| Modelo | MDR-100-12 | MDR-100-15 | MDR-100-24 | MDR-100-48 | |
| Producción | Voltaje CC | 12V | 15V | 24V | 48V |
| Corriente nominal | 7.5A | 6.7A | El 4A | 2a | |
| Rango actual | 0 ~ 7.5A | 0 ~6.7A | 0 -4A | 0 y 2a | |
| Potencia nominal | 100W | 100W | 100W | 100W | |
| Ondulación y ruido (max.) | 80mVp-p | 120mVp-p | 150mVp-p | 200mVp-p | |
| voltage ADJ Range | 12 -13.2V | 15-16.5V | 24 – 26.4V | 48 ~ 56V | |
| Tolerancia de voltaje | ± 2.0% | ±1.0% | ±1.0% | ±1.0% | |
| Regulación de línea | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
| Regulación de carga | ±1.5% | ±1.0% | ±1.0% | ±1.0% | |
| Setup, Rise Time Note.5 | 500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load | ||||
| Hold Up Time (Typ.) | 50 ms. y 230 VAC 20ms/115VAC at full load | ||||
| Aporte | Rango de voltaje | 85 y 264 VAC 120 a 370 VDC | |||
| Rango de frecuencia | 47 y 63 Hz | ||||
| Eficiencia (tipo) | 78% | 86% | 88% | 87% | |
| AC Current(Typ.) | 1.8A/115VAC 1A/230VAC | ||||
| Inrush Current (Typ.) | Cold start: 30A/115VAC, 60A/230VAC | ||||
| Corriente de fuga | <1mA/240VCA | ||||
| Protección | Sobrecarga | 105% – 150% rated output power | |||
| Tipo de protección: Limitación de corriente constante, se recupera automáticamente después de eliminar la condición de falla | |||||
| Overvoltage | 6.25-7.25V | 15.6 – 18V | 31.2-36V | 57.6 – 64.8V | |
| Tipo de protección: Apague el voltaje de salida, vuelva a encenderlo para recuperarlo | |||||
| Función | DC Signal | Relay contact rating (max.): 30V/1A resistive | |||
| Ambiente | Humedad de trabajo | 20% ~ 90%RH sin condensación | |||
| Temperatura de almacenamiento, humedad | -40°C ~ +85°C, 10% ~ 95%RH | ||||
| Coeficiente de Temp | ±0.03%/°C (0 – 50°C) | ||||
| Vibración | Component: 10 – 500Hz, 2G 10min./1 cycle, the period for 60min. each along X, Y, and Z axes; Mounting: Compliance to IEC60068-2-6 | ||||
| Safety & EMC | Estándares de seguridad | UL508, UL60950-1, TUV EN60950-1 approved | |||
| Tensión soportada | l/P-0/P: 3KVAC l/P-FG: 2KVAC 0/P-FG: 0.5KVAC | ||||
| Resistencia de aislamiento | l/P-O/P, l/P-FG, 0/P-FG:>100M Ohms/500VDC/25°C/70% RH | ||||
| EMC Emission | Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3 | ||||
| EMC Immunity | Compliance to EN6100(M-2,3,4,5,6,8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A | ||||
| Otros | El MTBF | 299.2K hrs min. MIL-HDBK-217F (25°C) | |||
| Dimensión | 50*90*100mm (W*H*D) | ||||
| Embalaje | 0.42Kg; 30pcs/20Kg/0.82CUFT | ||||
| Nota | 1. Todos los parámetros NO mencionados especialmente se miden a una entrada de 230 VCA, carga nominal y 25 °C de temperatura ambiente. | ||||
| 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1 uf & 47uf parallel capacitor. | |||||
| 3. Tolerancia: incluye tolerancia de configuración, regulación de línea y regulación de carga. | |||||
| 4. The power supply is considered a component that will be installed into the final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies. | |||||
| 5. The length of set-up time is measured at the first cold start. Turning ON/OFF the power supply may lead to an increase in the set-up time. | |||||
Temperature derating
Permissible load versus ambient temperature for MDR-100.
Swipe the curve horizontally to inspect all labels.