{"id":20332,"date":"2026-10-29T10:08:47","date_gmt":"2026-10-29T02:08:47","guid":{"rendered":"https:\/\/www.wehopower.com\/news\/parallel-dc-conductor-voltage-drop-current-sharing\/"},"modified":"2026-10-29T10:08:47","modified_gmt":"2026-10-29T02:08:47","slug":"parallel-dc-conductor-voltage-drop-current-sharing","status":"publish","type":"news","link":"https:\/\/www.wehopower.com\/tl\/news\/parallel-dc-conductor-voltage-drop-current-sharing\/","title":{"rendered":"Parallel DC Conductors: Calculate Voltage Drop Without Assuming Equal Current"},"content":{"rendered":"<div class=\"weho-blog-content\">\n<p class=\"lead\"><strong>Do not divide total DC current equally between parallel conductors unless the complete path resistances justify that assumption.<\/strong> Calculate the parallel combination, include contact and return-path resistance, then check the voltage and current in credible unequal or unavailable-path states. A satisfactory nominal voltage-drop result does not establish conductor ampacity, terminal suitability or fault protection.<\/p>\n<details class=\"article-toc\" open>\n<summary>On this page<\/summary>\n<ol class=\"toc-list\">\n<li><a href=\"#draw-calculation-boundary\">Define where the paths split and rejoin<\/a><\/li>\n<li><a href=\"#unequal-path-example\">Worked example with two unequal outbound paths<\/a><\/li>\n<li><a href=\"#loss-and-contact-change\">Check loss and a changed contact condition<\/a><\/li>\n<li><a href=\"#unavailable-path\">Evaluate a path that becomes unavailable<\/a><\/li>\n<li><a href=\"#qualification-record\">Build a path-level acceptance record<\/a><\/li>\n<li><a href=\"#supply-and-path-review\">Keep the supply\u2019s limits in the same review<\/a><\/li>\n<\/ol>\n<\/details>\n<p>This guide concerns multiple conducting paths from one DC source to a load. It does not approve paralleling power-supply outputs. It uses stated resistance values rather than selecting a wire size or interpreting installation rules.<\/p>\n<div id=\"ez-toc-container\" class=\"ez-toc-v2_0_86 counter-hierarchy ez-toc-counter ez-toc-grey ez-toc-container-direction\">\n<div class=\"ez-toc-title-container\">\n<p class=\"ez-toc-title\" style=\"cursor:inherit\">Talaan ng mga Nilalaman<\/p>\n<span class=\"ez-toc-title-toggle\"><a href=\"#\" class=\"ez-toc-pull-right ez-toc-btn ez-toc-btn-xs ez-toc-btn-default ez-toc-toggle\" aria-label=\"Toggle Table of Content\"><span class=\"ez-toc-js-icon-con\"><span class=\"\"><span class=\"eztoc-hide\" style=\"display:none;\">I-toggle<\/span><span class=\"ez-toc-icon-toggle-span\"><svg style=\"fill: #999;color:#999\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" class=\"list-377408\" width=\"20px\" height=\"20px\" viewbox=\"0 0 24 24\" fill=\"none\"><path d=\"M6 6H4v2h2V6zm14 0H8v2h12V6zM4 11h2v2H4v-2zm16 0H8v2h12v-2zM4 16h2v2H4v-2zm16 0H8v2h12v-2z\" fill=\"currentColor\"><\/path><\/svg><svg style=\"fill: #999;color:#999\" class=\"arrow-unsorted-368013\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" width=\"10px\" height=\"10px\" viewbox=\"0 0 24 24\" version=\"1.2\" baseprofile=\"tiny\"><path d=\"M18.2 9.3l-6.2-6.3-6.2 6.3c-.2.2-.3.4-.3.7s.1.5.3.7c.2.2.4.3.7.3h11c.3 0 .5-.1.7-.3.2-.2.3-.5.3-.7s-.1-.5-.3-.7zM5.8 14.7l6.2 6.3 6.2-6.3c.2-.2.3-.5.3-.7s-.1-.5-.3-.7c-.2-.2-.4-.3-.7-.3h-11c-.3 0-.5.1-.7.3-.2.2-.3.5-.3.7s.1.5.3.7z\"\/><\/svg><\/span><\/span><\/span><\/a><\/span><\/div>\n<nav><ul class='ez-toc-list ez-toc-list-level-1' ><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-1\" href=\"https:\/\/www.wehopower.com\/tl\/news\/parallel-dc-conductor-voltage-drop-current-sharing\/#Define_where_the_paths_split_and_rejoin\" >Define where the paths split and rejoin<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-2\" href=\"https:\/\/www.wehopower.com\/tl\/news\/parallel-dc-conductor-voltage-drop-current-sharing\/#Worked_example_with_two_unequal_outbound_paths\" >Worked example with two unequal outbound paths<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-3\" href=\"https:\/\/www.wehopower.com\/tl\/news\/parallel-dc-conductor-voltage-drop-current-sharing\/#Check_loss_and_a_changed_contact_condition\" >Check loss and a changed contact condition<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-4\" href=\"https:\/\/www.wehopower.com\/tl\/news\/parallel-dc-conductor-voltage-drop-current-sharing\/#Evaluate_a_path_that_becomes_unavailable\" >Evaluate