{"id":23063,"date":"2026-11-19T09:51:39","date_gmt":"2026-11-19T01:51:39","guid":{"rendered":"https:\/\/www.wehopower.com\/news\/heater-command-current-feedback-check\/"},"modified":"2026-11-19T09:51:39","modified_gmt":"2026-11-19T01:51:39","slug":"heater-command-current-feedback-check","status":"publish","type":"news","link":"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/","title":{"rendered":"TX4-S Heater Checks: Separate the Command from Delivered Current"},"content":{"rendered":"<div class=\"weho-blog\">\n<p>A heating command shows what the control system requests; it does not prove that the heater receives the intended current. Compare command state and actual load-current evidence before changing PID settings or replacing the controller.<\/p>\n<ul>\n<li>Record the controller request and the delivered heater current separately.<\/li>\n<li>Consider switching-device, heater, supply and measurement faults.<\/li>\n<li>Treat external protective functions as separate from ordinary temperature regulation.<\/li>\n<\/ul>\n<figure data-role=\"hero\"><a href=\"https:\/\/www.wehopower.com\/ur\/product\/tx4-series-tx4-s-economic-dual-display-pid-temperature-controller\/\" aria-label=\"View TX4-S product details\"><img fetchpriority=\"high\" decoding=\"async\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/71c746cd2c5d2790-tx4-s-heater-application.avif\" width=\"1200\" height=\"675\" alt=\"TX4-S Heater Checks: Separate the Command from Delivered Current  title=\" data-image-role=\"hero\" loading=\"eager\" tx4-s heater checks: separate the command from delivered current title =\"\"><\/a><figcaption>Application illustration; not a customer installation photo. Scene created with AI assistance. The inactive TX4-S front and generic protected connection do not show heater-current feedback or rear terminal wiring. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/a107b6959d4fc478-original-tx4-s-control-direction-application-1200x675-master.png\">View source image<\/a><\/figcaption><\/figure>\n<div id=\"ez-toc-container\" class=\"ez-toc-v2_0_89 counter-hierarchy ez-toc-counter ez-toc-grey ez-toc-container-direction\">\n<div class=\"ez-toc-title-container\">\n<p class=\"ez-toc-title\" style=\"cursor:inherit\">\u0645\u0646\u062f\u0631\u062c\u0627\u062a \u06a9\u0627 \u062c\u062f\u0648\u0644<\/p>\n<span class=\"ez-toc-title-toggle\"><a href=\"#\" class=\"ez-toc-pull-right ez-toc-btn ez-toc-btn-xs ez-toc-btn-default ez-toc-toggle\" aria-label=\"Toggle Table of Content\"><span class=\"ez-toc-js-icon-con\"><span class=\"\"><span class=\"eztoc-hide\" style=\"display:none;\">\u0679\u0648\u06af\u0644 \u06a9\u0631\u06cc\u06ba\u06d4<\/span><span class=\"ez-toc-icon-toggle-span\"><svg style=\"fill: #999;color:#999\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" class=\"list-377408\" width=\"20px\" height=\"20px\" viewbox=\"0 0 24 24\" fill=\"none\"><path d=\"M6 6H4v2h2V6zm14 0H8v2h12V6zM4 11h2v2H4v-2zm16 0H8v2h12v-2zM4 16h2v2H4v-2zm16 0H8v2h12v-2z\" fill=\"currentColor\"><\/path><\/svg><svg style=\"fill: #999;color:#999\" class=\"arrow-unsorted-368013\" xmlns=\"http:\/\/www.w3.org\/2000\/svg\" width=\"10px\" height=\"10px\" viewbox=\"0 0 24 24\" version=\"1.2\" baseprofile=\"tiny\"><path d=\"M18.2 9.3l-6.2-6.3-6.2 6.3c-.2.2-.3.4-.3.7s.1.5.3.7c.2.2.4.3.7.3h11c.3 0 .5-.1.7-.3.2-.2.3-.5.3-.7s-.1-.5-.3-.7zM5.8 14.7l6.2 6.3 6.2-6.3c.2-.2.3-.5.3-.7s-.1-.5-.3-.7c-.2-.2-.4-.3-.7-.3h-11c-.3 0-.5.1-.7.3-.2.2-.3.5-.3.7s.1.5.3.7z\"\/><\/svg><\/span><\/span><\/span><\/a><\/span><\/div>\n<nav><ul class='ez-toc-list ez-toc-list-level-1' ><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-1\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#Why_does_the_output_indicator_not_prove_heater_operation\" >Why does the output indicator not prove heater operation?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-2\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#What_can_a_command-current_state_table_establish\" >What can a command-current state table establish?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-3\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#What_external_switching_evidence_is_needed\" >What external switching evidence is needed?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-4\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#How_should_timing_be_handled_for_time-proportioned_outputs\" >How should timing be handled for time-proportioned outputs?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-5\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#What_should_a_supplier_receive_before_the_controller_is_replaced\" >What should a supplier receive before the controller is replaced?