{"id":22266,"date":"2026-11-17T10:51:29","date_gmt":"2026-11-17T02:51:29","guid":{"rendered":"https:\/\/www.wehopower.com\/news\/current-shunt-self-heating-error\/"},"modified":"2026-11-17T10:51:29","modified_gmt":"2026-11-17T02:51:29","slug":"current-shunt-self-heating-error","status":"publish","type":"news","link":"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/","title":{"rendered":"Current Shunt Self-Heating: Separate TCR Drift from Load Change"},"content":{"rendered":"<div class=\"weho-blog\">\n<p>A warmer current shunt can indicate a different current even when the actual current is unchanged. Calculate resistance change at the relevant element temperature before treating a drifting voltage-to-current conversion as evidence that a power-supply branch draws more current.<\/p>\n<p><strong>Key engineering takeaways<\/strong><\/p>\n<ul>\n<li>Convert shunt voltage using an applicable resistance value.<\/li>\n<li>Include ambient temperature and operating self-heating separately.<\/li>\n<li>Keep shunt gain drift distinct from its circuit voltage burden.<\/li>\n<li>Verify thermal conditions before applying temperature correction.<\/li>\n<\/ul>\n<figure class=\"article-figure hero\" data-asset=\"H09-hero\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/product\/wholesale-60w-single-output-din-rail-power-power-supply\/\" aria-label=\"MDR-60-12 details\"><img fetchpriority=\"high\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/60bea74f3923e2e9-mdr-60-12-application.webp\" alt=\"Current Shunt Self-Heating: Separate TCR Drift from Load Change  title=\" width=\"1200\" height=\"675\" loading=\"eager\" fetchpriority=\"high\" decoding=\"async\" Current Shunt Self-Heating: Separate TCR Drift from Load Change title=\"\"><\/a><figcaption>MDR-60-12 in an application illustration, not a customer installation photo. Scene created with AI assistance. The image does not establish a current-shunt temperature coefficient or thermal result. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/1bc31a485662a951-application-master.webp\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<nav class=\"table-of-contents\" aria-label=\"Article contents\">\n<details open>\n<summary>On this page<\/summary>\n<ol>\n<li><a href=\"#what-decision-does-a-drifting-current-reading-support\">What decision does a drifting current reading support?<\/a><\/li>\n<li><a href=\"#how-does-temperature-change-the-conversion\">How does temperature change the conversion?<\/a><\/li>\n<li><a href=\"#a-hypothetical-2-a-measurement-with-a-warming-shunt\">A hypothetical 2 A measurement with a warming shunt<\/a><\/li>\n<li><a href=\"#keep-self-heating-burden-and-sense-geometry-separate\">Keep self-heating, burden and sense geometry separate<\/a><\/li>\n<li><a href=\"#what-temperature-information-can-justify-correction\">What temperature information can justify correction?<\/a><\/li>\n<li><a href=\"#establish-a-usable-current-record\">Establish a usable current record<\/a><\/li>\n<li><a href=\"#prepare-an-mdr-60-12-measurement-review\">Prepare an MDR-60-12 measurement review<\/a><\/li>\n<li><a href=\"#engineering-faq\">Engineering FAQ<\/a><\/li>\n<\/ol>\n<\/details>\n<\/nav>\n<div id=\"ez-toc-container\" class=\"ez-toc-v2_0_89 counter-hierarchy ez-toc-counter ez-toc-grey ez-toc-container-direction\">\n<div class=\"ez-toc-title-container\">\n<p class=\"ez-toc-title\" style=\"cursor:inherit\">Table of Contents<\/p>\n<span class=\"ez-toc-title-toggle\"><a href=\"#\" class=\"ez-toc-pull-right ez-toc-btn ez-toc-btn-xs ez-toc-btn-default ez-toc-toggle\" aria-label=\"Toggle Table of Content\"><span class=\"ez-toc-js-icon-con\"><span class=\"\"><span class=\"eztoc-hide\" style=\"display:none;\">Toggle<\/span><span class=\"ez-toc-icon-toggle-span\"><svg style=\"fill: #999;color:#999\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" class=\"list-377408\" width=\"20px\" height=\"20px\" viewBox=\"0 0 24 24\" fill=\"none\"><path d=\"M6 6H4v2h2V6zm14 0H8v2h12V6zM4 11h2v2H4v-2zm16 0H8v2h12v-2zM4 16h2v2H4v-2zm16 0H8v2h12v-2z\" fill=\"currentColor\"><\/path><\/svg><svg style=\"fill: #999;color:#999\" class=\"arrow-unsorted-368013\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" width=\"10px\" height=\"10px\" viewBox=\"0 0 24 24\" version=\"1.2\" baseProfile=\"tiny\"><path d=\"M18.2 9.3l-6.2-6.3-6.2 6.3c-.2.2-.3.4-.3.7s.1.5.3.7c.2.2.4.3.7.3h11c.3 0 .5-.1.7-.3.2-.2.3-.5.3-.7s-.1-.5-.3-.7zM5.8 14.7l6.2 6.3 6.2-6.3c.2-.2.3-.5.3-.7s-.1-.5-.3-.7c-.2-.2-.4-.3-.7-.3h-11c-.3 0-.5.1-.7.3-.2.2-.3.5-.3.7s.1.5.3.7z\"\/><\/svg><\/span><\/span><\/span><\/a><\/span><\/div>\n<nav><ul class='ez-toc-list ez-toc-list-level-1 ' ><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-1\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#What_decision_does_a_drifting_current_reading_support\" >What decision does a drifting current reading support?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-2\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#How_does_temperature_change_the_conversion\" >How does temperature change the conversion?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-3\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#A_hypothetical_2_A_measurement_with_a_warming_shunt\" >A hypothetical 2 A measurement with a warming shunt<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-4\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#Keep_self-heating_burden_and_sense_geometry_separate\" >Keep self-heating, burden and sense geometry separate<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-5\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#What_temperature_information_can_justify_correction\" >What temperature information can justify correction?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-6\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#Establish_a_usable_current_record\" >Establish a usable current record<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-7\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#Prepare_an_MDR-60-12_measurement_review\" >Prepare an MDR-60-12 measurement review<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-8\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#Engineering_FAQ\" >Engineering FAQ<\/a><ul class='ez-toc-list-level-3' ><li class='ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-9\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#Can_an_unchanged_current_produce_a_rising_shunt-current_indication\" >Can an unchanged current produce a rising shunt-current indication?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-10\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#Does_four-wire_sensing_eliminate_shunt_self-heating_error\" >Does four-wire sensing eliminate shunt self-heating error?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-11\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#Can_02008_W_alone_establish_the_shunt_temperature\" >Can 0.2008 W alone establish the shunt temperature?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-12\" href=\"https:\/\/www.wehopower.com\/ru\/news\/current-shunt-self-heating-error\/#Does_correcting_shunt_resistance_establish_total_current_accuracy\" >Does correcting shunt resistance establish total current accuracy?<\/a><\/li><\/ul><\/li><\/ul><\/nav><\/div>\n<h2 id=\"what-decision-does-a-drifting-current-reading-support\"><span class=\"ez-toc-section\" id=\"What_decision_does_a_drifting_current_reading_support\"><\/span>What decision does a drifting current reading support?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>An OEM test engineer may observe a branch-current indication increasing during a cabinet warm-up. The first useful question is whether the current changed, the measurement conversion changed, or both changed. A stable digital display later in the sequence does not answer which mechanism produced the earlier trend.<\/p>\n<p>For an <a href=\"https:\/\/www.wehopower.com\/product\/wholesale-60w-single-output-din-rail-power-power-supply\/\">MDR-60-12 branch-current review<\/a>, retain the actual supply identity, branch and receiver conditions. The product reference identifies the source under discussion. It does not specify a shunt, its temperature coefficient or an achieved test current.