{"id":23602,"date":"2026-11-23T10:20:39","date_gmt":"2026-11-23T02:20:39","guid":{"rendered":"https:\/\/www.wehopower.com\/news\/efuse-retry-latch-fault-energy\/"},"modified":"2026-11-23T10:20:39","modified_gmt":"2026-11-23T02:20:39","slug":"efuse-retry-latch-fault-energy","status":"publish","type":"news","link":"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/","title":{"rendered":"eFuse Retry or Latch-Off: Budget Energy Through a Persistent Fault"},"content":{"rendered":"<div class=\"weho-blog\">\n<p>An external eFuse&#39;s retry policy determines how often energy is reapplied to a persistent fault. Choose auto-retry, limited retry or latch-off against the equipment&#39;s recovery and thermal requirements, not solely its current-limit setting.<\/p>\n<div class=\"key-takeaways\"><strong>Key Engineering Takeaways<\/strong><\/p>\n<ul>\n<li>Distinguish temporary overload from a persistent fault.<\/li>\n<li>Calculate energy per attempt and the repeat interval.<\/li>\n<li>Separate source energy, pass-device loss and downstream energy.<\/li>\n<li>Qualify reset permission and equipment restart independently.<\/li>\n<\/ul>\n<\/div>\n<figure class=\"article-figure hero\" data-asset=\"K10-hero\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/pl\/product\/lrs-series-400w-ac-to-dc-single-output-switching-power-supply\/\" aria-label=\"LRS-400-24 details\"><img fetchpriority=\"high\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/3c057ec44cefc101-lrs-400-24-application.avif\" alt=\"LRS-400-24 product installed in an industrial application scene with original housing and label details.\" width=\"1200\" height=\"675\" loading=\"eager\" decoding=\"async\" title=\"\"><\/a><figcaption>Application illustration of LRS-400-24 in an equipment setting; not a customer installation photo. Scene created with AI assistance. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/37fc252f0794f33d-application-master.webp\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<nav class=\"table-of-contents\" aria-label=\"Article contents\">\n<details open>\n<summary>On this page<\/summary>\n<ol>\n<li><a href=\"#1-specify-the-external-protection-decision\">1. Specify the external protection decision<\/a><\/li>\n<li><a href=\"#2-separate-protection-mode-from-equipment-permission\">2. Separate protection mode from equipment permission<\/a><\/li>\n<li><a href=\"#3-calculate-one-explicitly-invented-fault-attempt\">3. Calculate one explicitly invented fault attempt<\/a><\/li>\n<li><a href=\"#4-do-not-convert-average-loss-directly-into-temperature\">4. Do not convert average loss directly into temperature<\/a><\/li>\n<li><a href=\"#5-qualify-the-persistent-fault-policy\">5. Qualify the persistent-fault policy<\/a><\/li>\n<li><a href=\"#6-request-a-source-and-protector-review\">6. Request a source-and-protector review<\/a><\/li>\n<li><a href=\"#frequently-asked-questions\">Cz\u0119sto zadawane pytania<\/a><\/li>\n<\/ol>\n<\/details>\n<\/nav>\n<div id=\"ez-toc-container\" class=\"ez-toc-v2_0_89 counter-hierarchy ez-toc-counter ez-toc-grey ez-toc-container-direction\">\n<div class=\"ez-toc-title-container\">\n<p class=\"ez-toc-title\" style=\"cursor:inherit\">Spis tre\u015bci<\/p>\n<span class=\"ez-toc-title-toggle\"><a href=\"#\" class=\"ez-toc-pull-right ez-toc-btn ez-toc-btn-xs ez-toc-btn-default ez-toc-toggle\" aria-label=\"Prze\u0142\u0105cznik Spisu Tre\u015bci\"><span class=\"ez-toc-js-icon-con\"><span class=\"\"><span class=\"eztoc-hide\" style=\"display:none;\">D\u017awignia kolankowa<\/span><span class=\"ez-toc-icon-toggle-span\"><svg style=\"fill: #999;color:#999\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" class=\"list-377408\" width=\"20px\" height=\"20px\" viewbox=\"0 0 24 24\" fill=\"none\"><path d=\"M6 6H4v2h2V6zm14 0H8v2h12V6zM4 11h2v2H4v-2zm16 0H8v2h12v-2zM4 16h2v2H4v-2zm16 0H8v2h12v-2z\" fill=\"currentColor\"><\/path><\/svg><svg style=\"fill: #999;color:#999\" class=\"arrow-unsorted-368013\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" width=\"10px\" height=\"10px\" viewbox=\"0 0 24 24\" version=\"1.2\" baseprofile=\"tiny\"><path d=\"M18.2 9.3l-6.2-6.3-6.2 6.3c-.2.2-.3.4-.3.7s.1.5.3.7c.2.2.4.3.7.3h11c.3 0 .5-.1.7-.3.2-.2.3-.5.3-.7s-.1-.5-.3-.7zM5.8 14.7l6.2 6.3 6.2-6.3c.2-.2.3-.5.3-.7s-.1-.5-.3-.7c-.2-.2-.4-.3-.7-.3h-11c-.3 0-.5.1-.7.3-.2.2-.3.5-.3.7s.1.5.3.7z\"\/><\/svg><\/span><\/span><\/span><\/a><\/span><\/div>\n<nav><ul class='ez-toc-list ez-toc-list-level-1' ><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-1\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#1_Specify_the_external_protection_decision\" >1. Specify