| Modelo | DR-30-5 | DR-30-12 | DR-30-15 | DR-30-24 | |
| Producción | Voltaje CC | 5V | 12V | 15V | 24V |
| Corriente nominal | 3A | 2a | 2a | 1.5A | |
| Rango actual | 0 ~ 3A | 0 y 2a | 0 ~2A | 0 ~ 1.5A | |
| Potencia nominal | 15W | 24W | Los 30W | 36W | |
| Ondulación y ruido (max.) | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p | |
| Voltaje: Rango | 4.75 por 5.5V | 10.8 Desde 13.2V | 13.5 Desde 16.5V | 21.6 por 26.4V | |
| Tolerancia de voltaje | ± 2.0% | ±1.0% | ±1.0% | ±1.0% | |
| Regulación de línea | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
| Regulación de carga | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
| Tiempo, tiempo de subida | 100ms, 30ms/230VAC 100ms, 30ms/115VAC at full load | ||||
| Tiempo de espera (Typ.) | 100ms/230VAC 30ms/115VAC at full load | ||||
| Aporte | Rango de voltaje | 85 ~ 264 VAC 120 ~ 370 VDC | |||
| Rango de frecuencia | 47 y 63 Hz | ||||
| Eficiencia (tipo) | 74% | 81% | 82% | 83% | |
| AC Actuales | 0.88A/115VAC 0.48A/230VAC | ||||
| Corriente de Inrush (max.) | Cold Start: 15A/115VAC 30A/230VCA | ||||
| Protección | Sobre-carga | 105 ~ 160% rated output power | |||
| Tipo de protección: Limitación de corriente constante, se recupera automáticamente después de eliminar la condición de falla | |||||
| Sobre voltaje | 5.75 por 6.75V | 13.8 Desde 16.2V | 17,25 y 20,25 V | 27.6 por 32.4V | |
| Protection type: Shut down o/p voltage,re-power on to recover | |||||
| Ambiente | Trabajo Temp | -20ºC ~ +60ºC (Refer to output load derating curve) | |||
| Humedad de trabajo | 20% ~ 90% RH non-condensing | ||||
| Temperatura de almacenamiento. Humedad | -20ºC ~ +85ºC, 10% ~ 95%RH | ||||
| Coeficiente de Temp | ± 0.03%/º C (0 ~ 50 º C) | ||||
| Vibración | 10 ~ 500Hz, 2G 10min./1 ciclo, 60min. cada uno a lo largo de los ejes X, Y y Z | ||||
| Safety & EMC | Estándares de seguridad | Design refer to UL60950-1, TUV EN60950-1,EN50178 | |||
| Tensión soportada | I/P-O/P: 3KVAC I/P-FG: 1,5 KVAC O/P-FG: 0,5 KVAC | ||||
| Resistencia de aislamiento | I/P-O/P, I/P-FG, O/P-FG: 100M ohmios/500VDC | ||||
| EMI Conduction & Radiation | Cumplimiento de la norma EN55022 (CISPR22) Clase B | ||||
| Armonía actual | Cumplimiento de la norma EN61000 - 3 - 2,-3 | ||||
| EMS Immunity | Cumplimiento de las normas EN61000 - 4 - 2, 3, 4, 5; ENV50204, EN55024, Nivel de la industria ligera, criterio A | ||||
| Otros | El MTBF | 441.5K hrs min. MIL-HDBK-217F (25ºC) | |||
| Dimensión | 78*93*56mm (L*W*H) | ||||
| Embalaje | 0.27Kg; 45pcs/12.2Kg/1.02CUFT | ||||
Dinrail plastic model supply din rail power supply 30W
WeHo’s DR-30 series is a single output Din rail type power supply that can be installed on TS-35/7.5 or 15 DIN rails.
Adopting the full range 86-264VAC input, the entire series provides an output voltage line of 5V,12V,15V,24V,36V and 48V DR-30 is a reliable switching power supply with high-quality material, durability, and safety in use.DR-30 has a little higher price to perform power supply solutions for various industrial applications.Si tiene alguna pregunta, no dude en contactarnos en Correo electrónico: [email protected]
- Descripción
El rango de temperatura de funcionamiento del producto es-10’C ~+50’C.
Our partners can cooperate with us in OEM or ODM.
El producto se puede montar en riel DIN TS-35/7.5 o 15.
Tipo DIN RAIL, fácil de instalar.
El producto está equipado con indicadores LED que indican cuando está encendido, cargando o funcionando normalmente.
Este producto está cubierto por una garantía de 3 años.
Nuestros productos cuentan con la certificación CE ROHS para garantizar la calidad.
El producto ha completado la prueba de envejecimiento a carga completa 100%.