process Heat  title=\" width=\"1200\" height=\"675\" decoding=\"async\" rtd self-heating: separate excitation error from process heat title =\"\"><\/div><figcaption>Conceptual Engineering Diagram. Calculated steady self-heating at assumed 148 \u03a9, three currents and two dissipation constants. Thermal values are hypothetical; no TX4 excitation setting or measured probe performance is shown. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/c09832126de598b2-rtd-self-heating-engineering-example.svg\" target=\"_blank\" rel=\"noopener\">Open full-size diagram<\/a><\/figcaption><p class=\"figure-help\">Swipe horizontally on a small screen, or open the full-size diagram.<\/p>\n<\/figure>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<caption>Hypothetical steady estimates at 148 \u03a9; dissipation assumptions must match the installation<\/caption>\n<thead>\n<tr>\n<th scope=\"col\">Excitation current<\/th>\n<th scope=\"col\">Element power<\/th>\n<th scope=\"col\">Rise at 2.0 mW\/\u00b0C<\/th>\n<th scope=\"col\">Rise at 0.4 mW\/\u00b0C<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>0.5 mA<\/td>\n<td>0.037 mW<\/td>\n<td>0.0185\u00b0C<\/td>\n<td>0.0925\u00b0C<\/td>\n<\/tr>\n<tr>\n<td>1.0 mA<\/td>\n<td>0.148 mW<\/td>\n<td>0.0740\u00b0C<\/td>\n<td>0.3700\u00b0C<\/td>\n<\/tr>\n<tr>\n<td>2.0 mA<\/td>\n<td>0.592 mW<\/td>\n<td>0.2960\u00b0C<\/td>\n<td>1.4800\u00b0C<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>The table also explains why a satisfactory bath comparison may not transfer to the machine&#39;s actual sensing pocket. The electrical circuit can remain unchanged while the thermal path becomes weaker. Reproduce the intended mounting and medium before using a self-heating estimate as a release criterion.<\/p>\n<h2 id=\"build-an-evidence-budget-instead-of-a-blanket-offset\"><span class=\"ez-toc-section\" id=\"Build_an_evidence_budget_instead_of_a_blanket_offset\"><\/span>Build an evidence budget instead of a blanket offset<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Self-heating is one possible positive element-temperature bias, not a universal explanation for a high display reading. Curve selection, lead effects, sensor tolerance, input electronics, reference uncertainty and thermal gradients can all contribute. Beckhoff&#39;s <a href=\"https:\/\/infosys.beckhoff.com\/content\/1033\/ioanalogmanual\/12917476107.html\" target=\"_blank\" rel=\"noopener\">RTD self-heating explanation<\/a> provides another manufacturer treatment of the excitation effect without establishing the characteristics of a TX4 input.<\/p>\n<p>Use the maximum relevant sensor resistance and actual excitation behavior over the operating range. Where excitation is pulsed or changes during conversion, a constant-current steady estimate may be insufficient. Record the waveform information supplied by the input manufacturer and ask whether the probe&#39;s thermal response makes average, peak or another documented treatment appropriate.<\/p>\n<p>El <a href=\"https:\/\/www.wehopower.com\/es\/news\/weho-b2b-395-tx4-temperature-controller-with-k-type-thermocouple\/\">TX4-S measurement-chain article<\/a> addresses thermocouples rather than RTD excitation. Keep its reference-chain discipline, but do not transfer thermocouple compensation rules to a resistance sensor. Document which error mechanism each verification step actually tests.<\/p>\n<h2 id=\"verify-self-heating-without-assuming-current-is-adjustable\"><span class=\"ez-toc-section\" id=\"Verify_self-heating_without_assuming_current_is_adjustable\"><\/span>Verify self-heating without assuming current is adjustable<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<ol>\n<li><strong>Identify the input and probe.<\/strong> Record the complete controller configuration, RTD curve, connection and probe part number. Confirm their compatibility using the applicable instructions; the <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2023\/11\/TX4.pdf\">TX4 series manual<\/a> is a starting point rather than evidence of an adjustable measuring-current parameter.<\/li>\n<li><strong>Obtain excitation evidence.<\/strong> Request the applicable measuring-current value, tolerance and any pulsed behavior. Record the manufacturer&#39;s stated conditions, then verify that the information applies to the actual input mode instead of borrowing a value from another instrument.<\/li>\n<li><strong>Obtain thermal evidence.<\/strong> Record the probe&#39;s dissipation specification, medium, immersion and flow conditions. If the process installation differs, obtain relevant supplier data or plan a qualified comparison rather than treating the catalog value as installed performance.<\/li>\n<li><strong>Calculate the allocation.<\/strong> Record current, resistance, units and the selected dissipation basis. Compare the resulting contribution with the project&#39;s allotted uncertainty at each relevant operating condition; retain the other error contributions separately.<\/li>\n<li><strong>Validate the assembled arrangement.<\/strong> Record stabilized reference and controller readings under the intended thermal conditions. Where an approved external instrument supports multiple excitation currents, a specialist may compare current-dependent readings under a defined procedure; this is not an instruction to alter unsupported TX4 settings.