- Single-phase sinusoidal power can create a repetitive term at twice the AC output frequency.
- A 100 Hz or 120 Hz input-voltage component needs a different record from a single startup dip.
- Internal energy storage and source impedance determine how power pulsation appears at external terminals.
- Measure the actual variant and compare results with applicable limits; do not infer a WHP ripple allowance.

Identify the repetitive event before changing the DC path
A battery-fed inverter may show a repeating DC-terminal variation while supplying a steady AC load. Treating every trough as a new startup event can obscure the mechanism. Establish the component's frequency, measurement location and relationship to AC operation before deciding what the trace means.
Der WEHO WHP-2000 inverter reference provides the relevant family identification. Confirm the exact DC voltage and AC output variant before testing. The illustrated 12 V reference does not establish the AC frequency, permitted DC ripple or internal capacitor arrangement of a supplied unit.
Derive the twice-frequency power term
For an ideal sinusoidal voltage and an in-phase sinusoidal load current, write v(t) = √2 × V × sin(ωt) and i(t) = √2 × I × sin(ωt). V and I are RMS quantities, ω = 2πf, and f is the AC frequency. This model assumes a linear resistive load and excludes conversion losses.
Multiplying gives p(t) = 2VI × sin²(ωt) = P × [1 − cos(2ωt)], where P = VI. Average power is P, while the instantaneous power varies at 2f. At 50 Hz the repetitive term is 100 Hz; at 60 Hz it is 120 Hz.
Research on single-phase power decoupling explains how energy storage and control can buffer this power variation within a converter. The cited work concerns its stated topology and experimental system. It does not reveal the topology, component values or measured performance of a WHP inverter.
The distinction between power demand and external battery current matters. A capacitor or another energy-buffering stage can supply part of the instantaneous demand while the battery provides a smoother current. Do not apply the full calculated pulsation directly to a battery cable without evidence about the actual circuit and measured current.

Work an ideal 480 W example with explicit boundaries
Assume an ideal lossless inverter delivering 480 W to a resistive single-phase load from a perfectly constant 12.0 V DC source. Also assume, solely for this model, that no energy buffer smooths the power transfer. These assumptions create a transparent calculation, not a prediction of WHP operation.
Average input current is 480 W ÷ 12.0 V = 40.0 A. Under the assumed direct power transfer, iDC(t) = 40 × [1 − cos(2ωt)] A. The modeled current ranges from 0 A to 80 A even though its average is 40 A.
The alternating component has a peak amplitude of 40 A and an RMS value of 40 ÷ √2 = 28.28 A. Combining the DC and alternating components gives total RMS current √(40² + 28.28²) = 48.99 A. This is an ideal waveform result, not a cable-sizing instruction or an inverter rating.
Now use a separate hypothetical measured-current input of 8 A peak at 100 Hz and an assumed purely resistive loop impedance of 0.010 Ω at that frequency. The small-signal voltage amplitude is 8 × 0.010 = 0.080 V peak, or 0.160 V peak-to-peak. Its sinusoidal RMS value is 0.080 ÷ √2 = 0.0566 V.
That second calculation does not use the first model's 40 A ripple amplitude. The different amplitude represents an independently specified input after possible buffering. Real impedance can include frequency-dependent battery, cable and connection behavior; a DC resistance figure alone may not describe the entire response.
Swipe horizontally on a small screen, or open the full-size diagram.
Keep ripple, startup dip and switching noise distinct
A repetitive low-frequency component, a single load-step dip and high-frequency switching content can coexist. Each needs an appropriate time window and a clearly named metric. A single maximum-minus-minimum number can combine all three and conceal the event that changed.
| Observed feature | Useful record | Comparison condition | Avoid this inference |
|---|---|---|---|
| Repetition near 2f | Frequency, amplitude and location | Stable load and output frequency | Every trough is a fresh startup |
| One load transition | Minimum voltage and recovery trace | Defined before/after load | One dip defines steady ripple |
| Fast switching content | Trace with stated bandwidth | Same probe and connection | Unlimited bandwidth is comparable to a filtered result |
| Different terminal locations | Synchronized voltage records | Same operating interval | Battery-post voltage equals inverter-terminal voltage |
Victron's DC wiring theory discusses ripple in battery-fed inverter systems and the role of the DC path. Use that explanation to frame a measurement question. Its example values and installation recommendations are not universal WHP limits.