<\/p>\n<p>The shunt belongs to the external measurement path. Its resistance, temperature and voltage-sense boundary need their own evidence. Do not assign an apparent percentage change to the MDR-60-12 merely because that model powers the branch being measured.<\/p>\n<h2 id=\"how-does-temperature-change-the-conversion\"><span class=\"ez-toc-section\" id=\"How_does_temperature_change_the_conversion\"><\/span>How does temperature change the conversion?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Current conversion commonly uses Iind = Vshunt\/Rused. If the true resistance is Ractual while the software retains an earlier Rused, a constant actual current produces Iind = Iactual \u00d7 Ractual\/Rused. The resulting gain error is different from a fixed voltage offset in the amplifier or voltmeter.<\/p>\n<p>Over a defined range where a linear approximation is applicable, write R(T) = Rref \u00d7 [1 + \u03b1 \u00d7 (T \u2212 Tref)]. Express \u03b1 in inverse degrees Celsius: 100 ppm\/\u00b0C equals 0.000100\/\u00b0C. Use the actual resistor&#39;s specified behavior rather than assuming every shunt has this coefficient, sign or linearity.<\/p>\n<p><a href=\"https:\/\/www.vishay.com\/doc\/?30373=\" target=\"_blank\" rel=\"noopener\">Vishay&#39;s current-sense application note<\/a> distinguishes initial tolerance from temperature-related effects, including operating-power effects. A tightly grouped set of readings can still contain a consistent thermal error. Low scatter therefore does not establish that a nominal-resistance conversion remains accurate after the shunt warms.<\/p>\n<h2 id=\"a-hypothetical-2-a-measurement-with-a-warming-shunt\"><span class=\"ez-toc-section\" id=\"A_hypothetical_2_A_measurement_with_a_warming_shunt\"><\/span>A hypothetical 2 A measurement with a warming shunt<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Assume a shunt is exactly 50.000 m\u03a9 at 25\u00b0C and has an exactly linear positive coefficient of 100 ppm\/\u00b0C over this example. Assume the actual current remains 2.000 A and the voltage measurement is ideal. These assumptions isolate the resistor effect; they are not a shunt specification, a WEHO measurement or a complete uncertainty budget.<\/p>\n<p>At an assumed element temperature of 65\u00b0C, \u0394T = 40\u00b0C. Resistance becomes 0.050000 \u00d7 (1 + 0.000100 \u00d7 40) = 0.050200 \u03a9. The shunt voltage is 2.000 \u00d7 0.050200 = 0.100400 V, or 100.400 mV.<\/p>\n<p>If software still divides by 0.050000 \u03a9, the indication becomes 2.008 A. The apparent increase is 8 mA, or 0.4%, despite the unchanged assumed current. Dividing by the correct 0.050200 \u03a9 returns 2.000 A in this ideal model; real correction still requires valid temperature and resistance information.<\/p>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">Assumed element temperature<\/th>\n<th scope=\"col\">Actual resistance<\/th>\n<th scope=\"col\">Voltage at actual 2 A<\/th>\n<th scope=\"col\">Indication using 50 m\u03a9<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>25\u00b0C<\/td>\n<td>50.000 m\u03a9<\/td>\n<td>100.000 mV<\/td>\n<td>2.000 A<\/td>\n<\/tr>\n<tr>\n<td>45\u00b0C<\/td>\n<td>50.100 m\u03a9<\/td>\n<td>100.200 mV<\/td>\n<td>2.004 A<\/td>\n<\/tr>\n<tr>\n<td>65\u00b0C<\/td>\n<td>50.200 m\u03a9<\/td>\n<td>100.400 mV<\/td>\n<td>2.008 A<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<figure class=\"article-figure technical\" data-asset=\"H09-technical\">\n<div class=\"diagram-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering diagram\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/b33359a9af7fc06c-shunt-temperature-indication-error.svg\" alt=\"Current Shunt Self-Heating: Separate TCR Drift from Load Change  title=\" width=\"1200\" height=\"675\" loading=\"lazy\" decoding=\"async\" Current Shunt Self-Heating: Separate TCR Drift from Load Change title=\"\"><\/div><figcaption>Conceptual Engineering Diagram. Assumed positive TCR values produce calculated indication errors; temperatures are inputs, not predicted rises or WEHO test results. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/b33359a9af7fc06c-shunt-temperature-indication-error.svg\" target=\"_blank\" rel=\"noopener\">Open full-size diagram<\/a><\/figcaption><p class=\"figure-help\">Swipe horizontally on a small screen, or open the full-size diagram.<\/p>\n<\/figure>\n<p>At the last point, shunt dissipation is I\u00b2R = 2\u00b2 \u00d7 0.050200 = 0.2008 W. That calculation does not predict a 65\u00b0C element temperature. The temperature is an explicit hypothetical input that can include cabinet heating and self-heating; the actual result depends on the component, mounting, conductors and heat-transfer conditions.<\/p>\n<p>For comparison, an assumed 25 ppm\/\u00b0C coefficient over the same 40\u00b0C difference would create a 0.1% resistance change. At the same actual current and nominal resistance, the indicated value would be 2.002 A. This sensitivity comparison does not recommend a particular shunt or establish that changing one coefficient meets the full measurement requirement.<\/p>\n<h2 id=\"keep-self-heating-burden-and-sense-geometry-separate\"><span class=\"ez-toc-section\" id=\"Keep_self-heating_burden_and_sense_geometry_separate\"><\/span>Keep self-heating, burden and sense geometry separate<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>The voltage across the inserted shunt also subtracts from the voltage available elsewhere in its series path. That physical burden can change the actual load current, independently of the conversion error.<\/p>\n<p>Four-terminal sensing can exclude certain connection-voltage drops from the measured resistance boundary. It does not make the resistor&#39;s element temperature irrelevant. Keep the force path, voltage-sense points, component resistance definition and thermal behavior identifiable in the test record.<\/p>\n<p><a href=\"https:\/\/www.ti.com\/document-viewer\/lit\/html\/sbaa460\" target=\"_blank\" rel=\"noopener\">TI&#39;s shunt-selection brief<\/a> discusses resistance, dissipation, layout and temperature behavior as related selection variables. Apply the actual resistor&#39;s ratings and mounting conditions. Do not turn another manufacturer&#39;s application-specific design margin into a universal permissible fraction of a WEHO branch current.<\/p>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">Contribution<\/th>\n<th scope=\"col\">Physical cause<\/th>\n<th scope=\"col\">Useful evidence<\/th>\n<th scope=\"col\">Do not substitute<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Reference resistance error<\/td>\n<td>Actual value differs from the conversion value<\/td>\n<td>Applicable resistance characterization and uncertainty<\/td>\n<td>Nominal marking alone<\/td>\n<\/tr>\n<tr>\n<td>Thermal resistance change<\/td>\n<td>Element temperature and operating-power effects<\/td>\n<td>Documented coefficient\/model and thermal state<\/td>\n<td>Room-air temperature alone<\/td>\n<\/tr>\n<tr>\n<td>Voltage burden<\/td>\n<td>Inserted series voltage loss<\/td>\n<td>Receiver voltage and current under the actual setup<\/td>\n<td>A corrected software reading<\/td>\n<\/tr>\n<tr>\n<td>Sense-path error<\/td>\n<td>Unwanted conductor\/contact voltage is included<\/td>\n<td>Physical sense points and component instructions<\/td>\n<td>A generic four-wire label<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>Avoid counting the same thermal change twice. If a supplier&#39;s validated power-coefficient model already covers a self-heating contribution, an additional independently assumed temperature term may overlap it. Establish which effect each specification includes before combining numbers into an error allowance.<\/p>\n<h2 id=\"what-temperature-information-can-justify-correction\"><span class=\"ez-toc-section\" id=\"What_temperature_information_can_justify_correction\"><\/span>What temperature information can justify correction?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>A room thermometer does not automatically report the resistive element&#39;s temperature. A package surface sensor can also differ from the element, especially during a transient. Define the measurement location, attachment, thermal lag and any model used to relate the observation to the relevant resistance temperature.