a path that becomes unavailable<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-5\" href=\"https:\/\/www.wehopower.com\/tl\/news\/parallel-dc-conductor-voltage-drop-current-sharing\/#Build_a_path-level_acceptance_record\" >Build a path-level acceptance record<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-6\" href=\"https:\/\/www.wehopower.com\/tl\/news\/parallel-dc-conductor-voltage-drop-current-sharing\/#Keep_the_supplys_limits_in_the_same_review\" >Keep the supply\u2019s limits in the same review<\/a><\/li><\/ul><\/nav><\/div>\n<h2 id=\"draw-calculation-boundary\"><span class=\"ez-toc-section\" id=\"Define_where_the_paths_split_and_rejoin\"><\/span>Define where the paths split and rejoin<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Identify the two common nodes of the parallel section. Each path resistance must include the relevant conductor, connector and contact contributions between those nodes. Anything shared before the split or after the join carries total current and must be accounted for separately.<\/p>\n<p>A cable-length comparison alone can miss unequal terminations or a shared return. Record whether each resistance is a supplier value, an estimate or a measurement, and at what temperature and condition. A milliohm figure without its boundary is easy to use twice or omit from the loop.<\/p>\n<p><a href=\"https:\/\/openstax.org\/books\/university-physics-volume-2\/pages\/10-2-resistors-in-series-and-parallel\" target=\"_blank\" rel=\"noopener\">OpenStax\u2019s series and parallel resistance treatment<\/a> establishes the calculation basis: parallel paths have the same voltage across their common nodes, while their currents depend on resistance. Current divides inversely with resistance, and the individual currents add to the total.<\/p>\n<h2 id=\"unequal-path-example\"><span class=\"ez-toc-section\" id=\"Worked_example_with_two_unequal_outbound_paths\"><\/span>Worked example with two unequal outbound paths<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Assume a source remains exactly 24.00 V at its output terminals and the load draws a fixed 10.00 A. The outbound paths connect the same two nodes. Path 1 is 0.040 \u03a9 and path 2 is 0.060 \u03a9, including their respective contacts. A shared return adds 0.030 \u03a9. These are hypothetical complete-path resistances, not cable recommendations.<\/p>\n<p>The outbound equivalent is R = (0.040 \u00d7 0.060) \u00f7 (0.040 + 0.060) = 0.024 \u03a9. Its drop is 10.00 A \u00d7 0.024 \u03a9 = 0.240 V. Path currents are 0.240 \u00f7 0.040 = 6.00 A and 0.240 \u00f7 0.060 = 4.00 A. Assigning 5 A to each path would contradict the assumed resistances.<\/p>\n<figure class=\"article-relation concept-diagram\" id=\"figure-unequal-path-record\"><a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/10\/63-unequal-path-record.svg\" aria-label=\"Open full-size Unequal resistance means unequal current diagram\"><picture><source media=\"(max-width:640px)\" srcset=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/10\/63-unequal-path-record-mobile.svg\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/10\/63-unequal-path-record.svg\" width=\"1200\" height=\"473\" alt=\"Parallel DC Conductors: Calculate Voltage Drop Without Assuming Equal Current  title=\" parallel dc conductors: calculate voltage drop without assuming equal current title =\"\"><\/picture><\/a><figcaption>Calculation example with fixed 10 A load and stated complete-path resistances. This is not a cable-size, terminal or protection recommendation.<\/figcaption><a class=\"diagram-original\" href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/10\/63-unequal-path-record.svg\">Open full-size diagram<\/a><\/figure>\n<p>The return drop is 10.00 A \u00d7 0.030 \u03a9 = 0.300 V. Total modeled loop drop is 0.540 V, leaving 23.460 V at the load. The return cannot be halved merely because the outbound side contains two paths. The same boundary discipline applies if both outbound and return sections have parallel paths: calculate each actual section.