{"id":22664,"date":"2026-11-18T10:19:31","date_gmt":"2026-11-18T02:19:31","guid":{"rendered":"https:\/\/www.wehopower.com\/news\/pt100-jpt100-curve-replacement\/"},"modified":"2026-11-18T10:19:31","modified_gmt":"2026-11-18T02:19:31","slug":"pt100-jpt100-curve-replacement","status":"publish","type":"news","link":"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/","title":{"rendered":"Pt100 vs JPt100: Verify the RTD Curve Before Replacement"},"content":{"rendered":"<div class=\"weho-blog\">\n<div class=\"key-takeaways\"><strong>Key Engineering Takeaways<\/strong><\/p>\n<ul>\n<li>Pt100 and JPt100 can both measure 100 \u03a9 at 0\u00b0C while requiring different resistance-to-temperature curves.<\/li>\n<li>A correct ice-point reading cannot establish compatibility across the operating range.<\/li>\n<li>Match the probe curve, controller input selection and applicable instructions before replacing an RTD.<\/li>\n<li>The current TX4 manual lists Pt100 and Cu50; JPt100 compatibility requires separate confirmation.<\/li>\n<\/ul>\n<\/div>\n<figure class=\"article-figure hero\" data-asset=\"F07-hero\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/fr\/product\/tx4-series-tx4-s-economic-dual-display-pid-temperature-controller\/\" aria-label=\"TX4-S details\"><img fetchpriority=\"high\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/acdcda1e844dc939-tx4-s-application.webp\" alt=\"Pt100 vs JPt100: Verify the RTD Curve Before Replacement  title=\" width=\"1200\" height=\"675\" loading=\"eager\" decoding=\"async\" pt100 vs jpt100: verify the rtd curve before replacement title =\"\"><\/a><figcaption>AI-assisted application illustration of TX4-S. Display segments identify the panel context; no particular input curve or control response is demonstrated. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/2ce50d51a5f9fd3d-application-master.png\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<nav class=\"table-of-contents\" aria-label=\"Article contents\">\n<details open>\n<summary>On this page<\/summary>\n<ol>\n<li><a href=\"#why-a-replacement-probe-can-pass-one-check-and-fail-in-service\">Why a replacement probe can pass one check and fail in service<\/a><\/li>\n<li><a href=\"#identify-the-curve-separately-from-nominal-resistance\">Identify the curve separately from nominal resistance<\/a><\/li>\n<li><a href=\"#calculate-a-hypothetical-two-curve-mismatch\">Calculate a hypothetical two-curve mismatch<\/a><\/li>\n<li><a href=\"#use-a-curve-verification-record-before-changing-offsets\">Use a curve-verification record before changing offsets<\/a><\/li>\n<li><a href=\"#verify-the-installed-chain-under-controlled-conditions\">Verify the installed chain under controlled conditions<\/a><\/li>\n<li><a href=\"#send-weho-the-curve-evidence-with-the-controller-enquiry\">Send WEHO the curve evidence with the controller enquiry<\/a><\/li>\n<li><a href=\"#engineering-faq\">Engineering FAQ<\/a><\/li>\n<\/ol>\n<\/details>\n<\/nav>\n<div id=\"ez-toc-container\" class=\"ez-toc-v2_0_89 counter-hierarchy ez-toc-counter ez-toc-grey ez-toc-container-direction\">\n<div class=\"ez-toc-title-container\">\n<p class=\"ez-toc-title\" style=\"cursor:inherit\">Table des mati\u00e8res<\/p>\n<span class=\"ez-toc-title-toggle\"><a href=\"#\" class=\"ez-toc-pull-right ez-toc-btn ez-toc-btn-xs ez-toc-btn-default ez-toc-toggle\" aria-label=\"Toggle Table of Content\"><span class=\"ez-toc-js-icon-con\"><span class=\"\"><span class=\"eztoc-hide\" style=\"display:none;\">Basculer<\/span><span class=\"ez-toc-icon-toggle-span\"><svg style=\"fill: #999;color:#999\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" class=\"list-377408\" width=\"20px\" height=\"20px\" viewbox=\"0 0 24 24\" fill=\"none\"><path d=\"M6 6H4v2h2V6zm14 0H8v2h12V6zM4 11h2v2H4v-2zm16 0H8v2h12v-2zM4 16h2v2H4v-2zm16 0H8v2h12v-2z\" fill=\"currentColor\"><\/path><\/svg><svg style=\"fill: #999;color:#999\" class=\"arrow-unsorted-368013\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" width=\"10px\" height=\"10px\" viewbox=\"0 0 24 24\" version=\"1.2\" baseprofile=\"tiny\"><path d=\"M18.2 9.3l-6.2-6.3-6.2 6.3c-.2.2-.3.4-.3.7s.1.5.3.7c.2.2.4.3.7.3h11c.3 0 .5-.1.7-.3.2-.2.3-.5.3-.7s-.1-.5-.3-.7zM5.8 14.7l6.2 6.3 6.2-6.3c.2-.2.3-.5.3-.7s-.1-.5-.3-.7c-.2-.2-.4-.3-.7-.3h-11c-.3 0-.5.1-.7.3-.2.2-.3.5-.3.7s.1.5.3.7z\"\/><\/svg><\/span><\/span><\/span><\/a><\/span><\/div>\n<nav><ul class='ez-toc-list ez-toc-list-level-1' ><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-1\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Why_a_replacement_probe_can_pass_one_check_and_fail_in_service\" >Why a replacement probe can pass one check and fail in