The acceptance record should state whether an amplitude is peak, peak-to-peak or RMS. For one sine wave, peak-to-peak is twice peak, and RMS is peak divided by √2. Distorted traces require calculation from the actual waveform rather than automatic use of those sinusoidal conversions.
Capture the external evidence without opening the inverter
- Identify the operating point. Record the complete inverter label, DC and AC variants, load type, average output power and output frequency. Keep the load steady long enough to distinguish repetition from a transition; do not assume the nominal frequency from the housing alone.
- Define the measurement boundary. Name the battery-post and inverter-terminal locations, polarity, instrument, probe range and bandwidth. Establish permissible measurement connections under the equipment procedure before energizing; a qualified person must assess the actual grounding and voltage conditions.
- Record the slow and fast views. Capture enough time to show several 100 Hz or 120 Hz cycles and a separate appropriate view of switching content when relevant. Retain sampling, filtering and coupling settings so that a later comparison does not silently change the measurement.
- Compare synchronized quantities. Where the approved setup permits, compare DC-terminal voltage with DC current and AC output timing. Check whether the repetitive component tracks twice the actual output frequency; correlation supports the hypothesis but does not identify every internal cause.
- Judge against applicable criteria. Compare the current record with the supplied inverter instructions and project requirements. Record unresolved limits explicitly and request manufacturer clarification rather than importing another brand's alarm threshold or adding unapproved capacitors.
Tektronix's probing application note explains why probe selection and connection affect small ripple measurements. Select equipment for both the small signal and the underlying DC level. AC coupling does not remove a probe's voltage or common-mode limitations.
Tektronix's power-rail measurement guidance also notes that AC coupling can hide low-frequency events. Retain a suitable DC-level record when minimum terminal voltage matters. A cleaner-looking AC-coupled trace cannot establish that the complete DC input remained within its operating range.
Send a frequency-tagged trace to WEHO
Use the WHP-2000 technical enquiry page with the exact variant, load description, battery condition and measurement boundary. Include frequency-tagged voltage and current traces, coupling and bandwidth, and the required project criterion. Ask which documented external-input limits apply to that supplied configuration.
The next decision should follow the evidence: correct a confirmed connection problem, change a project requirement or obtain the missing limit. A repetitive waveform by itself does not justify opening the inverter, bypassing protection or changing internal energy storage. Keep any proposed external modification within the manufacturer's applicable instructions and the equipment review.
Engineering FAQ
Why can a 50 Hz inverter produce a 100 Hz DC-side component?
A sinusoidal voltage multiplied by an in-phase sinusoidal current produces a twice-frequency power term. At 50 Hz that term is 100 Hz. Internal buffering and external impedance determine how much of it appears in measured battery current or terminal voltage.
Does a 100 Hz component prove the inverter is faulty?
No, its frequency alone does not prove a fault. Record amplitude, operating conditions and measurement location, then compare with applicable limits. A normal physical mechanism can still produce an unacceptable system result if the actual conditions exceed those limits.
Can I use peak-to-peak and RMS ripple interchangeably?
No, peak-to-peak and RMS describe different quantities. A pure sine wave permits a defined conversion, while a distorted waveform needs its own calculation. State the metric and bandwidth with every comparison.
Can extra capacitance automatically solve inverter input ripple?
No, extra capacitance is not an automatically approved remedy. It can change charging current, protection behavior and system dynamics. Obtain applicable manufacturer instructions and review the complete external arrangement before specifying a modification.