{"id":23062,"date":"2026-11-19T09:51:28","date_gmt":"2026-11-19T01:51:28","guid":{"rendered":"https:\/\/www.wehopower.com\/news\/pid-proportional-band-units-gain\/"},"modified":"2026-11-19T09:51:28","modified_gmt":"2026-11-19T01:51:28","slug":"pid-proportional-band-units-gain","status":"publish","type":"news","link":"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/","title":{"rendered":"TX4-L PID Reviews: Separate Proportional Band Units from Gain"},"content":{"rendered":"<div class=\"weho-blog\">\n<p>Do not transfer a PID proportional setting by copying its number alone. Establish whether the parameter represents a temperature band, a percentage of span or a gain, then compare its units and control definition.<\/p>\n<ul>\n<li>Proportional band and proportional gain use different conventions.<\/li>\n<li>A band expressed in degrees needs a defined span before conversion to percent.<\/li>\n<li>A conversion supports comparison; it does not replace loop validation.<\/li>\n<\/ul>\n<figure data-role=\"hero\"><a href=\"https:\/\/www.wehopower.com\/tr\/product\/tx4-series-tx4-l-economic-dual-display-pid-temperature-controller\/\" aria-label=\"View TX4-L product details\"><img fetchpriority=\"high\" decoding=\"async\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/6e58f7753f903f80-tx4-l-pid-application.avif\" width=\"1200\" height=\"675\" alt=\"TX4-L PID Reviews: Separate Proportional Band Units from Gain  title=\" data-image-role=\"hero\" loading=\"eager\" tx4-l pid reviews: separate proportional band units from gain title =\"\"><\/a><figcaption>Application illustration; not a customer installation photo. Scene created with AI assistance using the original TX4-L front. Retained display artwork does not demonstrate a PID setting or a tuning result. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/9fdadce9ff6ebe9e-original-tx4-l-setpoint-window-application-1200x675-master.png\">View source image<\/a><\/figcaption><\/figure>\n<div id=\"ez-toc-container\" class=\"ez-toc-v2_0_89 counter-hierarchy ez-toc-counter ez-toc-grey ez-toc-container-direction\">\n<div class=\"ez-toc-title-container\">\n<p class=\"ez-toc-title\" style=\"cursor:inherit\">\u0130\u00e7indekiler<\/p>\n<span class=\"ez-toc-title-toggle\"><a href=\"#\" class=\"ez-toc-pull-right ez-toc-btn ez-toc-btn-xs ez-toc-btn-default ez-toc-toggle\" aria-label=\"\u0130\u00e7indekiler Tablosunu A\u00e7\/Kapat\"><span class=\"ez-toc-js-icon-con\"><span class=\"\"><span class=\"eztoc-hide\" style=\"display:none;\">Ge\u00e7i\u015f yapmak<\/span><span class=\"ez-toc-icon-toggle-span\"><svg style=\"fill: #999;color:#999\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" class=\"list-377408\" width=\"20px\" height=\"20px\" viewbox=\"0 0 24 24\" fill=\"none\"><path d=\"M6 6H4v2h2V6zm14 0H8v2h12V6zM4 11h2v2H4v-2zm16 0H8v2h12v-2zM4 16h2v2H4v-2zm16 0H8v2h12v-2z\" fill=\"currentColor\"><\/path><\/svg><svg style=\"fill: #999;color:#999\" class=\"arrow-unsorted-368013\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" width=\"10px\" height=\"10px\" viewbox=\"0 0 24 24\" version=\"1.2\" baseprofile=\"tiny\"><path d=\"M18.2 9.3l-6.2-6.3-6.2 6.3c-.2.2-.3.4-.3.7s.1.5.3.7c.2.2.4.3.7.3h11c.3 0 .5-.1.7-.3.2-.2.3-.5.3-.7s-.1-.5-.3-.7zM5.8 14.7l6.2 6.3 6.2-6.3c.2-.2.3-.5.3-.7s-.1-.5-.3-.7c-.2-.2-.4-.3-.7-.3h-11c-.3 0-.5.1-.7.3-.2.2-.3.5-.3.7s.1.5.3.7z\"\/><\/svg><\/span><\/span><\/span><\/a><\/span><\/div>\n<nav><ul class='ez-toc-list ez-toc-list-level-1' ><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-1\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#Why_can_the_same_proportional_number_produce_different_behavior\" >Why can the same proportional number produce different behavior?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-2\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#How_are_temperature_band_normalized_band_and_gain_related\" >How are temperature band, normalized band and gain related?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-3\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#What_assumptions_can_invalidate_a_direct_conversion\" >What assumptions can invalidate a direct conversion?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-4\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#How_should_a_migration_worksheet_be_built\" >How should a migration worksheet be built?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-5\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#Why_is_autotuning_not_a_substitute_for_parameter_identity\" >Why is autotuning not a substitute for parameter identity?