- A low-end dimming test should approach the same command from both directions.
- Define command history, settling time and the measured electrical or optical quantity before comparing results.
- Express direction differences against a declared reference; a small full-scale difference can be large near minimum output.
- Confirm the exact driver's dimming interface and ordered suffix before applying this method.

Ask whether the same command produces the same result
A dimming curve captured in only one direction cannot establish whether a lighting system returns to the same low output after a fade. The purchasing question is whether the complete control chain meets the project's repeatability and transition requirements. A minimum-output percentage alone does not settle that decision.
IL WEHO HLG-150 product page asks buyers to confirm dimming requirements before ordering. Treat the pictured HLG-150-24 as a product reference, not proof of a dimming interface or supported suffix. Apply a command sweep only after the supplied driver and controller documents establish the intended control function.
A fixture may use a documented dimming input or an external load-side controller with a compatible power source. Those are different assemblies and must remain different test records. Do not add an imaginary control lead to a fixed-output product because the article discusses dimming.
Separate command direction from command accuracy
The command shown on a user interface may differ from the signal reaching the receiver. Record the actual receiver-side signal, whether that quantity is a voltage, duty cycle or digital value. Comparing two display percentages without verifying the interface can attribute a controller error to the driver.
Texas Instruments' Simple Backlight Driver Dimming Performance describes a particular IC response that depends on the previous direction of command change. That example demonstrates why trajectory can matter. Its device-specific resolution, minimum current and hysteresis are not HLG-150 specifications.
Direction dependence may originate in the controller, conversion algorithm, driver or lighting assembly. It can also be confused with a test that changes other conditions between the upward and downward runs. Preserve the same load, wiring, measurement method and operating conditions before assigning a cause.
Lutron's 0–10 V Control Topology application note explains that a nominal control interface does not guarantee the desired dimming performance. Complete the interface compatibility review first. The separate WEHO dimming compatibility guide addresses that prerequisite; this article adds a paired direction-history comparison.

Calculate a low-end direction difference
Use a hypothetical lighting-control example with a documented dimming assembly and a 2.000 A full-output reference current. The reference is an assumed measurement baseline for the example, not a WEHO rating. Assume identical load and instrument conditions and a fixed sampling window at each command point.
Suppose the 2.0% command produces 18 mA when approached from below and 24 mA when approached from above. Define the direction difference as ΔI = |I_down − I_up|. The result is |24 − 18| = 6 mA.
Relative to the declared full-output reference, the difference is 6 mA ÷ 2,000 mA × 100% = 0.30%. Relative to the pair mean of (18 + 24) ÷ 2 = 21 mA, it is 6 ÷ 21 × 100% = 28.6%. Both calculations describe the same pair using different denominators.
State the denominator every time a percentage is reported. A purchasing requirement such as “difference below one percent” is ambiguous until it identifies full scale, command, local reading or another reference. Keep the absolute difference alongside the percentage so that the decision remains interpretable.
Swipe horizontally on a small screen, or open the full-size diagram.
| Hypothetical command | Upward current | Downward current | Absolute difference |
|---|---|---|---|
| 2.0% | 18 mA | 24 mA | 6 mA: 0.30% of reference |
| 3.0% | 36 mA | 40 mA | 4 mA: 0.20% of reference |
| 5.0% | 90 mA | 92 mA | 2 mA: 0.10% of reference |
If the hypothetical project permits at most 0.20% of the 2.000 A reference, its direction-difference limit is 4 mA. The 2.0% command pair fails that example criterion; the other two pairs meet it. A production decision would also need measurement uncertainty and every other applicable output requirement, rather than accepting a result exactly at the limit without an agreed decision rule.
These numbers evaluate electrical current only. They do not establish equivalent differences in illuminance, perceived brightness, colour or flicker. If the project requirement concerns optical output, define and measure that optical quantity separately while preserving the same paired command histories.
Decide what the trajectory test must preserve
An upward run needs a documented starting state and monotonic command sequence. A downward run needs its own starting state, normally above the points being compared. Visiting a point after an unrelated command excursion creates a different history and should not be quietly merged with the first sequence.
Record the actual command step, hold interval and sampling window. A response measured during a transition answers a different question from the result after the specified hold. Keep the timing rule identical for corresponding points and choose it from the intended operating task or documented response conditions.
TI's Analog PWM Dimming in White-LED Drivers distinguishes direct PWM from PWM-to-analog approaches and explains how hysteresis can filter command jitter in particular implementations. The signal label alone therefore cannot identify the internal response. Request the actual assembly's documentation instead of assuming that every PWM input switches LED current in the same way.
Record whether an off command, a power cycle or a control reset occurs between trajectories. Those events can establish a different internal starting state, so preserve them in the sequence rather than treating every return to the same display value as equivalent.
A full sequence should also distinguish repeatability within one unit from variation between units. Repeat both trajectories on the same assembly before comparing replacement units or production lots. Otherwise, a change in unit can be mistaken for a direction effect.
Create a paired-sweep acceptance record
- Identify the control path. Record controller, driver, output version, load and applicable interface documents. Accept the proposed test only when the actual command connection and permitted operating range are established.
- Declare the output quantity. Name the measured current, voltage or optical quantity and its reference. Record the instrument and settings; confirm that resolution and uncertainty can support the proposed low-end limit.
- Fix the trajectories. Define starting states, points, direction, hold intervals and sampling windows. Retain the receiver-side commands so that the two paths can be reproduced rather than approximated by a manual slider.
- Compare corresponding points. Calculate the absolute paired difference and the explicitly normalized value. Judge each point against the agreed limit, retaining individual observations rather than only a smoothed curve.
- Investigate and repeat. If a pair fails, separate command delivery, timing and assembly response before changing parts. After a supported adjustment, repeat the affected trajectories and document what changed.
An operator's observation of a visible jump can initiate this investigation, but it is not a quantitative acceptance result. Preserve the command location and operating state where the effect appears. That evidence lets the control and driver suppliers investigate the same event.
Send WEHO a complete dimming requirement
For an HLG-150 application inquiry, provide the full ordered label, intended controller, LED load and required low-end behavior. Ask which documented configuration, if any, supports the requested interface. Include paired-sweep limits and their reference quantities before approving a candidate assembly.
Frequently asked questions
Does a low minimum-dimming percentage prove repeatability?
No. Minimum output and repeatability describe different requirements. Compare the same command after defined upward and downward histories, using a declared measured quantity and acceptance limit.
Does PWM control always mean the LEDs receive matching pulses?
No. A PWM command can be processed in different ways inside the controller or driver. Obtain the actual interface and output description before choosing the measurement method or interpreting low-end behavior.
Should direction difference be a percentage of full output?
Only if that is the agreed reference. Report the absolute difference and identify the denominator, because full-scale and local-output percentages can differ substantially near the bottom of the range.
Can this procedure establish that HLG-150-24 is dimmable?
No. A test plan cannot add an undocumented function to a product. Confirm the exact supplied configuration and supported control interface before applying a dimming qualification procedure.