Match the supply to the load
Check the incoming supply against 90–132 V AC / 180–264 V AC (by switch). Add the starting currents of devices that energize together before selecting the output version.
The LRS-600 is a 600W-class single-output enclosed power supply with 5V, 12V, 15V, 24V, 36V and 48V versions. Select the exact version and listed current range for the load. Select 90–132VAC or 180–264VAC using the input-range switch; the DC input range is 255–370VDC (Switch on 230VAC) and the AC frequency range is 47–63Hz. The enclosure is fan-equipped. Its working range is -30°C to +70°C at 20%–90% RH, non-condensing. Confirm the actual enclosure version and mounting dimensions before final equipment layout, and confirm permissible loading for the installation.
If you interested in This Series,Please contact us at Электронная почта: [email protected]
Single-output AC–DC supply with switch-selectable AC input.
| Параметр | LRS-600-12 | LRS-600-15 | LRS-600-24 | LRS-600-36 | LRS-600-48 |
|---|---|---|---|---|---|
| DC output voltage and current | 12 В 0 ~ 50 А | 15V 0~40A | 24 В 0 ~ 25 А | 36V 0~16.6A | 48V 0~12.5A |
| Диапазон входного напряжения | 90–132VAC / 180–264VAC by switch; 255–370VDC (Switch on 230VAC); 47–63Hz | ||||
| Размеры | Dimensional references (L × W × H): Dimension entry 225 × 115 × 50 mm; table-heading reference 225 × 144 × 41 mm; mechanical drawing body 225 × 124 × 41 mm, with a 144 mm span including mounting ears. Confirm the actual version and mounting dimensions before specifying the installation space. | ||||
| Эффективность | 90% | 90% | 91% | 92% | 92% |
| Working temperature / humidity | -30°C to +70°C / 20%–90% RH, non-condensing. Storage: -40°C to +85°C / 10%–95% RH, non-condensing. Confirm permissible loading for the actual installation temperature. | ||||
| Ripple & noise | 200 мВпик-пик | 240 мВ (пик-пик) | 240 мВ (пик-пик) | 360mVp-p | 360mVp-p |
| Регулирование линии | ±0,5% | ||||
| Регулирование нагрузки | ±1% | ±0,5% | ±0,5% | ±0,5% | ±0,5% |
| DC voltage adjustment | 11.4–13.2V | 14.25–16.5V | 22.8–26.4V | 34.2–39.6V | 45.6–52.8V |
| Input / cold-start / leakage current | Input current: 12A/115VAC, 7.5A/230VAC. Cold-start current: 35A/115VAC, 60A/230VAC. Leakage current: <0.7mA @ 240V. | ||||
| Защита от перегрузки | 105%–150% of rated output power. Hiccup mode; automatic recovery after the abnormal condition is removed. | ||||
| Защита от перенапряжения | 13.8–16.2V | 18–21V | 28.8–33.6V | 41.4–48.6V | 55.2–64.8V |
| Overvoltage recovery | Hiccup mode; automatic recovery after the abnormal condition is removed. | ||||
| Short-circuit protection | Output terminal short circuit: hiccup mode; automatic recovery after the abnormal condition is removed. | ||||
| Защита от перегрева | Automatic recovery once the temperature returns to normal. | ||||
| Timing (setup / rise / hold-up) | 1300ms, 50ms/230VAC; 1300ms, 50ms/115VAC at full load. No separate hold-up time is specified. | ||||
| Выдерживая напряжение | I/P-O/P: 4kVAC; I/P-FG: 2kVAC; O/P-FG: 1.25kVAC | ||||
| Устойчивость к изоляции | I/P-O/P, I/P-FG, O/P-FG: 100M Ohm / 500VDC | ||||
| Масса | 0.95kg | ||||
| Упаковка | 45,5 × 31,5 × 26CM/20PCS/20 кг | ||||
| Выход | Текущий | Эффективность | Пульсация (mVp-p) |
|---|---|---|---|
| 12 V | 0–50 A | 90% | 200 |
| 15 V | 0–40 A | 90% | 240 |
| 24 V | 0–25 A | 91% | 240 |
| 36 V | 0–16.6 A | 92% | 360 |
| 48 V | 0–12.5 A | 92% | 360 |
| 12 V | ±1% |
|---|---|
| 15 V | ±0,5% |
| 24 V | ±0,5% |
| 36 V | ±0,5% |
| 48 V | ±0,5% |
| 12 V | 11.4–13.2V |
|---|---|
| 15 V | 14.25–16.5V |
| 24 V | 22.8–26.4V |
| 36 V | 34.2–39.6V |
| 48 V | 45.6–52.8V |
| 12 V | 13.8–16.2V |
|---|---|
| 15 V | 18–21V |
| 24 V | 28.8–33.6V |
| 36 V | 41.4–48.6V |
| 48 V | 55.2–64.8V |
| Диапазон входного напряжения | 90–132VAC / 180–264VAC by switch; 255–370VDC (Switch on 230VAC); 47–63Hz |
|---|---|
| Размеры | Dimensional references (L × W × H): Dimension entry 225 × 115 × 50 mm; table-heading reference 225 × 144 × 41 mm; mechanical drawing body 225 × 124 × 41 mm, with a 144 mm span including mounting ears. Confirm the actual version and mounting dimensions before specifying the installation space. |
| Working temperature / humidity | -30°C to +70°C / 20%–90% RH, non-condensing. Storage: -40°C to +85°C / 10%–95% RH, non-condensing. Confirm permissible loading for the actual installation temperature. |
| Регулирование линии | ±0,5% |
| Input / cold-start / leakage current | Input current: 12A/115VAC, 7.5A/230VAC. Cold-start current: 35A/115VAC, 60A/230VAC. Leakage current: <0.7mA @ 240V. |
| Защита от перегрузки | 105%–150% of rated output power. Hiccup mode; automatic recovery after the abnormal condition is removed. |
| Overvoltage recovery | Hiccup mode; automatic recovery after the abnormal condition is removed. |
| Short-circuit protection | Output terminal short circuit: hiccup mode; automatic recovery after the abnormal condition is removed. |
| Защита от перегрева | Automatic recovery once the temperature returns to normal. |
| Timing (setup / rise / hold-up) | 1300ms, 50ms/230VAC; 1300ms, 50ms/115VAC at full load. No separate hold-up time is specified. |
| Выдерживая напряжение | I/P-O/P: 4kVAC; I/P-FG: 2kVAC; O/P-FG: 1.25kVAC |
| Устойчивость к изоляции | I/P-O/P, I/P-FG, O/P-FG: 100M Ohm / 500VDC |
| Масса | 0.95kg |
| Упаковка | 45,5 × 31,5 × 26CM/20PCS/20 кг |
Version-dependent; see drawing (L × W × H)
| Dimension entry | 225 × 115 × 50 mm |
|---|---|
| Table-heading reference | 225 × 144 × 41 mm |
| Mechanical drawing body | 225 × 124 × 41 mm |
| Span including mounting ears | 144 mm |
Dimensions in millimetres. The dimension entry, table heading and mechanical drawing give different references. Confirm the enclosure version and mounting dimensions before installation.
Use these curves only within their -20 to +65 °C coverage and the WEHO input limits. They do not define load limits for the unplotted -30 to -20 °C or +65 to +70 °C parts of the table's operating range. Do not extrapolate.
Functional stages are shown here; the specification table governs rated output, protection thresholds and recovery.
For a 24 V control rail, the LRS-600-24 has a listed output range of 0–25 A. Compare that range with the combined demand of your controllers, sensors and interface modules, including devices that start together. Check the voltage-adjustment limits for the selected output. Check both the electrical column and the actual housing revision before completing the panel design.
Panel fit: The dimension row says 225 × 115 × 50 mm, the heading says 225 × 144 × 41 mm and the drawing shows a 225 × 124 × 41 mm body with a 144 mm ear span. Confirm the housing before committing the panel layout.
| Особенность | What to check |
|---|---|
| Output trim | On LRS-600-24, the output adjusts from 22.8 to 26.4 V. Check the limits for the specific output. |
| Enclosure fit | Confirm the mounting dimensions and allow room for wiring bends, airflow and terminal access. |
| Overload recovery | The output recovers after the overload condition is removed. Check how the equipment restarts. |