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-6\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#Prepare_a_TX4-L_parameter_comparison\" >Prepare a TX4-L parameter comparison<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-7\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#Frequently_asked_questions\" >Frequently asked questions<\/a><ul class='ez-toc-list-level-3' ><li class='ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-8\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#Is_proportional_band_always_a_percentage\" >Is proportional band always a percentage?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-9\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#Does_a_narrower_band_mean_a_stronger_proportional_response\" >Does a narrower band mean a stronger proportional response?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-10\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#Can_Celsius_and_Fahrenheit_band_values_be_copied_directly\" >Can Celsius and Fahrenheit band values be copied directly?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-11\" href=\"https:\/\/www.wehopower.com\/tr\/news\/pid-proportional-band-units-gain\/#Does_equal_proportional_gain_prove_interchangeable_tuning\" >Does equal proportional gain prove interchangeable tuning?<\/a><\/li><\/ul><\/li><\/ul><\/nav><\/div>\n<h2 id=\"why-can-the-same-proportional-number-produce-different-behavior\"><span class=\"ez-toc-section\" id=\"Why_can_the_same_proportional_number_produce_different_behavior\"><\/span>Why can the same proportional number produce different behavior?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Two controllers can assign different meanings to the same numeric proportional setting. One may use a band in degrees, another a percentage of input span and another an output-to-error gain. A copied value can therefore change the effective control response even when both instruments display a parameter named P.<\/p>\n<p>For a <a href=\"https:\/\/www.wehopower.com\/tr\/product\/tx4-series-tx4-l-economic-dual-display-pid-temperature-controller\/\">TX4-L PID controller project<\/a>, use the applicable TX4 parameter definition. The official manual describes the proportional band in temperature units. That definition should be carried into the commissioning record rather than replaced by a generic percentage convention.<\/p>\n<p>The product and panel illustrations identify the model context. They do not show a transferred tuning set or establish a particular process response. Displayed source values remain artwork, not evidence of a tuning experiment or a measured heating result.<\/p>\n<p>This article helps an OEM compare parameter meanings before migration or replacement. It does not provide a universal tuning value. Heater size, sensor placement, thermal inertia, output device and control structure all affect the eventual loop behavior, even when the proportional conversion itself is correct.<\/p>\n<nav aria-label=\"Article contents\">\n<details>\n<summary>On this page<\/summary>\n<ol>\n<li><a href=\"#why-can-the-same-proportional-number-produce-different-behavior\">Why can the same proportional number produce different behavior?<\/a><\/li>\n<li><a href=\"#how-are-temperature-band-normalized-band-and-gain-related\">How are temperature band, normalized band and gain related?<\/a><\/li>\n<li><a href=\"#what-assumptions-can-invalidate-a-direct-conversion\">What assumptions can invalidate a direct conversion?<\/a><\/li>\n<li><a href=\"#how-should-a-migration-worksheet-be-built\">How should a migration worksheet be built?<\/a><\/li>\n<li><a href=\"#why-is-autotuning-not-a-substitute-for-parameter-identity\">Why is autotuning not a substitute for parameter identity?<\/a><\/li>\n<li><a href=\"#prepare-a-tx4-l-parameter-comparison\">Prepare a TX4-L parameter comparison<\/a><\/li>\n<li><a href=\"#frequently-asked-questions\">Frequently asked questions<\/a><\/li>\n<\/ol>\n<\/details>\n<\/nav>\n<h2 id=\"how-are-temperature-band-normalized-band-and-gain-related\"><span class=\"ez-toc-section\" id=\"How_are_temperature_band_normalized_band_and_gain_related\"><\/span>How are temperature band, normalized band and gain related?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>First define a normalized input span and an output scale. Under a simple convention in which proportional gain is output-percent change per input-percent error, K<sub>p<\/sub> = 100\/PB%, where PB% is the proportional band expressed as a percentage number. The relationship assumes those particular normalized scales.