{"id":22002,"date":"2026-11-14T10:54:56","date_gmt":"2026-11-14T02:54:56","guid":{"rendered":"https:\/\/www.wehopower.com\/news\/tx4-h-on-off-hysteresis-return-value\/"},"modified":"2026-11-14T10:54:56","modified_gmt":"2026-11-14T02:54:56","slug":"tx4-h-on-off-hysteresis-return-value","status":"publish","type":"news","link":"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/","title":{"rendered":"TX4-H ON\/OFF Hysteresis: Check the Return-Value Mode"},"content":{"rendered":"<p><strong>Key Engineering Takeaways<\/strong><\/p>\n<ul>\n<li>TX4-H ON\/OFF return value defines a temperature switching band, not a time interval.<\/li>\n<li>The TX4 manual shows the oH parameter only when control type Pid is OFF.<\/li>\n<li>In the manual&#39;s HEAT diagram, the nominal ON boundary is SV \u2212 oH and the OFF boundary is SV.<\/li>\n<li>Keep control hysteresis, PID control cycle and alarm return difference separate.<\/li>\n<\/ul>\n<figure class=\"article-figure hero\" data-asset=\"hero\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/fr\/product\/tx4-series-tx4-h-economic-dual-display-pid-temperature-controller\/\" aria-label=\"TX4-H details\"><img fetchpriority=\"high\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/tx4-h-on-off-hysteresis-application-d8e2d5d82c.avif\" alt=\"TX4-H ON\/OFF Hysteresis: Check the Return-Value Mode  title=\" width=\"1200\" height=\"675\" loading=\"eager\" decoding=\"async\" tx4-h><\/a><figcaption>Application illustration; not a customer installation photo. Scene created with AI assistance. Original display values are retained and are not a measured hysteresis test. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/source-tx4-h-on-off-hysteresis-application-1200x675-master-1951978a.png\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<div id=\"ez-toc-container\" class=\"ez-toc-v2_0_89 counter-hierarchy ez-toc-counter ez-toc-grey ez-toc-container-direction\">\n<div class=\"ez-toc-title-container\">\n<p class=\"ez-toc-title\" style=\"cursor:inherit\">Table des mati\u00e8res<\/p>\n<span class=\"ez-toc-title-toggle\"><a href=\"#\" class=\"ez-toc-pull-right ez-toc-btn ez-toc-btn-xs ez-toc-btn-default ez-toc-toggle\" aria-label=\"Toggle Table of Content\"><span class=\"ez-toc-js-icon-con\"><span class=\"\"><span class=\"eztoc-hide\" style=\"display:none;\">Basculer<\/span><span class=\"ez-toc-icon-toggle-span\"><svg style=\"fill: #999;color:#999\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" class=\"list-377408\" width=\"20px\" height=\"20px\" viewbox=\"0 0 24 24\" fill=\"none\"><path d=\"M6 6H4v2h2V6zm14 0H8v2h12V6zM4 11h2v2H4v-2zm16 0H8v2h12v-2zM4 16h2v2H4v-2zm16 0H8v2h12v-2z\" fill=\"currentColor\"><\/path><\/svg><svg style=\"fill: #999;color:#999\" class=\"arrow-unsorted-368013\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" width=\"10px\" height=\"10px\" viewbox=\"0 0 24 24\" version=\"1.2\" baseprofile=\"tiny\"><path d=\"M18.2 9.3l-6.2-6.3-6.2 6.3c-.2.2-.3.4-.3.7s.1.5.3.7c.2.2.4.3.7.3h11c.3 0 .5-.1.7-.3.2-.2.3-.5.3-.7s-.1-.5-.3-.7zM5.8 14.7l6.2 6.3 6.2-6.3c.2-.2.3-.5.3-.7s-.1-.5-.3-.7c-.2-.2-.4-.3-.7-.3h-11c-.3 0-.5.1-.7.3-.2.2-.3.5-.3.7s.1.5.3.7z\"\/><\/svg><\/span><\/span><\/span><\/a><\/span><\/div>\n<nav><ul class='ez-toc-list ez-toc-list-level-1' ><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-1\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#Why_can_the_return-value_setting_disappear\" >Why can the return-value setting disappear?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-2\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#What_does_Pid_OFF_mean_in_this_context\" >What does Pid = OFF mean in this context?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-3\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#How_does_the_temperature_band_affect_switching\" >How does the temperature band affect switching?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-4\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#Which_TX4_parameters_should_not_be_confused_with_oH\" >Which TX4 parameters should not be confused with oH?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-5\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#How_can_the_band_be_verified_without_inventing_a_process_tolerance\" >How can the band be verified without inventing a process tolerance?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-6\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#What_should_be_retained_for_maintenance_and_replacement\" >What should be retained for maintenance and replacement?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-7\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#What_information_should_be_sent_to_WEHO\" >What information should be sent to WEHO?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-8\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#Engineering_FAQ\" >Engineering FAQ<\/a><ul class='ez-toc-list-level-3' ><li class='ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-9\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#Does_Pid_OFF_disable_the_control_output\" >Does Pid = OFF disable the control output?