<\/p>\n<p><a href=\"https:\/\/www.ti.com\/document-viewer\/lit\/html\/SNOAA84A\/GUID-8332AAED-7043-4F1F-A87E-5A3ADA99FC09\" target=\"_blank\" rel=\"noopener\">TI&#39;s worked current-sense design<\/a> illustrates evaluating shunt self-heating as part of a specific circuit. Its component values, derating basis and temperature result belong to that design. Use it as a reason to characterize the actual external measurement assembly, not as a temperature-rise prediction for this example.<\/p>\n<p>A correction table should cover the conditions where it will be used. A point obtained at one current, airflow or mounting state may not describe a later assembly. Retain uncorrected voltage and temperature data so that a revised model can be checked without recreating the original measurement from a rounded current display.<\/p>\n<h2 id=\"establish-a-usable-current-record\"><span class=\"ez-toc-section\" id=\"Establish_a_usable_current_record\"><\/span>Establish a usable current record<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<ol>\n<li><strong>Identify the conversion.<\/strong> Record shunt part number, resistance reference condition, coefficient or power-effect model, and software value. Verify that units and calibration scope match the actual voltage-sense boundary.<\/li>\n<li><strong>Define thermal states.<\/strong> Record ambient location, mounting, conductors, airflow, load sequence and relevant temperature observations. Verify that element-temperature assumptions are supported rather than inferred from dissipation alone.<\/li>\n<li><strong>Preserve raw signals.<\/strong> Save shunt voltage, reported current, receiver voltage and timestamps together. Verify that instrument ranges, offsets and timing can support the intended thermal-drift comparison.<\/li>\n<li><strong>Calculate distinct contributions.<\/strong> Record nominal-resistance, thermal, instrument and connection terms separately. Verify that the same effect is not counted twice and that a correction remains within its characterized conditions.<\/li>\n<li><strong>Apply the project decision rule.<\/strong> Record the current requirement, uncertainty treatment and unresolved terms. Accept the measurement only when that evidence supports the decision; a repeatable trend alone does not establish either a load change or a passed current limit.<\/li>\n<\/ol>\n<figure class=\"article-figure product\" data-asset=\"H09-product\"><a class=\"product-image-link\" href=\"https:\/\/www.wehopower.com\/product\/wholesale-60w-single-output-din-rail-power-power-supply\/\" aria-label=\"MDR-60-12 details\"><img loading=\"lazy\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/00af49cf0d1a3c23-mdr-60-12-product-reference.webp\" alt=\"Current Shunt Self-Heating: Separate TCR Drift from Load Change  title=\" width=\"800\" height=\"800\" loading=\"lazy\" decoding=\"async\" Current Shunt Self-Heating: Separate TCR Drift from Load Change title=\"\"><\/a><figcaption>WEHO MDR-60-12 product identification reference, retaining the source image&#8217;s visible identity. The photograph does not establish a current-shunt temperature coefficient or thermal result. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/3ab97502e2658a89-product-original.jpg\" target=\"_blank\" rel=\"noopener\">View original-resolution image<\/a><\/figcaption><\/figure>\n<h2 id=\"prepare-an-mdr-60-12-measurement-review\"><span class=\"ez-toc-section\" id=\"Prepare_an_MDR-60-12_measurement_review\"><\/span>Prepare an MDR-60-12 measurement review<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Send WEHO the <a href=\"https:\/\/www.wehopower.com\/product\/wholesale-60w-single-output-din-rail-power-power-supply\/\">MDR-60-12 source identity<\/a>, branch requirement, actual operating conditions and raw voltage\/current record. Include the external shunt and conversion information when thermal drift is suspected. Keep any product-document request distinct from claims about the measurement instrument&#39;s accuracy.