<\/li>\n<\/ol>\n<p>A current-dependent comparison needs a stable reference and repeatable thermal conditions. Changing instruments can also change lead compensation, conversion curves and input accuracy, so a difference between instruments cannot automatically be attributed entirely to self-heating. Control or quantify those influences before drawing the conclusion.<\/p>\n<p>Do not use a fitted offset to compensate for a variable thermal path without establishing its range of validity. A correction obtained at one flow rate, insertion depth or temperature can fail elsewhere. The useful release record identifies both the accepted arrangement and the conditions that require reassessment.<\/p>\n<h2 id=\"ask-weho-for-the-input-details-that-close-the-budget\"><span class=\"ez-toc-section\" id=\"Ask_WEHO_for_the_input_details_that_close_the_budget\"><\/span>Ask WEHO for the input details that close the budget<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Send the <a href=\"https:\/\/www.wehopower.com\/es\/product\/tx4-series-tx4-w-economic-dual-display-pid-temperature-controller\/\">TX4-W input configuration enquiry<\/a> with the complete unit label, RTD curve, probe construction, operating range and installation medium. Include the allocated self-heating error and ask for the applicable excitation information. Provide the probe supplier&#39;s dissipation evidence so that the electrical and thermal assumptions can be evaluated together.<\/p>\n<h2 id=\"engineering-faq\"><span class=\"ez-toc-section\" id=\"Engineering_FAQ\"><\/span>Engineering FAQ<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<h3 id=\"does-an-rtd-measure-its-own-temperature-or-the-surrounding-process\"><span class=\"ez-toc-section\" id=\"Does_an_RTD_measure_its_own_temperature_or_the_surrounding_process\"><\/span>Does an RTD measure its own temperature or the surrounding process?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>An RTD responds to its element temperature, which can differ from the surrounding process. Excitation heating and the thermal path both influence that difference. Appropriate installation and an uncertainty budget are needed to interpret the reported temperature.<\/p>\n<h3 id=\"does-doubling-rtd-measuring-current-double-self-heating\"><span class=\"ez-toc-section\" id=\"Does_doubling_RTD_measuring_current_double_self-heating\"><\/span>Does doubling RTD measuring current double self-heating?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>Doubling current quadruples I\u00b2R power when resistance is held constant. The resulting temperature rise also depends on heat dissipation and the validity of the thermal model. A change in medium can matter as much as a change in current.<\/p>\n<h3 id=\"can-i-use-a-water-bath-dissipation-value-for-still-air\"><span class=\"ez-toc-section\" id=\"Can_I_use_a_water-bath_dissipation_value_for_still_air\"><\/span>Can I use a water-bath dissipation value for still air?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>Only use that value if its applicability to the air installation is established. Different heat-transfer conditions can produce a different temperature rise for the same electrical power. Obtain installation-relevant evidence rather than copying the more favorable figure.<\/p>\n<h3 id=\"can-i-reduce-tx4-w-excitation-current-from-its-front-panel\"><span class=\"ez-toc-section\" id=\"Can_I_reduce_TX4-W_excitation_current_from_its_front_panel\"><\/span>Can I reduce TX4-W excitation current from its front panel?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>Do not assume an adjustable excitation setting is available. Confirm the applicable input configuration and instructions for the ordered unit. If adjustment is not documented, assess the supported input and probe arrangement rather than inventing a parameter change.<\/p>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>Calculate RTD self-heating from excitation current and dissipation, then send WEHO your TX4-W input and probe details to assess the installed error budget.<\/p>","protected":false},"author":2,"featured_media":22218,"parent":0,"menu_order":3,"comment_status":"","ping_status":"","template":"","format":"standard","meta":{"_acf_changed":false,"_joinchat":[],"footnotes":""},"news_category":[284],"class_list":["post-22665","news","type-news","status-publish","format-standard","has-post-thumbnail","hentry","news_category-product-articles","entry"],"acf":[],"post_mailing_queue_ids":[],"_links":{"self":[{"href":"https:\/\/www.wehopower.com\/es\/wp-json\/wp\/v2\/news\/22665","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.wehopower.com\/es\/wp-json\/wp\/v2\/news"}],"about":[{"href":"https:\/\/www.wehopower.com\/es\/wp-json\/wp\/v2\/types\/news"}],"author":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/es\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/es\/wp-json\/wp\/v2\/comments?post=22665"}],"version-history":[{"count":0,"href":"https:\/\/www.wehopower.com\/es\/wp-json\/wp\/v2\/news\/22665\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/es\/wp-json\/wp\/v2\/media\/22218"}],"wp:attachment":[{"href":"https:\/\/www.wehopower.com\/es\/wp-json\/wp\/v2\/media?parent=22665"}],"wp:term":[{"taxonomy":"news_category","embeddable":true,"href":"https:\/\/www.wehopower.com\/es\/wp-json\/wp\/v2\/news_category?post=22665"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}