service<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-2\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Identify_the_curve_separately_from_nominal_resistance\" >Identify the curve separately from nominal resistance<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-3\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Calculate_a_hypothetical_two-curve_mismatch\" >Calculate a hypothetical two-curve mismatch<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-4\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Use_a_curve-verification_record_before_changing_offsets\" >Use a curve-verification record before changing offsets<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-5\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Verify_the_installed_chain_under_controlled_conditions\" >Verify the installed chain under controlled conditions<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-6\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Send_WEHO_the_curve_evidence_with_the_controller_enquiry\" >Send WEHO the curve evidence with the controller enquiry<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-7\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Engineering_FAQ\" >Engineering FAQ<\/a><ul class='ez-toc-list-level-3' ><li class='ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-8\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Can_a_100_%CE%A9_reading_at_0%C2%B0C_distinguish_Pt100_from_JPt100\" >Can a 100 \u03a9 reading at 0\u00b0C distinguish Pt100 from JPt100?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-9\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Can_I_correct_a_wrong_RTD_curve_with_one_display_offset\" >Can I correct a wrong RTD curve with one display offset?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-10\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Does_three-wire_RTD_wiring_identify_the_temperature_curve\" >Does three-wire RTD wiring identify the temperature curve?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-11\" href=\"https:\/\/www.wehopower.com\/fr\/news\/pt100-jpt100-curve-replacement\/#Does_the_TX4-S_product_name_confirm_JPt100_support\" >Does the TX4-S product name confirm JPt100 support?<\/a><\/li><\/ul><\/li><\/ul><\/nav><\/div>\n<h2 id=\"why-a-replacement-probe-can-pass-one-check-and-fail-in-service\"><span class=\"ez-toc-section\" id=\"Why_a_replacement_probe_can_pass_one_check_and_fail_in_service\"><\/span>Why a replacement probe can pass one check and fail in service<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>A maintenance team replaces a legacy platinum probe, checks 100 \u03a9 at 0\u00b0C and releases the machine. The display later disagrees with a reference at the production temperature, although the wiring appears unchanged. Before applying an offset, determine whether the replacement sensor and controller use the same resistance curve.<\/p>\n<p>Le <a href=\"https:\/\/www.wehopower.com\/fr\/product\/tx4-series-tx4-s-economic-dual-display-pid-temperature-controller\/\">TX4-S controller input reference<\/a> identifies the controller family involved in this review. Product appearance does not establish support for every platinum-sensor curve, and a three-wire connection does not resolve a curve mismatch.<\/p>\n<h2 id=\"identify-the-curve-separately-from-nominal-resistance\"><span class=\"ez-toc-section\" id=\"Identify_the_curve_separately_from_nominal_resistance\"><\/span>Identify the curve separately from nominal resistance<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Pt100 describes a platinum RTD with a nominal resistance of 100 \u03a9 at 0\u00b0C, but nominal resistance alone is incomplete identification. OMRON&#39;s <a href=\"https:\/\/www.ia.omron.com\/support\/glossary\/meaning\/207.html\" target=\"_blank\" rel=\"noopener\">JPt100 definition<\/a> distinguishes the legacy Japanese characteristic from IEC-associated Pt100. The sensor certificate or manufacturer curve must establish which characteristic applies.<\/p>\n<p>A supplier description such as \u201c100-ohm platinum, three wire\u201d leaves the resistance law unresolved. Request the curve designation, relevant coefficients or resistance table, usable temperature range and tolerance information. Record the complete probe part number rather than assuming a familiar connector or cable color identifies the element.<\/p>\n<p>Le <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2023\/11\/TX4.pdf\">WEHO TX4 series instruction manual<\/a> identifies Pt100 and Cu50 in its RTD input list. The listed inputs do not provide evidence that every TX4 configuration accepts JPt100. Obtain the applicable ordered-unit instructions before approving an older JPt probe or an external conversion arrangement.