<\/p>\n<h2 id=\"loss-and-contact-change\"><span class=\"ez-toc-section\" id=\"Check_loss_and_a_changed_contact_condition\"><\/span>Check loss and a changed contact condition<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>For the original assumptions, path 1 dissipates 6\u00b2 \u00d7 0.040 = 1.44 W; path 2 dissipates 4\u00b2 \u00d7 0.060 = 0.96 W. The return dissipates 10\u00b2 \u00d7 0.030 = 3.00 W. Total modeled loss is 5.40 W, also equal to 10 A \u00d7 0.540 V.<\/p>\n<p>These losses do not predict component temperature. Heat transfer, contact location, ambient conditions and material limits still require assessment. A short high-resistance termination and a long distributed conductor can have the same calculated resistance but different thermal consequences.<\/p>\n<p>Now assume path 1 rises to 0.080 \u03a9 while path 2 stays at 0.060 \u03a9. The parallel equivalent becomes approximately 0.03429 \u03a9, giving 0.3429 V outbound drop. Current shifts to approximately 4.286 A in path 1 and 5.714 A in path 2. The modeled load voltage falls to approximately 23.357 V after adding the unchanged return drop.<\/p>\n<p>A higher-resistance path therefore need not become the higher-current path. Examine where the resistance and dissipation occur rather than inferring a healthy connection from the total current alone. This is one reason to retain path-level measurements during qualification.<\/p>\n<h2 id=\"unavailable-path\"><span class=\"ez-toc-section\" id=\"Evaluate_a_path_that_becomes_unavailable\"><\/span>Evaluate a path that becomes unavailable<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Return to the original resistances and assume path 2 opens. Path 1 now carries the full assumed 10 A. Its outbound drop becomes 0.400 V and total loop drop becomes 0.700 V, leaving 23.300 V at the load. Its modeled loss rises to 4.00 W.<\/p>\n<p>The remaining path has increased from 6 A to 10 A. Even if 23.300 V meets the load\u2019s voltage requirement, the surviving conductor, terminals and protection must independently support the relevant condition. This arithmetic does not establish permission for continued operation after a path failure.<\/p>\n<p>The example holds load current constant. A constant-power electronic load may draw more current as its terminal voltage falls; a startup pulse may follow another demand profile. Use the actual load behavior for the final system analysis instead of extending the fixed-current numbers to every operating state.<\/p>\n<h2 id=\"qualification-record\"><span class=\"ez-toc-section\" id=\"Build_a_path-level_acceptance_record\"><\/span>Build a path-level acceptance record<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<div class=\"table-wrap\">\n<div class=\"weho-table-wrap\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable article table\">\n<table>\n<thead>\n<tr>\n<th>Record<\/th>\n<th>What to include<\/th>\n<th>Why it affects the decision<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Electrical boundary<\/td>\n<td>Split\/join nodes, shared sections and return paths<\/td>\n<td>Prevents omitted or double-counted resistance<\/td>\n<\/tr>\n<tr>\n<td>Resistance basis<\/td>\n<td>Path, contacts, temperature and tolerance or measured condition<\/td>\n<td>Determines division and total loop drop<\/td>\n<\/tr>\n<tr>\n<td>Load states<\/td>\n<td>Continuous demand, transitions and relevant unavailable-path cases<\/td>\n<td>Defines the current that each path may carry<\/td>\n<\/tr>\n<tr>\n<td>Hardware permission<\/td>\n<td>Terminal conductor acceptance and applicable assembly\/protection instructions<\/td>\n<td>A low calculated drop does not qualify the connection method<\/td>\n<\/tr>\n<tr>\n<td>Verification<\/td>\n<td>Source\/load voltage, each path current and relevant temperatures<\/td>\n<td>Checks the calculation against the actual assembly<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<\/div>\n<p>Qualified personnel should make connection and measurement changes under the applicable safe procedure. Do not create an open-path fault by disturbing an energized unknown connection. Define a controlled test arrangement and stop conditions before validating a degraded state.