UVLO Chatter: Check Rising and Falling Thresholds with the Load

60bea74f3923e2e9 mdr 60 12 application

Undervoltage lockout needs separate rising and falling thresholds, evaluated at the protected circuit under its actual load. A source can recover when a load disconnects and collapse again when it reconnects, creating repeated starts instead of a stable operating state.

Key Engineering Takeaways

  • Record the protected circuit's actual threshold definitions.
  • Include the voltage drop created by its starting current.
  • Keep threshold chatter separate from control-loop oscillation.
  • Do not expect hysteresis to repair an inadequate source path.
MDR-60-12 product installed in an industrial application scene with original housing and label details.
Application illustration of MDR-60-12 in an equipment setting; not a customer installation photo. Scene created with AI assistance. View original-resolution image

1. Identify which circuit is making the decision

A cabinet may contain a source, distribution wiring and a downstream board with its own undervoltage qualification. When the board repeatedly starts and stops, identify which device is switching and which voltage it observes. An indicator on the upstream supply does not reveal the downstream threshold state or its local voltage.

Le WEHO MDR-60-12 product reference identifies an upstream source context. The following thresholds belong to an invented downstream interface model, not to the MDR. Obtain the exact supply and receiving-device documentation before attributing a repeated startup to either product.

Analog Devices explains UVLO threshold hysteresis in power-path control circuits. Supply noise or resistance can cause repeated switching near a qualification threshold. Hysteresis introduces different turn-on and turn-off conditions, but their values and operation remain specific to the selected circuit.

2. Keep three mechanisms separate

Threshold chatter is a state-transition problem: the circuit qualifies input, connects a load, sees a lower voltage and removes that load. The unloaded source then recovers enough to qualify again. Establish that sequence from appropriate observations rather than calling every repeated waveform a defective regulator.

A converter's dynamic interaction with a resonant input network is a different problem. The existing input-filter resonance guide concerns frequency-dependent source and converter behavior. A DC load-line calculation does not replace that analysis when sustained oscillation or a filter interaction is suspected.

Likewise, a programmed soft-start function does not establish a suitable undervoltage window. Analog Devices AN-44 treats undervoltage lockout and its hysteresis as explicit design functions in a named regulator. Its component calculations do not transfer to a finished WEHO supply or an undocumented downstream board.

Observed behavior Primary question Record to preserve What is insufficient
Repeated connect/disconnect Does loaded voltage cross the falling threshold? Local input, current and qualification state One upstream voltage reading
Continuous oscillation Does the network interact dynamically? Relevant voltage/current waveforms and network model Only a static resistance estimate
One slow startup Does the intended ramp complete correctly? Input event, ramp and ready conditions Threshold names alone
No start Was the rising qualification condition reached? Actual threshold, voltage and control conditions Nominal source label

TI's UVLO explanation explicitly relates source resistance, current and qualification behavior. Those circuit principles do not assign a universal threshold to a finished supply. For the actual receiver, request its own input range, qualification behavior, tolerances and startup conditions. A regulator's normal operating range and its lockout thresholds need not describe identical boundaries.

3. Recalculate a hypothetical weak-source case

Assume a generic branch can be represented by an ideal 12.0 V source and 0.60 Ω total series resistance. Assume its downstream qualification turns on at 11.0 V and turns off at 10.0 V. Ignore delays, capacitance, current limiting and converter dynamics for this static screening example.

Assume the disconnected load draws negligible current, so its input approaches 12.0 V and exceeds the rising threshold. After connection, an assumed 4.0 A starting demand produces a path drop of 4.0 × 0.60 = 2.40 V. The protected input becomes 12.0 − 2.40 = 9.60 V, below the assumed falling threshold.

If that condition makes the interface disconnect, the current falls and the input can return toward 12.0 V. The two states can therefore repeat. This model identifies a possible mechanism; it does not predict a retry period, establish actual device behavior or describe an MDR-60-12 test.

Hypothetical source load line crosses assumed qualification thresholds at different downstream current demands.
Conceptual Engineering Diagram. Assumed 12V source, 0.60Ω path and 11V/10V external thresholds illustrate static state qualification. No MDR lockout value or retry timing is assigned. Open full-size diagram

Swipe horizontally on a small screen, or open the full-size diagram.

