MDR-60 Series 60W Single Output DIN Rail Switching Power Supply (MDR-60-12 / MDR-60-24)

MDR-60 is a slim line DIN rail Class I switching power supply.
Designed with a fully isolated plastic case to prevent user contact and the risk of shock.Efficiency varies by output model. Operating temperature: -10°C to +50°C; apply the specified derating and installation conditions.Other standard features include its low no-load power consumption, to save energy, short circuit, overload, and over voltage protections, and DC OK relay contact with LED indicator for monitoring the PSU status.If you have any questions, please do not hesitate to contact us at Электронная почта: [email protected]

Photographed sample: MDR-60-12

MDR-60 Single-Output DIN Rail Power Supply

Size the control branch by its voltage and current: the 5 V version and the 48 V version have different load limits.

Select output voltage
Модель
MDR-60-5MDR-60-12MDR-60-24MDR-60-48
DC output
5 V · 0–10 A12 V · 0–5 A24 V · 0–2.5 A48 V · 0–1.25 A
AC input
85–264 VAC
DC input
120–370 VDC
Эффективность
76%84%86%86%
Dimensions (W × H × D)
40 × 90 × 100 mm

Specifications & models

ПараметрMDR-60-5MDR-60-12MDR-60-24MDR-60-48
DC output voltage and current5 V · 0–10 A12 V · 0–5 A24 V · 0–2.5 A48 V · 0–1.25 A
Эффективность76%84%86%86%
Ripple и шум80 mV p-p120 mV p-p150 mV p-p200 mV p-p
Регулирование линии±1%±1%±1%±1%
Регулирование нагрузки±1,5%±1%±1%±1%
DC voltage adjustment±2%±1%±1%±1%
AC input85–264 VAC
DC input120–370 VDC
Dimensions (W × H × D)40 × 90 × 100 mm
Input frequency47–63 Hz
Cold-start inrush30 A at 115 VAC; 60 A at 230 VAC
Защита от перегрузки105–150%; output cuts off and recovers automatically.
Защита от перенапряжения120–140%; output shuts down. Cycle input power to recover.
Setup / rise at full load500 / 30 ms at 230 VAC; 500 / 30 ms at 115 VAC.
Hold-up timeNot specified.
Withstand voltage (1 min)Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV.
Устойчивость к изоляции100 MΩ at 500 VDC: input/output, input/FG and output/FG.
Рабочая температура−10 °C to +50 °C
Mounting railTS35/7.5 or TS35/15
Unit weight0.33 kg
Упаковка45.5 × 32.5 × 23 cm / 60 pcs / 20 kg
DC OK relayClosed: power on / DC normal; open: power off / DC fault. Maximum contact rating: 30 V / 1 A, resistive load.
Output options
МодельВыходТекущийЭффективность
MDR-60-55 V0–10 A76%
MDR-60-1212 V0–5 A84%
MDR-60-2424 V0–2.5 A86%
MDR-60-4848 V0–1.25 A86%
Additional model specifications
MDR-60-5
Ripple и шум80 mV p-p
Регулирование линии±1%
Регулирование нагрузки±1,5%
DC voltage adjustment±2%
MDR-60-12
Ripple и шум120 mV p-p
Регулирование линии±1%
Регулирование нагрузки±1%
DC voltage adjustment±1%
MDR-60-24
Ripple и шум150 mV p-p
Регулирование линии±1%
Регулирование нагрузки±1%
DC voltage adjustment±1%
MDR-60-48
Ripple и шум200 mV p-p
Регулирование линии±1%
Регулирование нагрузки±1%
DC voltage adjustment±1%
Common specifications
AC input85–264 VAC
DC input120–370 VDC
Dimensions (W × H × D)40 × 90 × 100 mm
Input frequency47–63 Hz
Cold-start inrush30 A at 115 VAC; 60 A at 230 VAC
Защита от перегрузки105–150%; output cuts off and recovers automatically.
Защита от перенапряжения120–140%; output shuts down. Cycle input power to recover.
Setup / rise at full load500 / 30 ms at 230 VAC; 500 / 30 ms at 115 VAC.
Hold-up timeNot specified.
Withstand voltage (1 min)Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV.
Устойчивость к изоляции100 MΩ at 500 VDC: input/output, input/FG and output/FG.
Рабочая температура−10 °C to +50 °C
Mounting railTS35/7.5 or TS35/15
Unit weight0.33 kg
Упаковка45.5 × 32.5 × 23 cm / 60 pcs / 20 kg
DC OK relayClosed: power on / DC normal; open: power off / DC fault. Maximum contact rating: 30 V / 1 A, resistive load.