<\/p>\n<h2 id=\"supply-and-path-review\"><span class=\"ez-toc-section\" id=\"Keep_the_supplys_limits_in_the_same_review\"><\/span>Keep the supply\u2019s limits in the same review<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Do not turn up a supply simply to hide unexplained path loss. The source setting, near-end loads and permitted adjustment range still matter. <a href=\"https:\/\/www.us.lambda.tdk.com\/resources\/blogs\/20130402.html\" target=\"_blank\" rel=\"noopener\">TDK-Lambda\u2019s remote-sense discussion<\/a> concerns supplies designed for that function; it is not evidence that a WEHO model supports remote sense or that compensation resolves a poor connection.<\/p>\n<p>A connection review can start with the <a href=\"https:\/\/www.wehopower.com\/tl\/product\/lrs-series-350w-ac-to-dc-single-output-switching-power-supply\/\">WEHO LRS-350-24 product identity<\/a>, its <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2021\/10\/LRS-350-1.pdf\">published terminal assignments<\/a> and the full product photograph. The repeated output markings are not permission to place multiple conductors in one terminal or a guarantee of current sharing. Obtain the applicable terminal and conductor instructions for the ordered unit; keep the path-resistance calculation separate from those assembly permissions.<\/p>\n<figure class=\"product-reference\" id=\"figure-product-lrs-full\"><a class=\"product-image\" href=\"https:\/\/www.wehopower.com\/tl\/product\/lrs-series-350w-ac-to-dc-single-output-switching-power-supply\/\" aria-label=\"LRS-350-24 product details\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/10\/63-product-lrs-full-display.svg\" width=\"410\" height=\"710\" alt=\"Parallel DC Conductors: Calculate Voltage Drop Without Assuming Equal Current  title=\" parallel dc conductors: calculate voltage drop without assuming equal current title =\"\"><\/a><figcaption>WEHO LRS-350-24 complete-product view for the connection-document review. The photograph does not establish multiple-conductor termination permission, conductor ratings or equal current sharing.<\/figcaption><div class=\"image-actions\"><a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/10\/63-product-lrs-full-original.jpg\">View unchanged original photograph<\/a><a href=\"https:\/\/www.wehopower.com\/tl\/product\/lrs-series-350w-ac-to-dc-single-output-switching-power-supply\/\">LRS-350-24 product details<\/a><a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2021\/10\/LRS-350-1.pdf\">LRS-350-24 documentation<\/a><\/div>\n<\/figure>\n<p>Send WEHO the proposed source model, load-current states, allowed voltage at the load and the path-resistance record. Keep conductor selection, terminals and protection with the responsible assembly engineer while reviewing the supply\u2019s own operating limits.<\/p>\n<p><a class=\"primary-cta\" href=\"https:\/\/www.wehopower.com\/tl\/contact\/\" data-link-role=\"inquiry\">Discuss the source and load-voltage requirements<\/a><\/p>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>Parallel conductors reduce equivalent resistance, but unequal path resistance prevents an automatic equal-current split.<\/p>","protected":false},"author":2,"featured_media":20310,"parent":0,"menu_order":28,"comment_status":"","ping_status":"","template":"","format":"standard","meta":{"_acf_changed":false,"_joinchat":[],"footnotes":""},"news_category":[284],"class_list":["post-20332","news","type-news","status-publish","format-standard","has-post-thumbnail","hentry","news_category-product-articles","entry"],"acf":[],"post_mailing_queue_ids":[],"_links":{"self":[{"href":"https:\/\/www.wehopower.com\/tl\/wp-json\/wp\/v2\/news\/20332","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.wehopower.com\/tl\/wp-json\/wp\/v2\/news"}],"about":[{"href":"https:\/\/www.wehopower.com\/tl\/wp-json\/wp\/v2\/types\/news"}],"author":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/tl\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/tl\/wp-json\/wp\/v2\/comments?post=20332"}],"version-history":[{"count":0,"href":"https:\/\/www.wehopower.com\/tl\/wp-json\/wp\/v2\/news\/20332\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/tl\/wp-json\/wp\/v2\/media\/20310"}],"wp:attachment":[{"href":"https:\/\/www.wehopower.com\/tl\/wp-json\/wp\/v2\/media?parent=20332"}],"wp:term":[{"taxonomy":"news_category","embeddable":true,"href":"https:\/\/www.wehopower.com\/tl\/wp-json\/wp\/v2\/news_category?post=20332"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}