<\/p>\n<p>For the next test, identify the resistance reference, record the thermal state and preserve the uncorrected voltage. Those actions let the responsible engineer distinguish an actual branch-current change from a measurement gain change without inventing a temperature, a calibration result or a supplier performance claim.<\/p>\n<h2 id=\"engineering-faq\"><span class=\"ez-toc-section\" id=\"Engineering_FAQ\"><\/span>Engineering FAQ<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<h3 id=\"can-an-unchanged-current-produce-a-rising-shunt-current-indication\"><span class=\"ez-toc-section\" id=\"Can_an_unchanged_current_produce_a_rising_shunt-current_indication\"><\/span>Can an unchanged current produce a rising shunt-current indication?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>Yes. If shunt resistance increases while conversion still uses its earlier value, the indicated current increases even at constant actual current. Other effects can also change the reading, so retain independent thermal and electrical evidence before assigning the cause.<\/p>\n<h3 id=\"does-four-wire-sensing-eliminate-shunt-self-heating-error\"><span class=\"ez-toc-section\" id=\"Does_four-wire_sensing_eliminate_shunt_self-heating_error\"><\/span>Does four-wire sensing eliminate shunt self-heating error?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Suitable four-wire sensing can exclude specified connection drops, but the resistive element can still change value with temperature. The conversion needs an applicable resistance model and thermal conditions in addition to a correctly defined sense boundary.<\/p>\n<h3 id=\"can-0-2008-w-alone-establish-the-shunt-temperature\"><span class=\"ez-toc-section\" id=\"Can_02008_W_alone_establish_the_shunt_temperature\"><\/span>Can 0.2008 W alone establish the shunt temperature?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Dissipation alone does not specify the complete heat-transfer conditions. The example assumes the element temperature separately; actual temperature requires suitable characterization or measurement for the component, mounting and operating state.<\/p>\n<h3 id=\"does-correcting-shunt-resistance-establish-total-current-accuracy\"><span class=\"ez-toc-section\" id=\"Does_correcting_shunt_resistance_establish_total_current_accuracy\"><\/span>Does correcting shunt resistance establish total current accuracy?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. A resistance correction addresses one contribution within its validated scope. Voltage measurement, offsets, connection geometry, timing, model uncertainty and circuit disturbance can still affect the decision and must be assessed where relevant.<\/p>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>Calculate shunt TCR error separately from actual branch-current changes. Send WEHO an MDR-60-12 measurement record with resistance and thermal conditions.<\/p>","protected":false},"author":2,"featured_media":22248,"parent":0,"menu_order":12,"comment_status":"","ping_status":"","template":"","format":"standard","meta":{"_acf_changed":false,"_joinchat":[],"footnotes":""},"news_category":[284],"class_list":["post-22266","news","type-news","status-publish","format-standard","has-post-thumbnail","hentry","news_category-product-articles","entry"],"acf":[],"post_mailing_queue_ids":[],"_links":{"self":[{"href":"https:\/\/www.wehopower.com\/ru\/wp-json\/wp\/v2\/news\/22266","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.wehopower.com\/ru\/wp-json\/wp\/v2\/news"}],"about":[{"href":"https:\/\/www.wehopower.com\/ru\/wp-json\/wp\/v2\/types\/news"}],"author":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/ru\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/ru\/wp-json\/wp\/v2\/comments?post=22266"}],"version-history":[{"count":0,"href":"https:\/\/www.wehopower.com\/ru\/wp-json\/wp\/v2\/news\/22266\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/ru\/wp-json\/wp\/v2\/media\/22248"}],"wp:attachment":[{"href":"https:\/\/www.wehopower.com\/ru\/wp-json\/wp\/v2\/media?parent=22266"}],"wp:term":[{"taxonomy":"news_category","embeddable":true,"href":"https:\/\/www.wehopower.com\/ru\/wp-json\/wp\/v2\/news_category?post=22266"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}