<\/p>\n<p>Consider a <strong>hypothetical<\/strong> proportional band of 20\u00b0C over an illustrative 0\u2013400\u00b0C normalization span. The band occupies 20\/400 \u00d7 100 = 5% of span. Under the stated convention, normalized gain is 100\/5 = 20 percent-output per percent-input error.<\/p>\n<p>In temperature units, the same simple proportional slope is 100\/20 = 5 percentage points of output per degree Celsius. An error change of 2\u00b0C would therefore correspond to a 10-percentage-point proportional-output change before considering bias, saturation, integral or derivative action.<\/p>\n<p>If someone interprets the original number 20 as a 20% band over the same 400\u00b0C span, the implied temperature band becomes 80\u00b0C. Its proportional slope is only 1.25 output percentage points per degree. The copied number has changed the proportional sensitivity by a factor of four.<\/p>\n<figure data-role=\"technical\">\n<div class=\"diagram-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering diagram\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/956ddd01460a23ab-pid-proportional-band-units-gain-engineering.svg\" width=\"1200\" height=\"675\" alt=\"TX4-L PID Reviews: Separate Proportional Band Units from Gain  title=\" data-image-role=\"technical\" tx4-l pid reviews: separate proportional band units from gain title =\"\"><\/div><figcaption>Conceptual Engineering Diagram. Under these scales, normalized Kp = 100 \/ PB%. Validate the complete loop separately. All numerical inputs are hypothetical unless identified as mathematical relationships; no measured product performance is presented. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/956ddd01460a23ab-pid-proportional-band-units-gain-engineering.svg\">View source image<\/a><\/figcaption><\/figure>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<thead>\n<tr>\n<th>Hypothetical interpretation<\/th>\n<th>Temperature band<\/th>\n<th>Normalized band<\/th>\n<th>Simple output slope<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>20\u00b0C band over a 400\u00b0C span<\/td>\n<td>20\u00b0C<\/td>\n<td>5%<\/td>\n<td>5 percentage points\/\u00b0C<\/td>\n<\/tr>\n<tr>\n<td>20% band over a 400\u00b0C span<\/td>\n<td>80\u00b0C<\/td>\n<td>20%<\/td>\n<td>1.25 percentage points\/\u00b0C<\/td>\n<\/tr>\n<tr>\n<td>Normalized gain of 20<\/td>\n<td>20\u00b0C under these scales<\/td>\n<td>5%<\/td>\n<td>5 percentage points\/\u00b0C<\/td>\n<\/tr>\n<tr>\n<td>Undefined P = 20<\/td>\n<td>Unknown<\/td>\n<td>Unknown<\/td>\n<td>Cannot be compared reliably<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<h2 id=\"what-assumptions-can-invalidate-a-direct-conversion\"><span class=\"ez-toc-section\" id=\"What_assumptions_can_invalidate_a_direct_conversion\"><\/span>What assumptions can invalidate a direct conversion?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>The normalization span must be explicit. It may be the configured input range, an engineering-unit scale or another definition provided by the controller manufacturer. Do not choose the span merely because it produces a convenient conversion or matches the machine&#39;s usual setpoint interval.<\/p>\n<p>Control action and algorithm form also matter. A heating loop and a cooling loop may use different sign conventions, while interacting and noninteracting PID forms can interpret integral and derivative parameters differently. Matching proportional sensitivity alone does not establish equivalent overall tuning.<\/p>\n<p>The <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2023\/11\/TX4.pdf\">official TX4 manual<\/a> should define the supplied controller&#39;s parameter meaning. Use the other controller&#39;s own manual for its convention. External terminology guidance, such as <a href=\"https:\/\/www.ia.omron.com\/support\/guide\/53\/explanation_of_terms.html\" target=\"_blank\" rel=\"noopener\">OMRON&#39;s temperature-control explanations<\/a>, supports the distinction but does not define a WEHO variant&#39;s undocumented options.<\/p>\n<p>Check how output bias, limits and operating mode affect the comparison. A saturated output can hide the difference between two proportional settings during a large step. Compare the relevant unsaturated behavior within an appropriate test, then assess the actual controlled process under its own acceptance criteria.