A three-wire NPN sensor can be ON while its output terminal is near the negative return. Check the voltage delivered across the matched receiver input, including sensor residual voltage and wiring loss, rather than assuming that an active sensor supplies a 24 V high signal.
Key engineering takeaways
- Identify the receiver's current path and reference terminals.
- Include the sensor's documented ON-state residual voltage.
- Compare receiver voltage with its actual ON requirement.
- Keep electrical margin separate from NO/NC action and optical detection.

Which voltage does the receiving input actually use?
An OEM controls engineer needs to decide whether an active sensor can reliably energize its receiving input. That decision requires the input circuit and its documented conditions. A front indicator, an ON label or a voltage measured against an unrelated reference does not establish the voltage across the receiver element.
El C3Z-D100N output reference identifies the NPN version in the product table. The same page lists a residual-voltage row of ≤2 V. Obtain the applicable full-model instructions and the conditions behind that row before treating it as a fully characterized limit for every load and temperature.
An NPN output typically completes a path toward the negative return. In a compatible sourcing input arrangement, the receiving load sits between the positive supply and the sensor output. Most of the supply voltage can then appear across that load even while the sensor's output terminal is relatively low against the negative return.
Separate output type from logical meaning
OMRON's NPN/PNP explanation distinguishes where the load connects in the two arrangements. This is general interface guidance, not permission to copy another manufacturer's terminal numbers or assume the same internal circuit in every receiver. Read the actual sensor and receiving-module drawings together.
For a PNP arrangement, the output sources current toward a load referenced to the negative side. That comparison can clarify terminology, but it does not turn a C3Z-D100N into a PNP device. A program inversion or NO/NC action change cannot correct an electrically mismatched sourcing/sinking interface.
El C3Z-D100N state-table article addresses target condition, action mode and program interpretation. This article addresses the ON-current loop's available voltage. An interface can have correct logical meaning but insufficient electrical margin, or sufficient voltage but incorrect machine interpretation.
What does residual voltage subtract from the loop?
Residual voltage is the voltage remaining across the conducting output rather than an ideal zero-volt switch. Its relevant value depends on the actual product specification and conditions. Do not substitute a typical small-current observation for a stated worst-case value at the load current and environment being assessed.
For the simplified compatible NPN loop considered here, define Vreceiver = Vsupply − Voutput,on − Vwiring. Vsupply is the voltage across the complete supply boundary used by the loop. Vwiring includes the defined outgoing and return-path losses, without counting the same segment again under another name.
OMRON's receiver-input FAQ illustrates why residual-voltage requirements depend on the receiving device. Its counter example uses a different input arrangement and its own numerical conditions. Those numbers must not be copied as C3Z-D100N specifications or as universal PLC thresholds.
The receiver's ON requirement can include current as well as voltage. If input current varies with applied voltage, evaluate the documented input behavior consistently with the sensor's load-current limit. A convenient constant-resistance approximation is insufficient when the receiver documentation specifies a different characteristic.
A hypothetical receiver with an 18 V ON requirement
Assume an OEM worksheet uses a receiver requiring at least 18.0 V across its identified input element. Assume the relevant ON-state input current is 8 mA, the applicable sensor output-drop allowance is 2.0 V, and the characterized total wiring drop is 0.10 V. The receiver threshold, current and wiring value are invented example inputs, not a recommended PLC specification.
The 2.0 V allowance uses the magnitude of the published C3Z-D100 residual-voltage row for a preliminary arithmetic screen. That row does not provide all the conditions needed to approve this interface. The actual output-drop coverage, input-current behavior and operating corners still require applicable documentation or qualified verification.
At an assumed 21.6 V supply boundary, Vreceiver = 21.6 − 2.0 − 0.10 = 19.5 V. The illustrative ON margin is 19.5 − 18.0 = +1.5 V. A nominal “24 V system” description alone would hide how this margin changes at another actual supply condition.
| Assumed supply boundary | Output + wiring allowance | Calculated receiver voltage | Margin above assumed 18 V |
|---|---|---|---|
| 24.0 V | 2.0 + 0.10 V | 21.9 V | +3.9 V |
| 21.6 V | 2.0 + 0.10 V | 19.5 V | +1.5 V |
| 20.0 V | 2.0 + 0.10 V | 17.9 V | −0.1 V |
Swipe horizontally on a small screen, or open the full-size diagram.