the external protection decision<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-2\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#2_Separate_protection_mode_from_equipment_permission\" >2. Separate protection mode from equipment permission<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-3\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#3_Calculate_one_explicitly_invented_fault_attempt\" >3. Calculate one explicitly invented fault attempt<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-4\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#4_Do_not_convert_average_loss_directly_into_temperature\" >4. Do not convert average loss directly into temperature<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-5\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#5_Qualify_the_persistent-fault_policy\" >5. Qualify the persistent-fault policy<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-6\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#6_Request_a_source-and-protector_review\" >6. Request a source-and-protector review<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-7\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#Frequently_Asked_Questions\" >Cz\u0119sto zadawane pytania<\/a><ul class='ez-toc-list-level-3' ><li class='ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-8\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#Is_auto-retry_always_preferable_to_latch-off\" >Is auto-retry always preferable to latch-off?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-9\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#Does_the_eFuses_current-limit_setting_establish_its_temperature\" >Does the eFuse&#39;s current-limit setting establish its temperature?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-10\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#Can_input_energy_be_treated_entirely_as_eFuse_heat\" >Can input energy be treated entirely as eFuse heat?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-11\" href=\"https:\/\/www.wehopower.com\/pl\/news\/efuse-retry-latch-fault-energy\/#Does_an_accepted_electrical_reset_authorize_automatic_equipment_motion\" >Does an accepted electrical reset authorize automatic equipment motion?<\/a><\/li><\/ul><\/li><\/ul><\/nav><\/div>\n<h2 id=\"1-specify-the-external-protection-decision\"><span class=\"ez-toc-section\" id=\"1_Specify_the_external_protection_decision\"><\/span>1. Specify the external protection decision<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>An OEM choosing branch electronics often wants unattended recovery after a temporary fault. The same automatic recovery can repeatedly energize a fault that has not cleared. The useful purchasing output is a documented retry policy, supported by energy and temperature records for the complete protected branch.<\/p>\n<p>The <a href=\"https:\/\/www.wehopower.com\/pl\/product\/lrs-series-400w-ac-to-dc-single-output-switching-power-supply\/\">WEHO LRS-400-24 product reference<\/a> identifies a possible upstream source. The eFuse in this article is an external selected component, not a claimed internal feature. No retry interval, current-limit value, thermal threshold or fault waveform is assigned to the LRS-400-24.<\/p>\n<p><a href=\"https:\/\/www.ti.com\/lit\/an\/slvaed9\/slvaed9.pdf\" target=\"_blank\" rel=\"noopener\">TI&#39;s persistent-fault eFuse application report<\/a> discusses the recovery benefit and repeated heating cost of automatic retries in named devices. Its demonstrated waveforms are component-specific. A system design still needs its actual selected part, configuration, load, cooling and upstream behavior.<\/p>\n<h2 id=\"2-separate-protection-mode-from-equipment-permission\"><span class=\"ez-toc-section\" id=\"2_Separate_protection_mode_from_equipment_permission\"><\/span>2. Separate protection mode from equipment permission<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>An auto-retry part can attempt to reapply power after its specified off or cooling interval. A latch-off part remains disabled until the specified reset condition occurs. A controller can also implement a limited retry policy when supported by the selected hardware. Those descriptions require exact device and circuit evidence.<\/p>\n<p><a href=\"https:\/\/toshiba.semicon-storage.com\/ap-en\/semiconductor\/knowledge\/faq\/linear-efuse-ics\/how-does-overcurrent-protection-of-eFuse-IC-work.html\" target=\"_blank\" rel=\"noopener\">Toshiba&#39;s eFuse overcurrent FAQ<\/a> explicitly distinguishes auto-retry and latch behavior in its devices. The named reset sequence belongs to that product family. Do not assume that toggling any enable pin resets every protector or that an equipment operator may reset an unresolved fault.