PSC-350 12V 24V Ac to Dc Ups 3 Years Warranty Switching Power Supply
A 350W UPS-enabled power supply, the PSC-350W delivers 12V/20A or 24V/14.5A outputs with 89% efficiency. It supports cold-start operation, auto-switching between AC and battery, and precision voltage adjustment. Protections include overcurrent recovery and low-battery shutdown. The 215×115×30mm frame (0.85kg) features LED status lights and operates in -20°C to +60°C. Tailored for high-power applications like industrial automation, renewable energy systems, and large-scale lighting, it combines rugged design, universal input (90–264VAC), and 3-year warranty for critical backup needs.
- Description
Model | PSC-350-12 | PSC-350-24 | ||
DC Output Voltage | CH1:13.8V | CH2:13.8V | CH1:27.6V | CH2:27.6V |
Output Voltage Tolerance | ±1% | —– | ±1% | —– |
Rated Output Current | 20A | 5A(charge) | 10A | 25A(charge) |
Output Current Range | 0~25A | —- | 0~12.5A | —– |
Output Power | 345W | 350W | ||
Ripple and Noise | 180mVp-P | —– | 200mVp-P | —– |
Adjustable Range of DC Voltage | CH1:11.3~14.9V | CH1:21.3~29.8V | ||
Start-up,Rise,and Hold Time | 600ms,50ms,80ms/230VAC.1200ms.50ms.16ms/115VAC. | |||
Input Voltage Range | 90~264VACor 135~370VDC | |||
ACInput Current | 6.5A/115VAC 3.5A/230VAC | |||
Efficiency | 89% | 89% | ||
Inrush Current | Cold Start Current 45A/115VAC 55A/230VAC | |||
Leakage Current | <lmA/240VAC | |||
Overload Protection | Overload protection will be activated at 105%to 115%of the rated output power | |||
Protetion mode:ACcharging mode:Isolation mode,the system can automaticall resume operation afer the abnormal load condition is removed. | ||||
Low Battery Voltage Protection | 9.5~10.3V | 19~20.5V | ||
Protection mode:Output cut-off. | ||||
Introduction to UPS Function | Long-term online float charging for batteries with high efficiency,over 98%fullness. | |||
Automatically stops charging when full to prevent overcharge and extend battery life | ||||
Automaticswitch between utility power and batery without delay,no manual operation needed. | ||||
Cold start capability allows UPSto start directly from battery in case of no utility power,meeting emergency needs. | ||||
Operating Temperature and Humidity | -20°Cto~60°C;20%~90%RH(Please refer to theload derating curve). | |||
Storage Temperature and Humidity | -20℃~+85℃;10%~95%RHNon-condensing | |||
Shock Resistance | 10~500Hz,2G 10min./per cycle,duration 60 minutes,on each axis | |||
Voltage Withstanding Capability | Between input andoutput:1.5kVAC Between input and ground:1.5kVAC Between output and ground:0.5kVDC | |||
Insulation Resistanc | Between input and output,input and ground,output and ground:100MQ/500 VDC | |||
Dimensions | 215*115*30mm(L*W*H) | |||
Packaging | 0.85kg/20pcs/18.5kg/0.041m³ |