Check the rail position
Allow for the 55 × 90 × 100 mm housing on TS35/7.5 or TS35/15 rail. The drawing dimensions exclude the cable bend and working space.
MDR-100 is a slim line DIN rail Class I switching power supply.
Designed with a fully isolated plastic case to prevent user contact and the risk of shock.Featuring up to 88% efficiency this series can be cooled using only free air convection up to 60°C which significantly increases the reliability and lifetime of the power supply.Other standard features include its low no-load power consumption, to save energy, short circuit, overload, and over voltage protections, and DC OK relay contact with LED indicator for monitoring the PSU status.If you have any questions, please do not hesitate to contact us at ایمیل: [email protected]
Choose the 12, 24, 36 or 48 V control supply and check its current range before allocating cabinet space.
| Parameter | MDR-100-12 | MDR-100-24 | MDR-100-36 | MDR-100-48 |
|---|---|---|---|---|
| DC output voltage and current | 12 V · 0–7.5 A | 24 V · 0–4.16 A | 36 V · 0–2.7 A | 48 V · 0–2 A |
| کارایی | 78% | 86% | 88% | 88% |
| موج و نویز | 120 mV p-p | 150 mV p-p | 150 mV p-p | 200 mV p-p |
| تنظیم خط | ± 1% | ± 1% | ± 1% | ± 1% |
| تنظیم بار | ± 1% | ± 1% | ± 1% | ± 1% |
| DC voltage adjustment | ± 1% | ± 1% | ± 1% | ± 1% |
| ورودی AC | 85–264 VAC | |||
| ورودی DC | 120–370 VDC | |||
| Dimensions (W × H × D) | 55 × 90 × 100 mm | |||
| Input frequency | 47–63 Hz | |||
| Cold-start inrush | 30 A at 115 VAC; 60 A at 230 VAC | |||
| حفاظت اضافه بار | 105–150%; output cuts off and recovers automatically. | |||
| حفاظت از اضافه ولتاژ | 120–140%; output shuts down. Cycle input power to recover. | |||
| Setup / rise at full load | 3000 / 50 ms at 230 VAC; 3000 / 50 ms at 115 VAC. | |||
| Hold-up time | Not specified. | |||
| Withstand voltage (1 min) | Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV. | |||
| مقاومت عایق | 100 MΩ at 500 VDC: input/output, input/FG and output/FG. | |||
| دمای کاری | −10 °C to +50 °C | |||
| Mounting rail | TS35/7.5 or TS35/15 | |||
| Unit weight | 0.42 kg | |||
| بسته بندی | Not specified (/) | |||
| DC OK relay | Closed: power on / DC normal; open: power off / DC fault. Maximum contact rating: 30 V / 1 A, resistive load. | |||
| مدل | خروجی | Current | کارایی |
|---|---|---|---|
| MDR-100-12 | ۱۲ ولت | 0–7.5 A | 78% |
| MDR-100-24 | ۲۴ ولت | 0–4.16 A | 86% |
| MDR-100-36 | 36 V | 0–2.7 A | 88% |
| MDR-100-48 | ۴۸ ولت | 0–2 A | 88% |
| موج و نویز | 120 mV p-p |
|---|---|
| تنظیم خط | ± 1% |
| تنظیم بار | ± 1% |
| DC voltage adjustment | ± 1% |
| موج و نویز | 150 mV p-p |
|---|---|
| تنظیم خط | ± 1% |
| تنظیم بار | ± 1% |
| DC voltage adjustment | ± 1% |
| موج و نویز | 150 mV p-p |
|---|---|
| تنظیم خط | ± 1% |
| تنظیم بار | ± 1% |
| DC voltage adjustment | ± 1% |
| موج و نویز | 200 mV p-p |
|---|---|
| تنظیم خط | ± 1% |
| تنظیم بار | ± 1% |
| DC voltage adjustment | ± 1% |
| ورودی AC | 85–264 VAC |
|---|---|
| ورودی DC | 120–370 VDC |
| Dimensions (W × H × D) | 55 × 90 × 100 mm |
| Input frequency | 47–63 Hz |
| Cold-start inrush | 30 A at 115 VAC; 60 A at 230 VAC |
| حفاظت اضافه بار | 105–150%; output cuts off and recovers automatically. |
| حفاظت از اضافه ولتاژ | 120–140%; output shuts down. Cycle input power to recover. |
| Setup / rise at full load | 3000 / 50 ms at 230 VAC; 3000 / 50 ms at 115 VAC. |
| Hold-up time | Not specified. |
| Withstand voltage (1 min) | Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV. |
| مقاومت عایق | 100 MΩ at 500 VDC: input/output, input/FG and output/FG. |
| دمای کاری | −10 °C to +50 °C |
| Mounting rail | TS35/7.5 or TS35/15 |
| Unit weight | 0.42 kg |
| بسته بندی | Not specified (/) |
| DC OK relay | Closed: power on / DC normal; open: power off / DC fault. Maximum contact rating: 30 V / 1 A, resistive load. |
55 × 90 × 100 mm

Width and height are dimensioned on the front view.