<\/p>\n<p>The separate <a href=\"https:\/\/www.wehopower.com\/pl\/news\/24v-to-12v-converter-current-limit-fault-recovery\/\">converter overload-recovery guide<\/a> addresses the source&#39;s load support and recovery. This article instead calculates repeated energy through an external electronic protector. Source protection and branch protection can interact, so both need to remain represented in the test configuration.<\/p>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">Policy<\/th>\n<th scope=\"col\">Recovery opportunity<\/th>\n<th scope=\"col\">Persistent-fault concern<\/th>\n<th scope=\"col\">Evidence required<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Auto-retry<\/td>\n<td>Unattended new attempts<\/td>\n<td>Repeated heat and fault energization<\/td>\n<td>Actual pulse and cooling sequence<\/td>\n<\/tr>\n<tr>\n<td>Limited retry<\/td>\n<td>Defined number of attempts<\/td>\n<td>Counter\/reset ownership and failure modes<\/td>\n<td>Implemented count and terminal state<\/td>\n<\/tr>\n<tr>\n<td>Latch-off<\/td>\n<td>Explicit reset after the event<\/td>\n<td>Service access and reset permission<\/td>\n<td>Exact reset conditions and recovery test<\/td>\n<\/tr>\n<tr>\n<td>Upstream source response<\/td>\n<td>Independent limiting or recovery<\/td>\n<td>Changes energy delivered to the branch<\/td>\n<td>Simultaneous source and branch records<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<h2 id=\"3-calculate-one-explicitly-invented-fault-attempt\"><span class=\"ez-toc-section\" id=\"3_Calculate_one_explicitly_invented_fault_attempt\"><\/span>3. Calculate one explicitly invented fault attempt<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Assume an idealized external protector has 24 V at its input, 2 V at its output and a constant 2 A during a 5 ms fault attempt. Neglect quiescent demand, switching transitions, wiring losses and stored-capacitor changes. These are chosen arithmetic conditions, not data for the illustrated power supply or a marketed eFuse.<\/p>\n<p>Input power during the assumed interval is 24 V \u00d7 2 A = 48 W. Power in the protector&#39;s series pass path is (24 \u2212 2) V \u00d7 2 A = 44 W. Power delivered at the downstream boundary is 2 V \u00d7 2 A = 4 W.<\/p>\n<p>Integrating those constant powers for 5 ms gives 0.240 J drawn at the input boundary, 0.220 J dissipated in the pass path and 0.020 J delivered downstream. The energy balance is 0.240 = 0.220 + 0.020 J under the stated assumptions. Calling all 0.240 J protector heat would confuse these boundaries.<\/p>\n<figure class=\"article-figure technical\" data-asset=\"K10-technical\">\n<div class=\"diagram-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering diagram\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/e4fd3aa3ef0ea8d0-technical.svg\" alt=\"Cumulative heat from assumed repeated fault pulses rises with every external protector retry attempt.\" width=\"1200\" height=\"675\" decoding=\"async\" title=\"\"><\/div><figcaption>Conceptual Engineering Diagram. Assumed 44W pass-path loss for 5ms every 100ms adds 0.220J per attempt; heat integral is not junction temperature or LRS protection behavior. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/e4fd3aa3ef0ea8d0-technical.svg\" target=\"_blank\" rel=\"noopener\">Open full-size diagram<\/a><\/figcaption><p class=\"figure-help\">Swipe horizontally on a small screen, or open the full-size diagram.<\/p>\n<\/figure>\n<p>Now assume identical attempts begin every 100 ms, measured start to start. The duty ratio is 5\/100 = 0.05. The average input power associated with those pulses is 48 \u00d7 0.05 = 2.4 W, while average pass-path loss is 44 \u00d7 0.05 = 2.2 W.<\/p>\n<p>Over a declared ten-second interval containing exactly 100 complete attempts, the example draws 24 J, dissipates 22 J in the pass path and delivers 2 J downstream. A different endpoint convention or partial final pulse requires integrating the actual record rather than blindly multiplying by a rounded event count.