<\/p>\n<figure class=\"article-figure product\" data-asset=\"F07-product\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/fr\/product\/tx4-series-tx4-s-economic-dual-display-pid-temperature-controller\/\" aria-label=\"TX4-S details\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/3ac2ffaf271bb0c0-tx4-s-product-reference.webp\" alt=\"Pt100 vs JPt100: Verify the RTD Curve Before Replacement  title=\" width=\"800\" height=\"800\" decoding=\"async\" pt100 vs jpt100: verify the rtd curve before replacement title =\"\"><\/a><figcaption>Product reference for TX4-S; original visible identity is retained. Display segments identify the panel context; no particular input curve or control response is demonstrated. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/c996904ae289c83f-product-original.png\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<p>Input configuration and calibration also perform different jobs. Configuration selects the resistance law that converts the measured resistance into temperature; calibration checks the resulting measurement against a reference under stated conditions. A calibration offset cannot make two different resistance laws identical across a range.<\/p>\n<h2 id=\"calculate-a-hypothetical-two-curve-mismatch\"><span class=\"ez-toc-section\" id=\"Calculate_a_hypothetical_two-curve_mismatch\"><\/span>Calculate a hypothetical two-curve mismatch<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>This engineering example compares ideal reference curves above 0\u00b0C, with zero lead resistance and no self-heating. It is not a measured TX4 error, an actual probe calibration or an approved replacement specification. The comparison isolates curve identity so that other uncertainty sources do not hide its effect.<\/p>\n<p>For temperatures at or above 0\u00b0C, use R(T) = R\u2080 \u00d7 (1 + A \u00d7 T + B \u00d7 T\u00b2). Here R is in ohms, T is in degrees Celsius and R\u2080 = 100 \u03a9. NI&#39;s <a href=\"https:\/\/www.ni.com\/docs\/en-US\/bundle\/ni-dmm-c-api-ref\/page\/group____root__nidmm__functions__configuration__measurement__options__temperature_1gad5160554784f85f60e4e3625a9f5a238.html\" target=\"_blank\" rel=\"noopener\">RTD configuration documentation<\/a> lists separate coefficient sets for the common IEC-associated and JISC 1604 characteristics.<\/p>\n<p>For this calculation, curve P uses A = 0.0039083\u00b0C\u207b\u00b9 and B = \u22120.0000005775\u00b0C\u207b\u00b2. Curve J uses A = 0.0039739\u00b0C\u207b\u00b9 and B = \u22120.0000005870\u00b0C\u207b\u00b2. These are reference-curve inputs; they are not measured coefficients of the installed probe.<\/p>\n<p>At 100\u00b0C, curve P gives 100 \u00d7 (1 + 0.39083 \u2212 0.005775) = 138.5055 \u03a9. Curve J gives 100 \u00d7 (1 + 0.39739 \u2212 0.005870) = 139.1520 \u03a9. Both begin at 100 \u03a9, but the resistance difference at this point is 0.6465 \u03a9.<\/p>\n<p>To estimate what the wrong conversion would report, insert 139.1520 \u03a9 into curve P and solve its quadratic for temperature. The positive operating-range solution is approximately 101.70\u00b0C, creating a calculated indication difference of about +1.70\u00b0C at this example&#39;s true 100\u00b0C point. The difference belongs to the mismatched reference curves, not a claimed controller accuracy limit.<\/p>\n<p>At 200\u00b0C, curve P gives 175.8560 \u03a9 and curve J gives 177.1300 \u03a9. Interpreting the second resistance with curve P gives approximately 203.47\u00b0C. A single negative correction established at 100\u00b0C would therefore leave a different residual at 200\u00b0C.<\/p>\n<figure class=\"article-figure technical\" data-asset=\"F07-technical\">\n<div class=\"diagram-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering diagram\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/b48cd0a369c744f7-rtd-curve-identity-engineering-example.svg\" alt=\"Pt100 vs JPt100: Verify the RTD Curve Before Replacement  title=\" width=\"1200\" height=\"675\" decoding=\"async\" pt100 vs jpt100: verify the rtd curve before replacement title =\"\"><\/div><figcaption>Conceptual Engineering Diagram. Calculated ideal reference curves at 0\u00b0C, 100\u00b0C and 200\u00b0C; J-curve resistance is interpreted with the P curve. No measured TX4 or probe performance is shown. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/b48cd0a369c744f7-rtd-curve-identity-engineering-example.svg\" target=\"_blank\" rel=\"noopener\">Open full-size diagram<\/a><\/figcaption><p class=\"figure-help\">Swipe horizontally on a small screen, or open the full-size diagram.