Dimensions & technical notes

Mechanical dimensions

40 × 90 × 100 mm

Front view
MDR-60 front drawing from the manufacturer sheet

Width and height are dimensioned on the front view.

Side view
MDR-60 side drawing from the manufacturer sheet

Depth is dimensioned on the side view; it does not include field wiring.

Rail view
MDR-60 rail drawing from the manufacturer sheet

Rail profile from the model sheet. Mounting types: TS35/7.5 and TS35/15.

Terminal groups: 1 and 2 — AC input; 3 — ground; 4 — DC positive; 5 — DC negative; 6 — DC OK. Follow the markings on the actual unit. Do not infer DC-input polarity from the AC labels.

The DC OK relay reports output status. Its resistive-contact rating is not the supply output rating.

Product overview

For the 5 V version, check voltage drop at the load as well as the printed 0–10 A supply range. Its load regulation is ±1.5%.

The MDR-60 brings a regulated DC branch and a status relay to the rail. Choose the output from the load label, then use its own column for current, ripple and efficiency.

Design features

ОсобенностьWhat to check
Voltage selectionChoose a fixed output suffix before comparing current ranges.
Status monitoringThe DC OK relay reports output status. Its resistive-contact rating is not the supply output rating.
Service accessAllow for the 40 × 90 × 100 mm body plus wiring and access to the voltage trim.
Power budgetFor the 5 V version, check voltage drop at the load as well as the printed 0–10 A supply range. Its load regulation is ±1.5%.

The photo identifies one specimen; electrical data on this page come from the WEHO model sheet.

Installation & applications

Installation checks

Planning illustration: Rail planning, 40 × 90 × 100 mm, TS35/7.5 or TS35/15

Check the rail position

Allow for the 40 × 90 × 100 mm housing on TS35/7.5 or TS35/15 rail. The drawing dimensions exclude the cable bend and working space.

Planning illustration: Specimen identification, MDR-60-12, Match the full ordering suffix

Identify the output before connection

The photograph identifies MDR-60-12. With power isolated, check the full suffix and terminal markings on the unit being installed. A different output choice is a different version.

Planning illustration: DC branch check, MDR-60-24, 0–2.5 A at 24 V

Budget the DC load

For MDR-60-24, the printed current range is 0–2.5 A. Add the branch loads that can start together; do not substitute input inrush for DC capacity.

Planning illustration: Cold-start input, 30 A at 115 VAC, 60 A at 230 VAC

Check cold-start inrush

The input inrush is 30 A at 115 VAC; 60 A at 230 VAC. Check the upstream protection at the corresponding input voltage, separately from output current.

Application examples

A beaker of clear liquid rests on the top plate of a magnetic stirrer at a lab bench.

Stirring liquid in a beaker

A stirrer motor turns a magnet beneath the vessel to move the stir bar. For a 24 V DC motor controller, compare loaded starting current with MDR-60-24 (0–2.5 A). A hotplate heater is not part of that motor branch.

Photo: User:Ruhrfisch · CC BY-SA 3.0
Cropped and converted to WebP.
Original photographMagnetic Stirrer.JPG
Original SHA-256: f737e26a49d3f09220c4784e2e52bdc3f5c9729817d908411adaec28015348e2
Lamps shine through the sides and top of a light tent, with a camera facing its opening.

Lighting a tabletop photo set

At a light tent, separately driven lamps soften shadows around small objects. For lamps with 12 V DC driver inputs, add their full-brightness and startup demand before selecting MDR-60-12 (0–5 A). Do not substitute DC for mains lamps.

Photo: Alison Christine from North Yorkshire, UK · CC BY 2.0
Cropped and converted to WebP.
Original photographLight Tent DIY.jpg
Original SHA-256: 1fcc0ef480da0e82307570f8b7f5b68f517fe268e1cbe1c059bd83c44f4f8b3f
A coin slot, display and push buttons share the front panel of a pavement parking meter.