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-10\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#Why_can_the_same_temperature_have_two_output_states\" >Why can the same temperature have two output states?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-11\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#Is_oH_the_same_as_the_PID_control_cycle\" >Is oH the same as the PID control cycle?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-12\" href=\"https:\/\/www.wehopower.com\/fr\/news\/tx4-h-on-off-hysteresis-return-value\/#Can_a_published_band_replace_an_actual_switching_check\" >Can a published band replace an actual switching check?<\/a><\/li><\/ul><\/li><\/ul><\/nav><\/div>\n<h2 id=\"why-can-the-return-value-setting-disappear\"><span class=\"ez-toc-section\" id=\"Why_can_the_return-value_setting_disappear\"><\/span>Why can the return-value setting disappear?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>The setting can be hidden because the controller is configured for PID rather than ON\/OFF control. The missing parameter is therefore a reason to check the selected control type before assuming a display problem or restoring factory settings.<\/p>\n<p>For an OEM using the <a href=\"https:\/\/www.wehopower.com\/fr\/product\/tx4-series-tx4-h-economic-dual-display-pid-temperature-controller\/\">TX4-H temperature-controller settings<\/a>, the task is to establish the required ON\/OFF switching band and verify its behavior. A temperature band answers a different question from the duration of an output cycle. Confusing them can produce a setting that has the right-looking number but the wrong physical meaning.<\/p>\n<p>Record the actual input, units, control type and heating\/cooling selection before changing anything. A parameter that is appropriate for one configuration may be hidden or serve a different purpose in another.<\/p>\n<h2 id=\"what-does-pid-off-mean-in-this-context\"><span class=\"ez-toc-section\" id=\"What_does_Pid_OFF_mean_in_this_context\"><\/span>What does Pid = OFF mean in this context?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Le <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2023\/11\/TX4.pdf\">TX4 instruction manual, revision TX4 230808EN<\/a>, identifies control type Pid with ON for PID control and OFF for ON\/OFF control. Its ON\/OFF Return Value section states that oH is displayed when Pid is OFF.<\/p>\n<p>Here, OFF refers to the PID-control selection. It does not mean that the controller is electrically isolated, that its output is permanently disabled or that the process load cannot operate. ON\/OFF control remains an operating mode with a switching response.<\/p>\n<p>The manual describes oH as setting the interval between ON and OFF. Its HEAT diagram places the OFF boundary at SV and the ON boundary below SV by oH. Use that documented heating relationship for the example below; do not transfer it to an unverified cooling configuration.<\/p>\n<p>The front form alone does not establish the complete electrical option. Match the installed controller code, output selection and applicable connection information before testing the receiving circuit.<\/p>\n<figure class=\"article-figure product\" data-asset=\"product\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/fr\/product\/tx4-series-tx4-h-economic-dual-display-pid-temperature-controller\/\" aria-label=\"TX4-H details\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/tx4-h-product-reference-40877adff6.avif\" alt=\"TX4-H ON\/OFF Hysteresis: Check the Return-Value Mode  title=\" width=\"1000\" height=\"1000\" decoding=\"async\" tx4-h><\/a><figcaption>Official TX4-H product photograph. Original product markings are retained; configuration and operating claims require the applicable product documentation. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/source-tx4-h-official-1f45df67.png\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<h2 id=\"how-does-the-temperature-band-affect-switching\"><span class=\"ez-toc-section\" id=\"How_does_the_temperature_band_affect_switching\"><\/span>How does the temperature band affect switching?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>A band separates the point that turns heating OFF from the lower point that turns it ON again. Between the boundaries, the output state depends on the direction of travel and the preceding state. That state memory distinguishes hysteresis from a single instantaneous comparison with SV.<\/p>\n<p>Use a <strong>Hypothetical Heating-Band Example<\/strong>. Assume SV is 100\u00b0C and oH is 2\u00b0C. Following the manual&#39;s HEAT diagram, the nominal boundaries are:<\/p>\n<p>ON boundary = SV \u2212 oH = 100\u00b0C \u2212 2\u00b0C = 98\u00b0C.<\/p>\n<p>OFF boundary = SV = 100\u00b0C.<\/p>\n<p>These are illustrative diagram calculations, not measured TX4-H switching points or an approved process tolerance. Measurement accuracy, thermal lag and the complete equipment response still affect the actual process behavior.<\/p>\n<p>If heating was ON while temperature rose from below the lower boundary, the diagram keeps it ON until the upper boundary is reached. If heating was OFF while temperature fell from above the upper boundary, the diagram keeps it OFF until the lower boundary is reached. A reading of 99\u00b0C can therefore coexist with either prior state in this idealized example.