<\/p>\n<\/figure>\n<h2 id=\"use-a-curve-verification-record-before-changing-offsets\"><span class=\"ez-toc-section\" id=\"Use_a_curve-verification_record_before_changing_offsets\"><\/span>Use a curve-verification record before changing offsets<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>The useful output is a documented conversion decision, not a rule that one sensor type is better. NI&#39;s <a href=\"https:\/\/knowledge.ni.com\/KnowledgeArticleDetails?id=kA03q000000x1rnCAA&amp;l=en-US\" target=\"_blank\" rel=\"noopener\">RTD measurement guidance<\/a> explains that accurate resistance conversion uses the relevant curve rather than nominal resistance alone. Choose verification points that cover the actual production range.<\/p>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<caption>Ideal reference comparison; calculated values, not measured product performance<\/caption>\n<thead>\n<tr>\n<th scope=\"col\">True temperature<\/th>\n<th scope=\"col\">Curve P resistance<\/th>\n<th scope=\"col\">Curve J resistance<\/th>\n<th scope=\"col\">J resistance through P conversion<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>0\u00b0C<\/td>\n<td>100.0000 \u03a9<\/td>\n<td>100.0000 \u03a9<\/td>\n<td>0.00\u00b0C<\/td>\n<\/tr>\n<tr>\n<td>100\u00b0C<\/td>\n<td>138.5055 \u03a9<\/td>\n<td>139.1520 \u03a9<\/td>\n<td>About 101.70\u00b0C<\/td>\n<\/tr>\n<tr>\n<td>200\u00b0C<\/td>\n<td>175.8560 \u03a9<\/td>\n<td>177.1300 \u03a9<\/td>\n<td>About 203.47\u00b0C<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>A near-zero error at the first row would not validate the remaining rows. Conversely, a growing error with temperature is not proof of curve mismatch by itself; wiring, immersion, reference uncertainty and sensor condition can produce other patterns. Use the record to distinguish hypotheses rather than assigning a cause from one reading.<\/p>\n<p>Le <a href=\"https:\/\/www.wehopower.com\/fr\/news\/weho-b2b-395-tx4-temperature-controller-with-k-type-thermocouple\/\">TX4-S thermocouple measurement-chain article<\/a> addresses another input technology. Its broader lesson is to qualify the complete sensor-to-controller chain, while keeping thermocouple compensation and RTD curve identification as separate technical tasks.<\/p>\n<h2 id=\"verify-the-installed-chain-under-controlled-conditions\"><span class=\"ez-toc-section\" id=\"Verify_the_installed_chain_under_controlled_conditions\"><\/span>Verify the installed chain under controlled conditions<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<ol>\n<li><strong>Identify both parts.<\/strong> Record the probe part number, controller&#39;s complete label and current input selection. Compare them with the applicable probe curve and controller input documentation; an undocumented JPt setting remains unresolved rather than assumed available.<\/li>\n<li><strong>Define comparison points.<\/strong> Record the operating range, selected verification temperatures and required project tolerance. Choose points that can reveal a changing curve error; a single 0\u00b0C resistance check only tests the common nominal point.<\/li>\n<li><strong>Separate electronics from the probe.<\/strong> Where the equipment procedure permits, a qualified person can use a suitable resistance simulator with the heating circuit controlled independently. Record simulated resistances, input selection and displayed values, then compare the expected curve conversion without implying that simulator agreement validates probe immersion.<\/li>\n<li><strong>Check the assembled sensor chain.<\/strong> Record reference instrument identity, immersion arrangement, stabilized readings and lead configuration. Judge results against the project uncertainty budget and approved acceptance procedure, not against the illustrative differences in this article.<\/li>\n<li><strong>Freeze the accepted configuration.<\/strong> Record the approved probe code, input type, any justified correction and the verification result. Release purchasing and commissioning records together so that a later nominally equivalent spare cannot silently introduce another curve.<\/li>\n<\/ol>\n<p>A failed compatibility check should stop the replacement decision, not invite trial-and-error input selection on operating equipment. Changing input type can change the displayed temperature and control demand immediately. Follow the equipment&#39;s isolation and commissioning procedures before reconnecting the production loop.<\/p>\n<p>When a correction is justified after curve compatibility is established, document its purpose and tested range. A local installation bias, an electronic input correction and a curve mismatch require different remedies. Keeping those explanations separate prevents an apparently successful adjustment from hiding the wrong sensor identity.