<\/p>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">Invented quantity<\/th>\n<th scope=\"col\">Per 5 ms attempt<\/th>\n<th scope=\"col\">100 complete attempts<\/th>\n<th scope=\"col\">Meaning<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Source input energy<\/td>\n<td>0.240 J<\/td>\n<td>24.0 J<\/td>\n<td>Energy crossing input boundary<\/td>\n<\/tr>\n<tr>\n<td>Pass-path heat<\/td>\n<td>0.220 J<\/td>\n<td>22.0 J<\/td>\n<td>Idealized protector dissipation<\/td>\n<\/tr>\n<tr>\n<td>Downstream energy<\/td>\n<td>0.020 J<\/td>\n<td>2.0 J<\/td>\n<td>Energy crossing output boundary<\/td>\n<\/tr>\n<tr>\n<td>Limited three-attempt policy<\/td>\n<td>Same assumed pulse<\/td>\n<td>0.660 J pass-path heat<\/td>\n<td>Before remaining disabled; not a rating<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>A three-attempt policy under the identical pulse assumptions would accumulate 3 \u00d7 0.220 = 0.660 J of pass-path heat before remaining off. That smaller energy total does not independently qualify the design. The first pulse can still exceed a limit, and real pulse duration can depend on junction temperature and source behavior.<\/p>\n<h2 id=\"4-do-not-convert-average-loss-directly-into-temperature\"><span class=\"ez-toc-section\" id=\"4_Do_not_convert_average_loss_directly_into_temperature\"><\/span>4. Do not convert average loss directly into temperature<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p><a href=\"https:\/\/toshiba.semicon-storage.com\/us\/semiconductor\/knowledge\/faq\/linear-efuse-ics\/how-does-thermal-shutdown-of-eFuse-IC-work.html\" target=\"_blank\" rel=\"noopener\">Toshiba&#39;s thermal-shutdown explanation<\/a> distinguishes thermal shutdown and the subsequent retry or latched state. Thermal protection is a device response, not a temperature guarantee for the complete enclosure, nearby parts or connected fault path.<\/p>\n<p>Repeated pulse temperature depends on transient thermal behavior, PCB layout, ambient conditions and cooling between attempts. Multiplying average power by an unrelated thermal-resistance number cannot establish the peak junction temperature during a short pulse. Use the selected component&#39;s applicable thermal and safe-operating information, supported by a suitable measurement plan.<\/p>\n<p>Likewise, 2 A current limiting does not mean the fault location sees only a harmless event. The downstream voltage and energy distribution determine its exposure. Capacitors already charged beyond the protector can release energy independently; include their state when defining the protected boundary and fault cases.<\/p>\n<p>PPTC thermal recovery concerns passive high-resistance heating and cooldown. An electronic protector&#39;s retry control is a different mechanism. Do not substitute PPTC cooling assumptions for an eFuse&#39;s timing or assume both provide a safe isolation gap.<\/p>\n<figure class=\"article-figure product\" data-asset=\"K10-product\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/pl\/product\/lrs-series-400w-ac-to-dc-single-output-switching-power-supply\/\" aria-label=\"LRS-400-24 details\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/0f29ed8b4c6b5ff9-lrs-400-24-product-reference.avif\" alt=\"LRS-400-24 product reference preserving the original housing, visible label and connection features.\" width=\"1000\" height=\"1000\" decoding=\"async\" title=\"\"><\/a><figcaption>Product appearance reference for LRS-400-24, preserving the source housing, visible label and connections. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/44622179442b7304-product-original.jpg\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<h2 id=\"5-qualify-the-persistent-fault-policy\"><span class=\"ez-toc-section\" id=\"5_Qualify_the_persistent-fault_policy\"><\/span>5. Qualify the persistent-fault policy<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<ol>\n<li><strong>Define the branch.<\/strong> Record source, protector, downstream capacitance, wiring and fault locations. Verify that every relevant energy source is included in the stated boundary.<\/li>\n<li><strong>Choose the intended response.<\/strong> Record auto-retry, limited retry or latch-off requirements and reset ownership. Verify that the exact selected device and circuit implement that policy.<\/li>\n<li><strong>Measure each attempt.<\/strong> Record protector input\/output voltage, signed current and timing together. Verify polarity and integrate power at the intended energy boundaries.<\/li>\n<li><strong>Assess repetition and heat.<\/strong> Record attempt count, intervals, local temperatures and applicable component limits. Verify both the individual pulse and the sustained required fault condition.<\/li>\n<li><strong>Verify recovery permission.<\/strong> Record fault removal, reset action and receiving-equipment behavior. Verify that restored power does not bypass a required deliberate equipment restart.