Taking payment at a parking meter

In a meter fitted with a 12 V DC coin validator, the reader checks each coin before credit is recorded. Compare peak current, including the reject mechanism, with MDR-60-12 (0–5 A); the printer and outdoor enclosure need separate checks.

Photo: Parking Ticket Machine on St Petersgate by Gerald England · CC BY-SA 2.0
Cropped and converted to WebP.
Original photographParking Ticket Machine on St Petersgate - geograph.org.uk - 4727816.jpg
Original SHA-256: 461bd82ac26d0986a19c5337aae8dffe2b66501afc9e38bc1b235a885fcaa04a
Ethernet leads plug into a compact switch beneath a small computer on a work surface.

Connecting a bench network

The switch forwards data between wired devices. For a switch with a specified 12 V DC input, compare its maximum draw with MDR-60-12 (0–5 A). The computer is a separate load; Ethernet ports alone do not imply PoE.

Photo: RAIL P ( RAIL.PHOTOGRAPHY ) · CC0 1.0
Cropped and converted to WebP.
Original photographRaspberry Pi 4 on a network switch.jpg
Original SHA-256: 6b36572d744b44f2fe0104c98b8e3d0eb7f8582d14ba35c28b2e1b74a319b988

These photographs show examples of low-voltage loads, not verified MDR-60 installations or endorsements. Check the actual component’s input specification before selecting a supply.

Часто задаваемые вопросы

Can I switch between the listed output voltages on one unit?

No. Each column identifies a separate single-output version. For example, MDR-60-12 is the 12 V model and MDR-60-24 is the 24 V model. The trim adjustment is not a voltage selector.

Which current range applies to the 24 V model?

MDR-60-24 is specified at 0–2.5 A. Include simultaneous loads and startup demand when sizing the branch.

What are the AC and DC input ranges?

The MDR-60 datasheet specifies 85–264 VAC and 120–370 VDC. The 47–63 Hz frequency range applies to AC.

Which rail and enclosure dimensions should I use?

The housing measures 40 × 90 × 100 mm. The manufacturer drawing lists TS35/7.5 or TS35/15; reserve extra space for cable access.

How is DC OK used?

The DC OK relay reports output status. Its resistive-contact rating is not the supply output rating.

Does the upper temperature limit imply full load?

No. The sheet lists −10 °C to +50 °C as the working range; it does not establish full load at every ambient temperature. Check the actual enclosure conditions.

How does the output recover after a fault?

Overload cuts off output with automatic recovery. Overvoltage shuts down the output; cycle input power after the fault is cleared.

Is a hold-up time specified?

500 / 30 ms at 230 VAC; 500 / 30 ms at 115 VAC. These are full-load setup and rise times. No separate hold-up value is printed.

How large is the input surge?

30 A at 115 VAC; 60 A at 230 VAC are the two cold-start input conditions. Coordinate upstream protection for the actual input and number of supplies starting together.

What is the ripple figure for the 12 V output?

MDR-60-12 lists 120 mV p-p. Check the ripple tolerance at the load as well as the DC current requirement.

What is the insulation test stated on the sheet?

Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV. These one-minute withstand figures are not continuous operating voltages.

What information helps specify a replacement?

Give the full MDR-60 suffix, DC load and startup demand, installed rail and available space. A match in family wattage or cabinet width does not establish interchangeability.

Service conditions

Рабочая температура
−10 °C to +50 °C ambient; this range does not establish continuous full load at its upper limit.
Startup
500 / 30 ms at 230 VAC; 500 / 30 ms at 115 VAC. No hold-up time is specified.
Upstream protection
Use the cold-start inrush figure for the actual input: 30 A at 115 VAC; 60 A at 230 VAC.
Installation space
Check the rail fit and keep terminals and voltage trim accessible; the printed dimensions describe the unit, not the cabinet clearance.

Send Inquiry

Tell us how many units you need and where they will be delivered.

MDR-60-12 WEHO sample, front and right side
Photographed sample: MDR-60-12
Selected model
MDR-60-5MDR-60-12MDR-60-24MDR-60-48
DC output
5 V · 0–10 A12 V · 0–5 A24 V · 0–2.5 A48 V · 0–1.25 A