<\/p>\n<h2 id=\"send-weho-the-curve-evidence-with-the-controller-enquiry\"><span class=\"ez-toc-section\" id=\"Send_WEHO_the_curve_evidence_with_the_controller_enquiry\"><\/span>Send WEHO the curve evidence with the controller enquiry<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Use the <a href=\"https:\/\/www.wehopower.com\/fr\/product\/tx4-series-tx4-s-economic-dual-display-pid-temperature-controller\/\">TX4-S configuration enquiry page<\/a> with the complete ordered-unit label, probe part number, curve designation, production range and required accuracy. Include the comparison record and ask which documented input arrangement applies. If JPt100 is required, request explicit compatibility confirmation rather than treating a Pt100 menu entry as equivalent.<\/p>\n<h2 id=\"engineering-faq\"><span class=\"ez-toc-section\" id=\"Engineering_FAQ\"><\/span>Engineering FAQ<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<h3 id=\"can-a-100-reading-at-0-c-distinguish-pt100-from-jpt100\"><span class=\"ez-toc-section\" id=\"Can_a_100_%CE%A9_reading_at_0%C2%B0C_distinguish_Pt100_from_JPt100\"><\/span>Can a 100 \u03a9 reading at 0\u00b0C distinguish Pt100 from JPt100?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No, both characteristics can share that nominal resistance at 0\u00b0C. Identify the curve from the probe documentation and verify additional points within the intended range. The common nominal point cannot establish interchangeability.<\/p>\n<h3 id=\"can-i-correct-a-wrong-rtd-curve-with-one-display-offset\"><span class=\"ez-toc-section\" id=\"Can_I_correct_a_wrong_RTD_curve_with_one_display_offset\"><\/span>Can I correct a wrong RTD curve with one display offset?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>A single offset cannot generally correct a curve mismatch across the range. The example&#39;s difference changes between 100\u00b0C and 200\u00b0C. Establish curve compatibility before deciding whether a remaining installation bias warrants a documented correction.<\/p>\n<h3 id=\"does-three-wire-rtd-wiring-identify-the-temperature-curve\"><span class=\"ez-toc-section\" id=\"Does_three-wire_RTD_wiring_identify_the_temperature_curve\"><\/span>Does three-wire RTD wiring identify the temperature curve?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No, three-wire wiring concerns the measurement connection rather than the resistance law. The input still needs the correct sensor characteristic, and unequal lead effects require their own assessment. Record wiring and curve identity separately.<\/p>\n<h3 id=\"does-the-tx4-s-product-name-confirm-jpt100-support\"><span class=\"ez-toc-section\" id=\"Does_the_TX4-S_product_name_confirm_JPt100_support\"><\/span>Does the TX4-S product name confirm JPt100 support?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No, the product name alone does not confirm JPt100 support. The cited TX4 manual lists Pt100 and Cu50 RTD inputs, so a JPt100 requirement needs applicable-unit evidence. Submit the complete controller and probe identification before approving replacement.<\/p>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>Compare Pt100 and JPt100 curves beyond the ice point, calculate mismatch, and send WEHO your probe curve and TX4-S label before approving a replacement.<\/p>","protected":false},"author":2,"featured_media":22223,"parent":0,"menu_order":6,"comment_status":"","ping_status":"","template":"","format":"standard","meta":{"_acf_changed":false,"_joinchat":[],"footnotes":""},"news_category":[284],"class_list":["post-22664","news","type-news","status-publish","format-standard","has-post-thumbnail","hentry","news_category-product-articles","entry"],"acf":[],"post_mailing_queue_ids":[],"_links":{"self":[{"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/news\/22664","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/news"}],"about":[{"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/types\/news"}],"author":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/comments?post=22664"}],"version-history":[{"count":0,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/news\/22664\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/media\/22223"}],"wp:attachment":[{"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/media?parent=22664"}],"wp:term":[{"taxonomy":"news_category","embeddable":true,"href":"https:\/\/www.wehopower.com\/fr\/wp-json\/wp\/v2\/news_category?post=22664"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}