<\/li>\n<\/ol>\n<p>Repeat the relevant case after the assembly reaches its required hot condition. A first cold attempt can have a different duration from later attempts controlled by thermal state. Preserve the measured sequence rather than reporting a single convenient pulse as representative of all sustained-fault operation.<\/p>\n<h2 id=\"6-request-a-source-and-protector-review\"><span class=\"ez-toc-section\" id=\"6_Request_a_source-and-protector_review\"><\/span>6. Request a source-and-protector review<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>For an <a href=\"https:\/\/www.wehopower.com\/pl\/product\/lrs-series-400w-ac-to-dc-single-output-switching-power-supply\/\">LRS-400-24 branch review<\/a>, provide the external protector reference, settings, load states, intended retry policy and fault record. Include input and output energy calculations with their boundaries. Request applicable supply information while the branch owner qualifies protector stress, fault containment and equipment recovery.<\/p>\n<h2 id=\"frequently-asked-questions\"><span class=\"ez-toc-section\" id=\"Frequently_Asked_Questions\"><\/span>Cz\u0119sto zadawane pytania<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<h3 id=\"is-auto-retry-always-preferable-to-latch-off\"><span class=\"ez-toc-section\" id=\"Is_auto-retry_always_preferable_to_latch-off\"><\/span>Is auto-retry always preferable to latch-off?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Automatic recovery can help after temporary faults but repeatedly energizes a persistent fault. The equipment&#39;s recovery, energy, thermal and service requirements determine the appropriate policy.<\/p>\n<h3 id=\"does-the-efuse-s-current-limit-setting-establish-its-temperature\"><span class=\"ez-toc-section\" id=\"Does_the_eFuses_current-limit_setting_establish_its_temperature\"><\/span>Does the eFuse&#39;s current-limit setting establish its temperature?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Voltage across the pass path, pulse duration, repetition and thermal conditions also matter. Use actual device information and the relevant measured sequence.<\/p>\n<h3 id=\"can-input-energy-be-treated-entirely-as-efuse-heat\"><span class=\"ez-toc-section\" id=\"Can_input_energy_be_treated_entirely_as_eFuse_heat\"><\/span>Can input energy be treated entirely as eFuse heat?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Some energy can cross the output boundary or change stored energy. Identify the boundaries and account for those terms before assigning dissipation to a component.<\/p>\n<h3 id=\"does-an-accepted-electrical-reset-authorize-automatic-equipment-motion\"><span class=\"ez-toc-section\" id=\"Does_an_accepted_electrical_reset_authorize_automatic_equipment_motion\"><\/span>Does an accepted electrical reset authorize automatic equipment motion?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Restoring branch power and permitting equipment operation are separate decisions. Qualify the required control state and restart permission with the responsible equipment owner.<\/p>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>Compare external eFuse retry and latch-off policies using energy per fault attempt, repetition, component heat and the equipment reset requirement.<\/p>","protected":false},"author":2,"featured_media":22243,"parent":0,"menu_order":6,"comment_status":"","ping_status":"","template":"","format":"standard","meta":{"_acf_changed":false,"_joinchat":[],"footnotes":""},"news_category":[284],"class_list":["post-23602","news","type-news","status-publish","format-standard","has-post-thumbnail","hentry","news_category-product-articles","entry"],"acf":[],"post_mailing_queue_ids":[],"_links":{"self":[{"href":"https:\/\/www.wehopower.com\/pl\/wp-json\/wp\/v2\/news\/23602","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.wehopower.com\/pl\/wp-json\/wp\/v2\/news"}],"about":[{"href":"https:\/\/www.wehopower.com\/pl\/wp-json\/wp\/v2\/types\/news"}],"author":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/pl\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/pl\/wp-json\/wp\/v2\/comments?post=23602"}],"version-history":[{"count":0,"href":"https:\/\/www.wehopower.com\/pl\/wp-json\/wp\/v2\/news\/23602\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/pl\/wp-json\/wp\/v2\/media\/22243"}],"wp:attachment":[{"href":"https:\/\/www.wehopower.com\/pl\/wp-json\/wp\/v2\/media?parent=23602"}],"wp:term":[{"taxonomy":"news_category","embeddable":true,"href":"https:\/\/www.wehopower.com\/pl\/wp-json\/wp\/v2\/news_category?post=23602"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}