For an assumed sustained 2.0 A demand, the same path gives 12.0 − 2.0 × 0.60 = 10.80 V. That voltage lies below the rising threshold but above the falling threshold. A circuit already on can remain qualified under the assumed hysteresis rules, while a circuit initially off still needs to meet its rising condition.

The maximum current that keeps this simplified branch exactly at the assumed falling threshold is (12.0 − 10.0)/0.60 ≈ 3.33 A. This is a model boundary with no margin, not an acceptable design current or product rating. Real tolerances and dynamic behavior can move the result.

4. Interpret the hysteresis window without hiding the supply problem

The assumed hysteresis is 11.0 − 10.0 = 1.0 V. Increasing that window might change the state behavior, but it cannot create input energy or remove the series-path loss. A proposed lower turn-off threshold must remain compatible with the protected circuit's permitted operation and the governing equipment design.

Do not change a protection threshold merely to suppress an unexplained restart. First determine whether the source, conductors, contacts, startup demand and receiving circuit meet their documented conditions. The appropriate remedy could involve the load profile or distribution path rather than the threshold network.

Assumed condition Actuel Calculated local input State implication in this model
Disconnected Approximately zero Approximately 12.0 V Above 11.0 V rising threshold
Starting demand 4.0 A 9.60 V Below 10.0 V falling threshold
Sustained demand 2.0 A 10.80 V Above falling threshold after qualification
Mathematical boundary Approximately 3.33 A 10.0 V No margin; not a released operating limit

The existing DC-DC soft-start guide helps when specifying a controlled startup ramp and upstream current. Keep that task distinct from defining the receiver's rising and falling qualification. Combining both functions requires their actual documented timing and operating conditions.

MDR-60-12 product reference preserving the original housing, visible label and connection features.
Product appearance reference for MDR-60-12, preserving the source housing, visible label and connections. View original-resolution image

5. Produce a threshold-and-load validation record

  1. Identify the switching owner. Record the source, downstream interface, relevant control states and exact revisions. Verify which circuit observes the voltage and initiates disconnection or retry.
  2. Obtain both thresholds. Record rising/falling definitions, tolerances, delay behavior and reset rules. Verify them against the receiving circuit's own documentation rather than a similar product example.
  3. Describe the source path. Record supply conditions, conductor/contact arrangement and load-current profile. Verify voltage at the protected input during startup as well as sustained operation.
  4. Compare state transitions. Record local voltage, current, qualification state and timestamps with an appropriate common observation method. Verify whether each transition matches the declared threshold behavior.
  5. Release a controlled correction. Record the proposed change, affected operating corners and acceptance basis. Verify startup, recovery and sustained operation after that change without erasing the original finding.

Include the tolerance corners that the real design requires. As an additional invented case, assume the source falls to 11.8 V, path resistance rises to 0.70 Ω and the receiver turns off at 10.2 V. At 2.0 A the calculated local input is 11.8 − 2.0 × 0.70 = 10.4 V, leaving only 0.2 V against that assumed falling threshold.

That small margin is different from the nominal model’s 0.8 V at 2.0 A. It demonstrates why a release calculation needs the applicable source, path and receiver bounds together. It does not prove that any particular tolerance combination can occur, and it is not a replacement for dynamic startup evidence.

Slow input ramps, noisy crossings and source recovery can expose different behaviors. Select cases from the equipment's real operating envelope and the applicable instructions. There is no universal ramp slope or number of retries that makes an undocumented interface acceptable.

6. Send the local-input evidence with the inquiry

For an MDR-60-12 downstream-interface review, send the exact source and receiver identities, input conditions, distribution diagram, starting/sustained current and local voltage traces. Include the receiver's threshold definitions and the observed control state. Ask for the product documentation needed to evaluate the source boundary while the equipment designer qualifies the complete interface.

7. Engineering FAQ

Are the 11.0 V and 10.0 V thresholds MDR-60-12 specifications?

No. They are assumptions for an external-interface calculation. Use the actual device documents for any real rising or falling threshold.

Can a load remain on below its turn-on threshold?

Yes, under a documented hysteresis scheme it can remain on above its lower turn-off threshold. Confirm the selected circuit's actual rules and permitted operating range.

Does a wider hysteresis band fix an inadequate source?

No. It changes qualification behavior but does not remove source-path loss or supply the missing power. Evaluate the source and load together before changing thresholds.

Does the example predict a retry frequency?

No. Delays, capacitance, source control and load dynamics were omitted. Measure or model those factors before making a timing claim.