Check the incoming supply against 90–132 V AC / 180–264 V AC (by switch). Add the starting currents of devices that energize together before selecting the output version.

The sheet gives different body and mounting references. Verify the physical version and ear span before drilling the panel.

The listed working range is -30 to +70 °C. Measure the air near the installed supply under sustained load. Use the applicable loading curve within its stated limits.

When power returns, the controls may restart before the machine is ready. Check the host equipment’s restart sequence independently.
Size the supply for the auxiliary electronics, not for the whole machine.

Power a sign timer or a compatible display controller. LED modules may need separate current regulation.
24 V option: LRS-600-24 · listed current 0–25 A.

Size the rail for sensors and the operator interface. Account separately for lock pickup current.
12 V option: LRS-600-12 · listed current 0–50 A.

Supply sensors and indicators at the forming station. Size drive and safety circuits separately.
24 V option: LRS-600-24 · listed current 0–25 A.

Supply status indicators or trigger interfaces. Use a separate precision source when the test requires controlled excitation.
12 V option: LRS-600-12 · listed current 0–50 A.
AI illustrations for application planning; not installation photographs, wiring diagrams or mechanical references.
Choose one nominal output: 12 V, 15 V, 24 V, 36 V, 48 V. Each voltage is a separate model.
The listed AC input is 90–132 V AC / 180–264 V AC (by switch); the DC input is 255–370 V DC (switch on 230 V AC). The gap between the two AC bands is not part of the specified input range.
LRS-600-24 is listed at 0–25 A. Check the current at startup as well as in steady operation.
The datasheet gives output current by voltage. Use the selected model’s current range and application conditions rather than treating the series name as a continuous rating for every version.
The working range is -30 to +70 °C. The curves cover only −20 to +65 °C. Do not extrapolate into the remaining temperature range.
Check each dimension reference and confirm the enclosure version before installation.
The cold-start input current is 35 A at 115 V AC, 60 A at 230 V AC. This is an input-side event, not the current available to the DC load.
Include the exact model, quantity, input source, load profile and destination. Include the available mounting space if the enclosure is tight.
In the inquiry form, enter model LRS-600-12LRS-600-15LRS-600-24LRS-600-36LRS-600-48 with your requirements.