HDR-100 Industrial DIN-Rail Single-Output Power Supply

WEHO’s HDR-100 is a compact, single-output DIN-rail power-supply family for panel-mounted control, sensing and communications electronics. Separate 12V, 15V, 24V, 48V versions support voltage-specific selection, while the 70×90×54.5mm body gives a defined mechanical envelope. Match the selected model’s current rating and actual installation conditions before ordering.

Si vous avez des questions, n'hésitez pas à nous contacter au E-mail: [email protected]

 

WEHO's HDR-100 is a compact, single-output DIN-rail power-supply family for panel-mounted control, sensing and communications electronics. Separate 12V, 15V, 24V, 48V versions support voltage-specific selection, while the 70×90×54.5mm body gives a defined mechanical envelope. Match the selected model's current rating and actual installation conditions before ordering.

Modèle HDR-100-12 HDR-100-15 HDR-100-24 HDR-100-48
DC output voltage, current 12V 0~7.5A 15V 0~6.5A 24V 0~4.2A 48V 0~2.1A
Vague et bruit 120 mVcrête à crête 120 mVcrête à crête 150 mVcrête à crête 240 mVcrête à crête
Stabilité du fil d'entrée ±1% ±1% ±1% ±1%
Stabilité de la charge ±1% ±1% ±1% ±1%
Efficacité 86% 86% 88% 88%
Plage réglable pour la tension CC ±10% ±10% ±10% ±10%
Plage de tension d'entrée 85~264VAC/120~370VDC; 47~63Hz
Courant d'impact Cold start current: 35A/115VAC; 70A/230VAC
Protection contre les surcharges 105%~150% cut off the output, automatic recovery
Protection contre les surtensions 115%~140% rated output power. Protection type: Hiccup mode, recovers automatically after fault condition is removed
Configuration, montée, temps de maintien 1500ms, 80ms/230VAC; 1500ms, 80ms/115VAC (at full load)
Tension de tenue I/P-O/P: 1.5kV; I/P-FG: 1.5kV; O/P-FG: 0.5kV; 1 minute
Résistance d'isolement I/P-O/P, I/P-FG, O/P-FG: 100MΩ / 500VDC / 25℃ / 70%RH
Température de fonctionnement -20℃~+70℃
Dimension 70×90×54.5mm
Poids 0,27 kg

Why choose HDR-100?

Defined mechanical envelope

The stated body dimensions are 70×90×54.5mm. Use these dimensions to allocate panel space, then check the complete drawing, terminal access and nearby equipment.

Distinct single-output versions

The listed versions are HDR-100-12, HDR-100-15, HDR-100-24, HDR-100-48. Each is a single-output model, not a simultaneous multi-voltage supply. Match the selected version to the equipment input.

Documented input coverage

The specified input ranges are 85–264VAC and 120–370VDC, with an AC frequency range of 47–63Hz. Confirm the actual source, wiring requirements and supplied revision.

Defined overload recovery

Overload protection is listed at 105%~150% with output cut-off and automatic recovery. Coordinate the supply and downstream load so a fault response is not treated as normal continuous operation.

Caractéristique Alimentation industrielle à sortie unique sur rail DIN HDR-100

Model-specific output information: HDR-100-12: 12V 0~7.5A; HDR-100-15: 15V 0~6.5A; HDR-100-24: 24V 0~4.2A; HDR-100-48: 48V 0~2.1A. Keep each current range with its stated model; the family designation does not establish one continuous-power rating for every output option.

Regulation and adjustment: Line regulation and load regulation are each listed as ±1%. The DC voltage adjustment range is ±10%; confirm the connected electronics input limits before adjusting the setting.

Noise and efficiency data for selection: Ripple/noise: HDR-100-12: 120mVp-p; HDR-100-15: 120mVp-p; HDR-100-24: 150mVp-p; HDR-100-48: 240mVp-p. Efficiency: HDR-100-12: 86%; HDR-100-15: 86%; HDR-100-24: 88%; HDR-100-48: 88%. Use the selected model figures in the load noise and power-budget assessment.

Model-specific terminal information: Pin 1: AC/L; pin 2: AC/N; pins 3 and 4: -V; pins 5 and 6: +V. The drawing specifies TS35/7.5 or TS35/15 DIN rails. Follow the complete drawing and the installation electrical-safety requirements.