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-6\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#Prepare_a_TX4-S_heating-path_review\" >Prepare a TX4-S heating-path review<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-2'><a class=\"ez-toc-link ez-toc-heading-7\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#Frequently_asked_questions\" >Frequently asked questions<\/a><ul class='ez-toc-list-level-3' ><li class='ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-8\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#Does_an_ON_indicator_prove_that_the_heater_receives_power\" >Does an ON indicator prove that the heater receives power?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-9\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#Can_current_flowing_with_an_OFF_command_be_ignored_as_normal_leakage\" >Can current flowing with an OFF command be ignored as normal leakage?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-10\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#Does_zero_measured_current_prove_safe_isolation\" >Does zero measured current prove safe isolation?<\/a><\/li><li class='ez-toc-page-1 ez-toc-heading-level-3'><a class=\"ez-toc-link ez-toc-heading-11\" href=\"https:\/\/www.wehopower.com\/ur\/news\/heater-command-current-feedback-check\/#Should_PID_tuning_be_changed_when_commanded_heat_produces_no_current\" >Should PID tuning be changed when commanded heat produces no current?<\/a><\/li><\/ul><\/li><\/ul><\/nav><\/div>\n<h2 id=\"why-does-the-output-indicator-not-prove-heater-operation\"><span class=\"ez-toc-section\" id=\"Why_does_the_output_indicator_not_prove_heater_operation\"><\/span>Why does the output indicator not prove heater operation?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>An output indicator represents a control state, not a direct measurement of every downstream component. A command can be present while a heater circuit is open, or absent while a failed switching path continues conducting. The exact interpretation depends on the supplied controller and external switching arrangement.<\/p>\n<p>For an OEM integrating a <a href=\"https:\/\/www.wehopower.com\/ur\/product\/tx4-series-tx4-s-economic-dual-display-pid-temperature-controller\/\">TX4-S temperature controller<\/a>, verify the ordered output type and applicable connection diagram. Do not infer a current-monitoring input, heater-break alarm or independent shutdown capability from the controller&#39;s front-panel appearance.<\/p>\n<p>The application scene shows the controller&#39;s panel context. Its inactive display does not establish a measured heater current or an actual fault condition. The technical state table below is a separate conceptual example, not evidence that TX4-S provides built-in monitoring for every listed state.<\/p>\n<p>This distinction helps avoid unnecessary tuning changes. If the controller requests heat but a disconnected heater draws no current, altering the proportional band cannot repair the open circuit. If current continues when heat is not requested, a different and potentially more serious path needs investigation under the equipment procedure.<\/p>\n<nav aria-label=\"Article contents\">\n<details>\n<summary>On this page<\/summary>\n<ol>\n<li><a href=\"#why-does-the-output-indicator-not-prove-heater-operation\">Why does the output indicator not prove heater operation?<\/a><\/li>\n<li><a href=\"#what-can-a-command-current-state-table-establish\">What can a command-current state table establish?<\/a><\/li>\n<li><a href=\"#what-external-switching-evidence-is-needed\">What external switching evidence is needed?<\/a><\/li>\n<li><a href=\"#how-should-timing-be-handled-for-time-proportioned-outputs\">How should timing be handled for time-proportioned outputs?<\/a><\/li>\n<li><a href=\"#what-should-a-supplier-receive-before-the-controller-is-replaced\">What should a supplier receive before the controller is replaced?<\/a><\/li>\n<li><a href=\"#prepare-a-tx4-s-heating-path-review\">Prepare a TX4-S heating-path review<\/a><\/li>\n<li><a href=\"#frequently-asked-questions\">Frequently asked questions<\/a><\/li>\n<\/ol>\n<\/details>\n<\/nav>\n<h2 id=\"what-can-a-command-current-state-table-establish\"><span class=\"ez-toc-section\" id=\"What_can_a_command-current_state_table_establish\"><\/span>What can a command-current state table establish?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>A state table compares two independent observations and identifies the next diagnostic question. It does not prove a unique failed component. A missing current reading may come from the load path, the supply state or the measuring system itself.