Depth is dimensioned on the side view; it does not include field wiring.

Rail profile from the model sheet. Mounting types: TS35/7.5 and TS35/15.
Terminal groups: 1 and 2 — AC input; 3 — ground; 4 — DC positive; 5 — DC negative; 6 — DC OK. Follow the markings on the actual unit. Do not infer DC-input polarity from the AC labels.
The DC OK relay reports output status. Its resistive-contact rating is not the supply output rating.
This family includes a 36 V model; it does not list a 5 V model. The 24 V sheet column specifies 0–4.16 A.
The MDR-100 brings a regulated DC branch and a status relay to the rail. Choose the output from the load label, then use its own column for current, ripple and efficiency.
| ویژگی | What to check |
|---|---|
| Voltage selection | Choose a fixed output suffix before comparing current ranges. |
| Status monitoring | The DC OK relay reports output status. Its resistive-contact rating is not the supply output rating. |
| Service access | Allow for the 55 × 90 × 100 mm body plus wiring and access to the voltage trim. |
| Power budget | This family includes a 36 V model; it does not list a 5 V model. The 24 V sheet column specifies 0–4.16 A. |
The photo identifies one specimen; electrical data on this page come from the WEHO model sheet.

Allow for the 55 × 90 × 100 mm housing on TS35/7.5 or TS35/15 rail. The drawing dimensions exclude the cable bend and working space.

The photograph identifies MDR-100-24. With power isolated, check the full suffix and terminal markings on the unit being installed. A different output choice is a different version.

For MDR-100-24, the printed current range is 0–4.16 A. Add the branch loads that can start together; do not substitute input inrush for DC capacity.

The input inrush is 30 A at 115 VAC; 60 A at 230 VAC. Check the upstream protection at the corresponding input voltage, separately from output current.

The extruder drive advances filament while the head traces the part. For a separately supplied 24 V DC motor driver, compare its peak input with MDR-100-24 (0–4.16 A). The nozzle and bed heaters need their own power budget.
Photo: Jonathan Juursema · CC BY-SA 3.0
A photometer uses a light source and detector to read a sample. For an instrument specified for an external 12 V DC input, check ripple tolerance and the combined source, detector and display demand against MDR-100-12 (0–7.5 A).
Photo: NeoLyo89 · CC BY 4.0
A peristaltic drive advances liquid through flexible tubing to the dispensing head. For an independent 24 V DC pump controller, check peak input under the intended tubing load against MDR-100-24 (0–4.16 A). The drive, not the supply, sets the flow.
Photo: Photocyte · CC BY-SA 4.0
A lightbox shines through the negative while the camera records it. For a backlight with a 12 V DC driver input, compare maximum brightness current with MDR-100-12 (0–7.5 A) and check for flicker at the intended shutter speed. Exclude the camera.
Photo: Djm-leighpark · CC BY-SA 4.0These photographs show examples of low-voltage loads, not verified MDR-100 installations or endorsements. Check the actual component’s input specification before selecting a supply.
No. Each column identifies a separate single-output version. For example, MDR-100-12 is the 12 V model and MDR-100-24 is the 24 V model. The trim adjustment is not a voltage selector.
MDR-100-24 is specified at 0–4.16 A. Include simultaneous loads and startup demand when sizing the branch.
The MDR-100 datasheet specifies 85–264 VAC and 120–370 VDC. The 47–63 Hz frequency range applies to AC.
The housing measures 55 × 90 × 100 mm. The manufacturer drawing lists TS35/7.5 or TS35/15; reserve extra space for cable access.
The DC OK relay reports output status. Its resistive-contact rating is not the supply output rating.
No. The sheet lists −10 °C to +50 °C as the working range; it does not establish full load at every ambient temperature. Check the actual enclosure conditions.
Overload cuts off output with automatic recovery. Overvoltage shuts down the output; cycle input power after the fault is cleared.
3000 / 50 ms at 230 VAC; 3000 / 50 ms at 115 VAC. These are full-load setup and rise times. No separate hold-up value is printed.
30 A at 115 VAC; 60 A at 230 VAC are the two cold-start input conditions. Coordinate upstream protection for the actual input and number of supplies starting together.
MDR-100-12 lists 120 mV p-p. Check the ripple tolerance at the load as well as the DC current requirement.
Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV. These one-minute withstand figures are not continuous operating voltages.
Give the full MDR-100 suffix, DC load and startup demand, installed rail and available space. A match in family wattage or cabinet width does not establish interchangeability.



This view shows MDR-100-24; the photographed unit does not change when another output is selected. Electrical specifications follow the MDR-100 datasheet.

A crop of the pictured specimen for identification, not a separate specification source.

Width and height are dimensioned on the front view.

Depth is dimensioned on the side view; it does not include field wiring.

Rail profile from the model sheet. Mounting types: TS35/7.5 and TS35/15.