The last row does not meet the invented receiver requirement under the stated allowances. It does not prove that the sensor has stopped detecting, that the receiver will necessarily turn OFF at exactly that instant, or that a different input would behave identically. Threshold bands, hysteresis and operating instructions belong to the actual receiving module.
If an independently characterized series path carried only the assumed 8 mA, a 0.10 V resistive loss would correspond to 0.10/0.008 = 12.5 Ω. This calculation is a consistency check, not a cable-length recommendation. A real shared return can include other currents and reference shifts, so identify the physical paths rather than assigning all observed loss to one cable conductor.
Do not cure one missing margin by creating another
Increasing supply voltage can affect every device sharing that boundary. Check their maximum operating limits, startup conditions and applicable settings before proposing a change. A receiver's minimum ON requirement does not authorize exceeding the sensor or another load's permitted voltage.
Adding an interface component also creates a new circuit requiring its own ratings and input/output checks. Do not add a pull-up, relay or converter solely because an unfamiliar input remains inactive. First establish whether the sensor, receiver common and actual signal path are the intended combination.
OMRON's photomicrosensor precautions explicitly relates residual voltage to load current in a particular example. Its component values and wiring recommendations apply to the specified products, not this WEHO application. The transferable lesson is to retain the stated current condition with the output-voltage information.
| Question | Evidence required | Decision supported | Insufficient shortcut |
|---|---|---|---|
| Is the interface type matched? | Sensor output and receiver input/common drawings | A valid current-loop architecture | Matching supply-voltage labels |
| Is ON margin sufficient? | Output drop, wiring loss and actual receiver conditions | Calculated and verified input energization | Sensor indicator ON |
| Is output loading acceptable? | Receiver current characteristic and sensor limits | Supported output duty | A voltage measurement without load context |
| Does the machine interpret it correctly? | Qualified target, action mode and program state | Correct process meaning | Electrical margin alone |
Verify the ON loop under the required conditions
- Identify both interfaces. Record the full sensor model, receiver module, common arrangement and applicable drawings. Verify the actual current path before selecting measurement references or changing wiring.
- Collect conditional limits. Record output-drop conditions, receiver voltage/current requirements and supply range. Verify unresolved conditions with the responsible supplier; keep an unspecified test condition visible in the preliminary worksheet.
- Calculate the complete loop. Record each voltage allowance, current assumption and physical segment. Verify the arithmetic and avoid double-counting a shared return or treating a nominal supply value as its minimum.
- Check the assembled input. Qualified personnel should follow the equipment's commissioning and energy-control procedures. Record voltage across the identified receiver boundary, relevant current and actual input state under the defined operating conditions.
- Release a bounded result. Record supported corners, remaining gaps and the required machine interpretation. Accept the interface only when electrical conditions and intended action are both verified; a favorable calculation with missing product conditions remains preliminary.

Prepare a C3Z-D100N interface review
Send WEHO the C3Z-D100N sensor identity, receiver circuit, supply conditions and input-current information. Include the ON-state budget and ask which residual-voltage conditions apply to the supplied revision. Keep actual optical-target qualification and NO/NC configuration identified as separate checks.
Before changing a component, name the receiver boundary, obtain conditional limits and complete the ON-loop calculation. Those actions turn “the sensor is ON but the input is unreliable” into an evidence-based interface question without inventing a receiver threshold or assuming that NPN means a sourcing high output.
Engineering FAQ
Does NPN ON mean the output terminal rises toward +24 V?
No. A typical NPN output conducts toward the negative return, while a compatible receiving load is energized from the positive side through that path. Identify the actual receiver circuit and voltage boundary rather than assigning a universal high-level meaning to ON.
Does the sensor's 10–30 V supply row prove receiver compatibility?
No. The sensor supply range and the receiver's ON requirements describe different conditions. Residual voltage, wiring loss, receiver current and the correct interface arrangement must also be checked for the actual assembly.
Is the 18 V example a C3Z-D100N switching threshold?
No. It is an invented requirement for the hypothetical receiving input. The sensor's output characteristic and the receiver's voltage/current conditions must come from their own applicable documents rather than from that explanatory number.
Can NO/NC inversion repair insufficient ON-state voltage?
No. Action mode changes the relationship between detection and output state, not the available voltage in the conducting loop. Correct the documented electrical interface and separately verify the machine's intended logical interpretation.