<\/p>\n<p>That is not a contradiction. The 99\u00b0C reading lies within the band, where the preceding state matters. The commissioning record should include the direction of temperature travel rather than treating one static reading as a complete switching test.<\/p>\n<h2 id=\"which-tx4-parameters-should-not-be-confused-with-oh\"><span class=\"ez-toc-section\" id=\"Which_TX4_parameters_should_not_be_confused_with_oH\"><\/span>Which TX4 parameters should not be confused with oH?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Use the parameter&#39;s physical quantity to identify its purpose. Similar terms such as cycle, return and difference do not make the settings interchangeable.<\/p>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">Param\u00e8tre<\/th>\n<th scope=\"col\">Role<\/th>\n<th scope=\"col\">Relevant condition<\/th>\n<th scope=\"col\">Separate verification<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>oH, ON\/OFF return value<\/td>\n<td>Temperature band between ON and OFF<\/td>\n<td>Shown when Pid is OFF<\/td>\n<td>Switching boundaries and direction of travel<\/td>\n<\/tr>\n<tr>\n<td>t, control cycle<\/td>\n<td>Time basis of PID output cycling<\/td>\n<td>Applicable PID configuration<\/td>\n<td>Output timing and receiving-device suitability<\/td>\n<\/tr>\n<tr>\n<td>AH1\/AH2<\/td>\n<td>Alarm return differences<\/td>\n<td>Applicable alarm configuration<\/td>\n<td>Alarm action and release behavior<\/td>\n<\/tr>\n<tr>\n<td>SV<\/td>\n<td>Requested control setpoint<\/td>\n<td>Configured unit and permitted range<\/td>\n<td>Effective recipe value after changes<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>Do not enter a number of seconds into a temperature-band decision. A 2\u00b0C return value and a 2 s control cycle have different units and functions even though the displayed numeral can look similar.<\/p>\n<p>An alarm that releases at a different temperature also does not prove the control output uses that same band. Test the controller output and the relevant alarm as their own functions when the equipment requires both.<\/p>\n<figure class=\"article-figure technical\" data-asset=\"technical\">\n<div class=\"diagram-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering diagram\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/tx4-h-on-off-hysteresis-9a96ae1cac.svg\" alt=\"TX4-H ON\/OFF Hysteresis: Check the Return-Value Mode  title=\" width=\"1200\" height=\"675\" decoding=\"async\" tx4-h><\/div><figcaption>Conceptual Engineering Diagram. The hypothetical 98\u2013100\u00b0C heating band illustrates prior-state dependence; actual switching points require verification. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/source-tx4-h-on-off-hysteresis-9a96ae1c.svg\" target=\"_blank\" rel=\"noopener\">Open full-size diagram<\/a><\/figcaption><p class=\"figure-help\">Swipe horizontally on a small screen, or open the full-size diagram.<\/p>\n<\/figure>\n<h2 id=\"how-can-the-band-be-verified-without-inventing-a-process-tolerance\"><span class=\"ez-toc-section\" id=\"How_can_the_band_be_verified_without_inventing_a_process_tolerance\"><\/span>How can the band be verified without inventing a process tolerance?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<ol>\n<li>Record the complete controller marking, manual revision, input, unit, SV, control type, heating\/cooling selection and output selection.<\/li>\n<li>Obtain the required process band and permissible switching behavior from the equipment specification. Confirm that ON\/OFF control is the intended method before selecting Pid = OFF.<\/li>\n<li>Read the oH setting and calculate the nominal heating boundaries from the applicable diagram. Keep the calculated values separate from measurements.<\/li>\n<li>Use an approved simulated input or controlled thermal sequence. Observe output changes during both rising and falling conditions, including the actual receiving device where appropriate.<\/li>\n<li>Record the input or reference value, direction, output transition and relevant measurement uncertainty. Compare them with the stated acceptance requirement.<\/li>\n<li>Restore and read back the released configuration. Resolve unexpected behavior before normal process operation resumes.<\/li>\n<\/ol>\n<p>Avoid changing an active process from PID to ON\/OFF solely to reveal a menu item. That change alters the control method. Manage output permission and process energy through the machine commissioning procedure, using qualified personnel for electrical work.<\/p>\n<p>A narrow band can produce frequent changes when the measured temperature fluctuates across its boundaries. A wider band changes the permitted control behavior. Neither observation supplies a universal best setting; the process, receiver and required temperature performance determine the acceptable choice.<\/p>\n<h2 id=\"what-should-be-retained-for-maintenance-and-replacement\"><span class=\"ez-toc-section\" id=\"What_should_be_retained_for_maintenance_and_replacement\"><\/span>What should be retained for maintenance and replacement?