<\/p>\n<h2 id=\"how-should-a-migration-worksheet-be-built\"><span class=\"ez-toc-section\" id=\"How_should_a_migration_worksheet_be_built\"><\/span>How should a migration worksheet be built?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Give each parameter a name, physical meaning, unit, source definition and proposed destination value. Include the input span and output scale used in every calculation. Keep the original values so the responsible engineer can reconstruct the migration rather than rely on a final list of numbers.<\/p>\n<ol>\n<li>Identify the exact source and destination controller configurations.<\/li>\n<li>Extract each proportional definition from its applicable manual.<\/li>\n<li>Convert through explicit engineering or normalized units where justified.<\/li>\n<li>Review integral, derivative, cycle and output settings separately.<\/li>\n<li>Validate the proposed settings on the actual process under a controlled plan.<\/li>\n<\/ol>\n<p>Qualified personnel should manage the effects of changed control settings. A more aggressive loop can alter heater operation and process temperature, while an incorrect control direction can produce a more serious response. Do not perform an uncontrolled setting transfer during production simply because the conversion arithmetic is complete.<\/p>\n<p>Record the test&#39;s starting condition and disturbance. Comparing one controller on a cold empty process with another on a warm loaded process does not isolate the tuning difference. A useful comparison needs matched or explicitly accounted-for conditions and an acceptance criterion related to the actual process requirement.<\/p>\n<h2 id=\"why-is-autotuning-not-a-substitute-for-parameter-identity\"><span class=\"ez-toc-section\" id=\"Why_is_autotuning_not_a_substitute_for_parameter_identity\"><\/span>Why is autotuning not a substitute for parameter identity?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Autotuning, where supported and appropriate to the supplied configuration, can generate settings for its observed process condition. It does not explain an undocumented parameter convention or guarantee an acceptable result under every load. The settings still require a defined handover record and relevant process verification.<\/p>\n<p>The <a href=\"https:\/\/www.wehopower.com\/tr\/product\/tx4-series-tx4-l-economic-dual-display-pid-temperature-controller\/\">TX4-L product information<\/a> provides the entry for confirming the actual model arrangement. Avoid inferring supported output combinations, control functions or migration tools from another size in the family. A common front-panel style does not prove identical installed options.<\/p>\n<p>When a comparison fails, preserve the original settings and observed response before changing multiple parameters. A factor-of-four proportional mistake can otherwise become buried under several compensating adjustments. Resolving the definition first usually produces a more understandable engineering record than tuning around an unknown conversion.<\/p>\n<p>A commissioning report should distinguish a successful unit conversion from a successful process test. The former means that the parameter relationship has been interpreted consistently. The latter requires evidence that the machine meets its temperature, recovery and operating requirements under the documented conditions.<\/p>\n<p>Keep interval conversions separate from absolute-temperature conversions. Proportional-band width is a temperature difference: converting it between Celsius and Fahrenheit scales uses the scale factor, without adding an absolute offset. Setpoints and alarm temperatures require their own appropriate conversion.<\/p>\n<p>A worksheet should preserve the algorithm conventions even when no direct conversion is justified. Writing that two definitions require further validation is more useful than forcing them into one number. The actual controlled response, rather than the appearance of matching settings, determines whether the proposed migration meets the project requirement.<\/p>\n<figure data-role=\"product\"><a href=\"https:\/\/www.wehopower.com\/tr\/product\/tx4-series-tx4-l-economic-dual-display-pid-temperature-controller\/\" aria-label=\"View TX4-L product details\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/deafae329e2e996c-tx4-l-pid-product-reference.avif\" width=\"1000\" height=\"1000\" alt=\"TX4-L PID Reviews: Separate Proportional Band Units from Gain  title=\" data-image-role=\"product\" tx4-l pid reviews: separate proportional band units from gain title =\"\"><\/a><figcaption>Official TX4-L product photograph. Original markings and source clarity are retained; the image is not a test or configuration record. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/7322af719d366bd8-original-tx4-l-official.png\">View source image<\/a><\/figcaption><\/figure>\n<h2 id=\"prepare-a-tx4-l-parameter-comparison\"><span class=\"ez-toc-section\" id=\"Prepare_a_TX4-L_parameter_comparison\"><\/span>Prepare a TX4-L parameter comparison<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Send WEHO the supplied variant, applicable parameter pages, input span and existing tuning record. State whether the goal is understanding a parameter or replacing another controller. Include the process test requirements so the discussion can connect a correct definition with the actual engineering decision rather than produce an unsupported universal setting.<\/p>\n<h2 id=\"frequently-asked-questions\"><span class=\"ez-toc-section\" id=\"Frequently_asked_questions\"><\/span>Frequently asked questions<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<h3 id=\"is-proportional-band-always-a-percentage\"><span class=\"ez-toc-section\" id=\"Is_proportional_band_always_a_percentage\"><\/span>Is proportional band always a percentage?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. It can be expressed in engineering units or normalized units depending on the controller. Read the parameter definition and carry its unit into the worksheet before comparing values.<\/p>\n<h3 id=\"does-a-narrower-band-mean-a-stronger-proportional-response\"><span class=\"ez-toc-section\" id=\"Does_a_narrower_band_mean_a_stronger_proportional_response\"><\/span>Does a narrower band mean a stronger proportional response?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>Under the same band definition and scaling, a narrower band gives a larger proportional-output change for the same error change. That relationship alone does not predict the stability of the complete PID loop.<\/p>\n<h3 id=\"can-celsius-and-fahrenheit-band-values-be-copied-directly\"><span class=\"ez-toc-section\" id=\"Can_Celsius_and_Fahrenheit_band_values_be_copied_directly\"><\/span>Can Celsius and Fahrenheit band values be copied directly?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. A temperature interval of 20\u00b0C corresponds to 36\u00b0F, without adding the 32-degree absolute-temperature offset. Confirm how the controller handles unit changes and verify the complete configuration afterward.<\/p>\n<h3 id=\"does-equal-proportional-gain-prove-interchangeable-tuning\"><span class=\"ez-toc-section\" id=\"Does_equal_proportional_gain_prove_interchangeable_tuning\"><\/span>Does equal proportional gain prove interchangeable tuning?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Integral and derivative conventions, output timing, limits, sensor dynamics and process conditions can differ. Use the conversion as one documented comparison step, then validate the relevant complete-loop behavior.<\/p>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>Compare PID proportional-band settings using defined units and scaling for a TX4-L project. Prepare the control record before transferring settings.<\/p>","protected":false},"author":2,"featured_media":23044,"parent":0,"menu_order":9,"comment_status":"","ping_status":"","template":"","format":"standard","meta":{"_acf_changed":false,"_joinchat":[],"footnotes":""},"news_category":[284],"class_list":["post-23062","news","type-news","status-publish","format-standard","has-post-thumbnail","hentry","news_category-product-articles","entry"],"acf":[],"post_mailing_queue_ids":[],"_links":{"self":[{"href":"https:\/\/www.wehopower.com\/tr\/wp-json\/wp\/v2\/news\/23062","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.wehopower.com\/tr\/wp-json\/wp\/v2\/news"}],"about":[{"href":"https:\/\/www.wehopower.com\/tr\/wp-json\/wp\/v2\/types\/news"}],"author":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/tr\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/tr\/wp-json\/wp\/v2\/comments?post=23062"}],"version-history":[{"count":0,"href":"https:\/\/www.wehopower.com\/tr\/wp-json\/wp\/v2\/news\/23062\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/tr\/wp-json\/wp\/v2\/media\/23044"}],"wp:attachment":[{"href":"https:\/\/www.wehopower.com\/tr\/wp-json\/wp\/v2\/media?parent=23062"}],"wp:term":[{"taxonomy":"news_category","embeddable":true,"href":"https:\/\/www.wehopower.com\/tr\/wp-json\/wp\/v2\/news_category?post=23062"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}