HDR-100W size

Typical service conditions

Panel space and mechanical fit

Plan around the 70×90×54.5mm body and 0.27kg stated weight. The drawing specifies TS35/7.5 or TS35/15 DIN rails. Allow for wiring and the surrounding equipment; the body dimensions are not a universal clearance specification.

Input and terminal checks

Check the actual supply against 85–264VAC or 120–370VDC and the 47–63Hz AC range. Pin 1: AC/L; pin 2: AC/N; pins 3 and 4: -V; pins 5 and 6: +V. Confirm DC-input wiring for the selected revision rather than assuming AC labels alone define every DC installation.

Temperature and load planning

The working-temperature range is -20°C to +70°C. Assess the real enclosure, airflow and selected output load; the stated temperature range alone does not establish full output at every ambient temperature.

Start-up and fault coordination

Timing information is listed as 1500ms, 80ms/230VAC; 1500ms, 80ms/115VAC (at full load). Cold-start current is 35A/115VAC; 70A/230VAC. Keep these figures with their stated input conditions when coordinating upstream protection and downstream start-up.

Application guidance

These are potential integration roles, not customer-installation claims. Match the selected voltage, steady-state current, start-up demand and environment before selection.

Access-control electronics

Use a voltage-compatible HDR-100 version for reader, controller or interface electronics inside a protected access-control panel. Assess door strikes, motors and pulsed loads separately; a matching nominal voltage alone does not establish suitability.

Process sensing and monitoring

Provide local DC power to compatible sensor interfaces, monitoring modules or indication electronics with the selected HDR-100 voltage. Check steady-state and start-up demand and compare ripple/noise with the measurement-system requirements.

Building-automation interfaces

Supply compatible zone-controller or building-management interface electronics in a protected panel. Check the HDR-100 mechanical envelope, panel temperature and load input limits; the supply alone does not establish outdoor or system-level approval.

Industrial communications equipment

Power compatible gateways, serial-interface modules or local communications electronics that accept the selected HDR-100 DC input. Verify the whole load budget and start-up conditions; this selection does not add PoE, backup or UPS functions.

HDR-100 technical FAQs

Which DC output models are listed for HDR-100?

The listed models are HDR-100-12, HDR-100-15, HDR-100-24, HDR-100-48, with nominal outputs of 12V, 15V, 24V, 48V respectively. Each is a single-output version.

What current ratings are listed for HDR-100?

HDR-100-12: 12V 0~7.5A; HDR-100-15: 15V 0~6.5A; HDR-100-24: 24V 0~4.2A; HDR-100-48: 48V 0~2.1A. Keep each current range with its exact output model and assess the actual load and operating conditions.

What input-voltage and frequency ranges are specified?

The input-voltage ranges are 85–264VAC and 120–370VDC. The AC frequency range is 47–63Hz. Check the selected unit and installation requirements before connection.

What line-regulation and load-regulation figures are listed?

Line regulation and load regulation are each listed as ±1% for every output version in this family.

What DC voltage adjustment range is listed?

The listed DC voltage adjustment range is ±10% for each version. Verify the connected equipment input limits before changing the setting.

What ripple/noise values are listed for HDR-100?

HDR-100-12: 120mVp-p; HDR-100-15: 120mVp-p; HDR-100-24: 150mVp-p; HDR-100-48: 240mVp-p. Confirm any application-specific measurement conditions separately.

What efficiency values are listed for HDR-100?

HDR-100-12: 86%; HDR-100-15: 86%; HDR-100-24: 88%; HDR-100-48: 88%. Use the figure for the selected voltage version.

What cold-start current is specified?

The listed cold-start current is 35A/115VAC; 70A/230VAC. Keep each value tied to its stated AC input when assessing upstream protection.

How is overload recovery specified?

The overload range is 105%~150%, with output cut-off and automatic recovery. Do not treat the protection threshold as a normal continuous operating rating.

What timing information is provided?

The timing row lists 1500ms, 80ms/230VAC; 1500ms, 80ms/115VAC (at full load). A separate third hold-up-time value is not printed in that row.

What working-temperature range and dimensions are stated for HDR-100?

The stated working-temperature range is -20°C to +70°C. Body dimensions are 70×90×54.5mm and weight is 0.27kg. Verify thermal performance with the actual load and enclosure rather than assuming full output at every temperature.

Which terminal assignments are shown for HDR-100?

Pin 1: AC/L; pin 2: AC/N; pins 3 and 4: -V; pins 5 and 6: +V. The drawing specifies TS35/7.5 or TS35/15 DIN rails. Use the complete drawing and applicable installation instructions for final integration.