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Retain control type with the oH value. A maintenance record that lists only \u201creturn value = 2\u201d leaves out its units, applicable mode and intended behavior. Include SV, heating\/cooling selection, output interface and the observed rising\/falling sequence.<\/p>\n<p>Le <a href=\"https:\/\/www.wehopower.com\/fr\/product\/tx4-series-tx4-h-economic-dual-display-pid-temperature-controller\/\">TX4-H control-mode information<\/a> is the relevant product reference for this review. The parameter record and actual installed code should accompany a replacement so a similar front panel does not conceal a different configuration.<\/p>\n<p>Use the <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/on-off-hysteresis-check.csv\">ON\/OFF hysteresis worksheet<\/a> to keep nominal boundaries and actual observations separate. The blank fields require commissioning evidence; the worked 100\u00b0C\/2\u00b0C example does not qualify a particular machine.<\/p>\n<h2 id=\"what-information-should-be-sent-to-weho\"><span class=\"ez-toc-section\" id=\"What_information_should_be_sent_to_WEHO\"><\/span>What information should be sent to WEHO?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Send the complete TX4-H marking, manual revision and settings for Pid, HC, SV, oH and output selection. If oH is not visible, describe the current mode and the menu sequence. If switching is unexpected, include the direction of temperature travel, actual transitions and receiving-device behavior.<\/p>\n<p><a href=\"https:\/\/www.wehopower.com\/fr\/contact\/\">Contact WEHO about the TX4-H return value<\/a> with that record. Ask for clarification of the applicable parameter behavior while keeping the process band and machine acceptance criteria with the responsible engineering team.<\/p>\n<h2 id=\"engineering-faq\"><span class=\"ez-toc-section\" id=\"Engineering_FAQ\"><\/span>Engineering FAQ<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<h3 id=\"does-pid-off-disable-the-control-output\"><span class=\"ez-toc-section\" id=\"Does_Pid_OFF_disable_the_control_output\"><\/span>Does Pid = OFF disable the control output?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>In the cited TX4 parameter table, Pid = OFF selects ON\/OFF control. It is not an electrical isolation instruction or a guarantee that the output remains inactive.<\/p>\n<h3 id=\"why-can-the-same-temperature-have-two-output-states\"><span class=\"ez-toc-section\" id=\"Why_can_the_same_temperature_have_two_output_states\"><\/span>Why can the same temperature have two output states?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>Inside a hysteresis band, the preceding state and direction of travel matter. In the hypothetical 98\u2013100\u00b0C heating band, 99\u00b0C can occur while heating remains ON during a rise or OFF during a fall.<\/p>\n<h3 id=\"is-oh-the-same-as-the-pid-control-cycle\"><span class=\"ez-toc-section\" id=\"Is_oH_the_same_as_the_PID_control_cycle\"><\/span>Is oH the same as the PID control cycle?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>oH defines an ON\/OFF temperature interval, while the PID control cycle concerns output timing. Keep the physical quantities and units separate when writing the machine parameter record.<\/p>\n<h3 id=\"can-a-published-band-replace-an-actual-switching-check\"><span class=\"ez-toc-section\" id=\"Can_a_published_band_replace_an_actual_switching_check\"><\/span>Can a published band replace an actual switching check?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>A diagram establishes the intended relationship. Verify the actual configured controller, receiving device and process requirements using the appropriate measurement conditions. A calculated band is not a test result.<\/p>","protected":false},"excerpt":{"rendered":"<p>Check TX4-H ON\/OFF return value and why it is hidden in PID mode. Compare the switching band, then send WEHO your settings and observed temperature points.<\/p>","protected":false},"author":2,"featured_media":21975,"parent":0,"menu_order":44,"comment_status":"","ping_status":"","template":"","format":"standard","meta":{"_acf_changed":false,"_joinchat":[],"footnotes":""},"news_category":[284],"class_list":["post-22002","news","type-news","status-publish","format-standard","has-post-thumbnail","hentry","news_category-product-articles","entry"],"acf":[],"post_mailing_queue_ids":[],"_links":{"self":[{"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/news\/22002","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/news"}],"about":[{"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/types\/news"}],"author":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/comments?post=22002"}],"version-history":[{"count":0,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/news\/22002\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/media\/21975"}],"wp:attachment":[{"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/media?parent=22002"}],"wp:term":[{"taxonomy":"news_category","embeddable":true,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/news_category?post=22002"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}