<\/p>\n<p>Consider a <strong>hypothetical<\/strong> resistive heating branch that draws 4.0 A during a valid ON interval. An externally established observation threshold of 0.2 A is used only to distinguish substantial conduction from the example&#39;s measurement noise and expected residual behavior. That threshold is not a TX4-S or universal heater-protection setting.<\/p>\n<p>When the command is ON and measured current is 4.0 A, the record supports that current flowed in the measured branch. It does not prove that heat reached the workpiece correctly. When the command is ON and current is below the chosen threshold, the branch needs investigation without assuming the controller is defective.<\/p>\n<p>When the command is OFF and substantial current remains, establish the actual switching topology and source paths. Solid-state switching devices can fail conducting; other paths can also exist. Do not use this table as an instruction to work on an energized heater or as a substitute for the machine&#39;s protective design.<\/p>\n<figure data-role=\"technical\">\n<div class=\"diagram-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering diagram\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/e260c1ffc0b6b14b-heater-command-current-feedback-check-engineering.svg\" width=\"1200\" height=\"675\" alt=\"TX4-S Heater Checks: Separate the Command from Delivered Current  title=\" data-image-role=\"technical\" tx4-s heater checks: separate the command from delivered current title =\"\"><\/div><figcaption>Conceptual Engineering Diagram. External observation concept; no built-in TX4 current-monitoring function is claimed. All numerical inputs are hypothetical unless identified as mathematical relationships; no measured product performance is presented. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/e260c1ffc0b6b14b-heater-command-current-feedback-check-engineering.svg\">View source image<\/a><\/figcaption><\/figure>\n<div class=\"table-scroll\" tabindex=\"0\" role=\"region\" aria-label=\"Scrollable engineering table\">\n<table>\n<thead>\n<tr>\n<th>Observed command<\/th>\n<th>Observed branch current<\/th>\n<th>Initial interpretation<\/th>\n<th>Required distinction<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>ON<\/td>\n<td>4.0 A in the example<\/td>\n<td>Current reaches the measured branch<\/td>\n<td>Heating effectiveness and correct load identity<\/td>\n<\/tr>\n<tr>\n<td>ON<\/td>\n<td>Below example 0.2 A threshold<\/td>\n<td>Expected conduction not established<\/td>\n<td>Open heater, missing source, switch path or sensor issue<\/td>\n<\/tr>\n<tr>\n<td>OFF<\/td>\n<td>Below the chosen threshold<\/td>\n<td>No substantial current observed by this method<\/td>\n<td>Isolation and absence of voltage remain separate<\/td>\n<\/tr>\n<tr>\n<td>OFF<\/td>\n<td>Substantial current persists<\/td>\n<td>Uncommanded conduction requires investigation<\/td>\n<td>Switch failure, alternate path or incorrect state measurement<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<h2 id=\"what-external-switching-evidence-is-needed\"><span class=\"ez-toc-section\" id=\"What_external_switching_evidence_is_needed\"><\/span>What external switching evidence is needed?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Identify whether the actual system uses a relay contact, an SSR drive and external SSR, or another documented arrangement. A drive signal and a load-power contact have different ratings and roles. Applying a load directly to an unsuitable signal output is not justified by a generic wiring example.<\/p>\n<p>The <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2023\/11\/TX4.pdf\">official TX4 manual<\/a> provides the starting point for the relevant controller arrangement. Match it to the delivered variant and the switching component&#39;s own documentation. Do not assume all ordering combinations shown in a reference diagram are supplied or supported.<\/p>\n<p><a href=\"https:\/\/www.ia.omron.com\/product\/cautions\/18\/safety_precautions.html\" target=\"_blank\" rel=\"noopener\">OMRON&#39;s SSR precautions<\/a> explain why a conducting failure mode must be considered in a heater system. This external principle does not establish that a WEHO controller includes a particular detection or protective function. The equipment designer must assess the complete arrangement.