| Modelo | MDR-100-12 | MDR-100-15 | MDR-100-24 | MDR-100-48 | |
| Producción | Voltaje CC | 12V | 15V | 24V | 48V |
| Corriente nominal | 7.5A | 6.7A | 4A | 2a | |
| Rango actual | 0 ~ 7.5A | 0 ~6.7A | 0 -4A | 0-2A | |
| Potencia nominal | 100W | 100W | 100W | 100W | |
| Ripple & Noise (max.) | 80mVp-p | 120mVp-p | 150mVp-p | 200mVp-p | |
| Volage ADJ Range | 12 -13.2V | 15-16.5V | 24 – 26.4V | 48 ~ 56V | |
| Tolerancia de voltaje | ±2.0% | ±1.0% | ±1.0% | ±1.0% | |
| Regulación de línea | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
| Regulación de carga | ±1.5% | ±1.0% | ±1.0% | ±1.0% | |
| Setup, Rise Time Note.5 | 500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load | ||||
| Hold Up Time (Typ.) | 50ms/230VAC 20ms/115VAC at full load | ||||
| Aporte | Rango de voltaje | 85~264VAC 120~370VDC | |||
| Rango de frecuencia | 47 ~ 63Hz | ||||
| Efficiency (Typ.) | 78% | 86% | 88% | 87% | |
| AC Current(Typ.) | 1.8A/115VAC 1A/230VAC | ||||
| Inrush Current (Typ.) | Cold start: 30A/115VAC, 60A/230VAC | ||||
| Corriente de fuga | <1mA/240VCA | ||||
| Protección | Overload | 105% – 150% rated output power | |||
| Protection type: Constant current limiting, recovers automatically after fault condition is removed | |||||
| Overvoltage | 6.25-7.25V | 15.6 – 18V | 31.2-36V | 57.6 – 64.8V | |
| Tipo de protección: Apague el voltaje de salida, vuelva a encenderlo para recuperarlo | |||||
| Function | DC Signal | Relay contact rating (max.): 30V/1A resistive | |||
| Ambiente | Working Humidity | 20% ~ 90%RH non-condensing | |||
| Temperatura de almacenamiento, humedad | -40°C ~ +85°C, 10% ~ 95%RH | ||||
| Temp Coefficient | ±0.03%/°C (0 – 50°C) | ||||
| Vibración | Component: 10 – 500Hz, 2G 10min./1 cycle, the period for 60min. each along X, Y, and Z axes; Mounting: Compliance to IEC60068-2-6 | ||||
| Safety & EMC | Estándares de seguridad | UL508, UL60950-1, TUV EN60950-1 approved | |||
| Tensión soportada | l/P-0/P: 3KVAC l/P-FG: 2KVAC 0/P-FG: 0.5KVAC | ||||
| Resistencia de aislamiento | l/P-O/P, l/P-FG, 0/P-FG:>100M Ohms/500VDC/25°C/70% RH | ||||
| EMC Emission | Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3 | ||||
| EMC Immunity | Compliance to EN6100(M-2,3,4,5,6,8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A | ||||
| Otros | MTBF | 299.2K hrs min. MIL-HDBK-217F (25°C) | |||
| Dimensión | 50*90*100mm (W*H*D) | ||||
| Embalaje | 0.42Kg; 30pcs/20Kg/0.82CUFT | ||||
| Nota | 1. Todos los parámetros NO mencionados especialmente se miden a una entrada de 230 VCA, carga nominal y 25 °C de temperatura ambiente. | ||||
| 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1 uf & 47uf parallel capacitor. | |||||
| 3. Tolerancia: incluye tolerancia de configuración, regulación de línea y regulación de carga. | |||||
| 4. The power supply is considered a component that will be installed into the final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies. | |||||
| 5. The length of set-up time is measured at the first cold start. Turning ON/OFF the power supply may lead to an increase in the set-up time. | |||||
Plastic shell 5V/12V/24V/48V dc dinrail power supply 100w
MDR-100 is a slim line DIN rail Class I switching power supply.
Designed with a fully isolated plastic case to prevent user contact and the risk of shock.Featuring up to 88% efficiency this series can be cooled using only free air convection up to 60°C which significantly increases the reliability and lifetime of the power supply.Other standard features include its low no-load power consumption, to save energy, short circuit, overload, and over voltage protections, and DC OK relay contact with LED indicator for monitoring the PSU status.If you have any questions, please do not hesitate to contact us at Correo electrónico: [email protected]
- Descripción
Quick Deliver after putting an order, within 3-7 works days for common models
Todos los productos pasan por procedimientos de prueba estandarizados durante la producción.
Nosotros mismos fabricamos transformadores e inductores de potencia con cobres puros,
Global wide input volatge range 100V to 264V AC
Este producto es pequeño y fácil de instalar, lo que ahorra espacio y es rentable.
Fixed switching frequency at 70KHz
El producto se puede enfriar por convección de aire natural.
Save space and cost
¿Cuáles son los mejores productos de fuentes de alimentación para su empresa?
Impulsa tu negocio con productos de suministro de energía de calidad WEHO.
Pregúntale a un experto