Budget the fan drawers together
If 6 fan drawers each draw 2.4 A, their running load is 14.4 A. The S-320-12 lists 26.6 A at 12 V DC. Use start-up data for the fitted drawer population and include any management electronics. Check peak demand and available output at the installed temperature.