<\/p>\n<p>Record alternate power sources, shared branches and current-sensor location. A sensor around a common feeder may include more than the heater under investigation. A current transformer or clamp around both outgoing and return conductors can also produce a misleading result, depending on the method. Follow the instrument&#39;s applicable instructions.<\/p>\n<h2 id=\"how-should-timing-be-handled-for-time-proportioned-outputs\"><span class=\"ez-toc-section\" id=\"How_should_timing_be_handled_for_time-proportioned_outputs\"><\/span>How should timing be handled for time-proportioned outputs?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>A time-proportioned command intentionally alternates ON and OFF intervals. A slow meter may average those intervals, while a spot observation may catch only one state. Compare current with the command on an appropriate common time reference rather than treating an average display as continuous conduction.<\/p>\n<p>For a hypothetical DC heating-current waveform over 10 seconds, suppose current is 4.0 A for 3 seconds and zero for 7 seconds. Its average current over that simplified window is 1.2 A. Its RMS current is 4 \u00d7 \u221a0.3 = 2.19 A, approximately. Those quantities answer different questions. For an AC heater, distinguish signed current from its RMS or magnitude envelope rather than applying the DC average directly.<\/p>\n<ol>\n<li>Identify the actual control-output cycle and downstream switching method.<\/li>\n<li>Select measurement equipment with suitable current, voltage and timing capability.<\/li>\n<li>Record command state and branch current over complete relevant intervals.<\/li>\n<li>Separate ordinary OFF-state residual behavior from substantial conduction using a justified method.<\/li>\n<li>Investigate discrepancies under the equipment&#39;s isolation and fault-response procedure.<\/li>\n<\/ol>\n<p>Qualified personnel should establish the setup and control any consequences of simulated states. A zero current observation does not prove electrical isolation or absence of hazardous voltage. Never use an output indicator or a current threshold as the sole basis for accessing a circuit.<\/p>\n<h2 id=\"what-should-a-supplier-receive-before-the-controller-is-replaced\"><span class=\"ez-toc-section\" id=\"What_should_a_supplier_receive_before_the_controller_is_replaced\"><\/span>What should a supplier receive before the controller is replaced?<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Provide the controller variant, output arrangement, switching-device identity and a synchronized command\/current record. Include supply state, load identity and the measurement boundary. This distinguishes a controller request problem from a downstream power-delivery problem without forcing an early component diagnosis.<\/p>\n<p>The <a href=\"https:\/\/www.wehopower.com\/ur\/product\/tx4-series-tx4-s-economic-dual-display-pid-temperature-controller\/\">TX4-S product entry<\/a> helps identify the supplied model. Request applicable documentation if the output configuration is unclear. The article does not promise a built-in current-sensing function, safety-rated shutdown or compatibility with an unspecified SSR.<\/p>\n<p>Keep the actual process response in the record as another channel. Current may flow normally while a loose heater, changed thermal contact or displaced probe causes poor temperature behavior. Electrical delivery and useful heat transfer need different evidence, and a tuning change should not conceal a mechanical or sensor problem.<\/p>\n<p>A current sensor&#39;s threshold and delay should be matched to the intended state distinction. A threshold selected only to avoid nuisance indications can hide a meaningful low-current failure, while one set below ordinary residual behavior can create false alarms. Establish the actual measurement capability and equipment requirement before choosing either value.<\/p>\n<p>The record should also distinguish one failed element from several parallel heaters. Total branch current may remain substantial after one element opens. A simple current-present decision can therefore miss a partial loss of heating capacity unless the monitoring boundary and acceptance rule address it.<\/p>\n<figure data-role=\"product\"><a href=\"https:\/\/www.wehopower.com\/ur\/product\/tx4-series-tx4-s-economic-dual-display-pid-temperature-controller\/\" aria-label=\"View TX4-S product details\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/8a6ae9cd2f20bc9f-tx4-s-heater-product-reference.avif\" width=\"1000\" height=\"1000\" alt=\"TX4-S Heater Checks: Separate the Command from Delivered Current  title=\" data-image-role=\"product\" tx4-s heater checks: separate the command from delivered current title =\"\"><\/a><figcaption>Official TX4-S product photograph. Original markings and source clarity are retained; the image is not a test or configuration record. <a href=\"https:\/\/www.wehopower.com\/wp-content\/uploads\/2026\/11\/4e5ba95d41af0f15-original-tx4-s-official.png\">View source image<\/a><\/figcaption><\/figure>\n<h2 id=\"prepare-a-tx4-s-heating-path-review\"><span class=\"ez-toc-section\" id=\"Prepare_a_TX4-S_heating-path_review\"><\/span>Prepare a TX4-S heating-path review<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<p>Send WEHO the ordered controller details, applicable connection diagram, load and switching information, and the observed state table. State whether the discrepancy concerns the command, electrical delivery or process temperature. This supports a focused technical discussion while leaving protective design and fault handling with the responsible equipment team.<\/p>\n<h2 id=\"frequently-asked-questions\"><span class=\"ez-toc-section\" id=\"Frequently_asked_questions\"><\/span>Frequently asked questions<span class=\"ez-toc-section-end\"><\/span><\/h2>\n<h3 id=\"does-an-on-indicator-prove-that-the-heater-receives-power\"><span class=\"ez-toc-section\" id=\"Does_an_ON_indicator_prove_that_the_heater_receives_power\"><\/span>Does an ON indicator prove that the heater receives power?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. It indicates a control state according to the device&#39;s design. The downstream switching path, supply and heater must be checked with suitable independent evidence.<\/p>\n<h3 id=\"can-current-flowing-with-an-off-command-be-ignored-as-normal-leakage\"><span class=\"ez-toc-section\" id=\"Can_current_flowing_with_an_OFF_command_be_ignored_as_normal_leakage\"><\/span>Can current flowing with an OFF command be ignored as normal leakage?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>Not without a justified assessment. Expected residual behavior and substantial uncommanded conduction must be distinguished using the actual switch, load and measurement specifications. Follow the machine&#39;s fault procedure.<\/p>\n<h3 id=\"does-zero-measured-current-prove-safe-isolation\"><span class=\"ez-toc-section\" id=\"Does_zero_measured_current_prove_safe_isolation\"><\/span>Does zero measured current prove safe isolation?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>No. Current observation is not an absence-of-voltage test or an isolation procedure. Electrical access requires the equipment&#39;s established energy-control and verification method.<\/p>\n<h3 id=\"should-pid-tuning-be-changed-when-commanded-heat-produces-no-current\"><span class=\"ez-toc-section\" id=\"Should_PID_tuning_be_changed_when_commanded_heat_produces_no_current\"><\/span>Should PID tuning be changed when commanded heat produces no current?<span class=\"ez-toc-section-end\"><\/span><\/h3>\n<p>First establish the electrical delivery path and measurement validity. Tuning cannot repair an open heater or missing power source, and changing settings may obscure the original diagnostic evidence.<\/p>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>Check a TX4-S heating system using separate command and heater-current evidence. Build a fault-state table before changing controller settings.<\/p>","protected":false},"author":2,"featured_media":23049,"parent":0,"menu_order":10,"comment_status":"","ping_status":"","template":"","format":"standard","meta":{"_acf_changed":false,"_joinchat":[],"footnotes":""},"news_category":[284],"class_list":["post-23063","news","type-news","status-publish","format-standard","has-post-thumbnail","hentry","news_category-product-articles","entry"],"acf":[],"post_mailing_queue_ids":[],"_links":{"self":[{"href":"https:\/\/www.wehopower.com\/ur\/wp-json\/wp\/v2\/news\/23063","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.wehopower.com\/ur\/wp-json\/wp\/v2\/news"}],"about":[{"href":"https:\/\/www.wehopower.com\/ur\/wp-json\/wp\/v2\/types\/news"}],"author":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/ur\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/ur\/wp-json\/wp\/v2\/comments?post=23063"}],"version-history":[{"count":0,"href":"https:\/\/www.wehopower.com\/ur\/wp-json\/wp\/v2\/news\/23063\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.wehopower.com\/ur\/wp-json\/wp\/v2\/media\/23049"}],"wp:attachment":[{"href":"https:\/\/www.wehopower.com\/ur\/wp-json\/wp\/v2\/media?parent=23063"}],"wp:term":[{"taxonomy":"news_category","embeddable":true,"href":"https:\/\/www.wehopower.com\/ur\/wp-json\/wp\/v2\/news_category?post=23063"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}