SP-3000 High Power Switching Power Supply
SP-3000 is a 3KW single output chassis type AC to DC power supply. The entire series input voltage range is 95-265VAC, and can provide DC output for most industrial needs.
Each chassis can be air-cooled through an internal speed-controlled fan, and the operating temperature is close to 60°C.Built-in multiple functions such as output voltage,Current adjustable, current sharing, remote on/off control, 485 communication control, auxiliary power supply and other functions provide a variety of flexible designs.
If you have any questions, please do not hesitate to contact us at Email: [email protected]
- Description
Summary
Single output: power 3000W
Input voltage: 95-190VAC(output current 50%)195-265VAC(output current 100%)
Features
1. Protection type: short circuit/overcurrent/overvoltage/overtemperature
2. Power factor PF≧0.99
3. Working efficiency up to 93%
4. 485 communication control
General Specification
| Model | SP-3000-12 | SP-3000-24 | SP-3000-30 | SP-3000-36 | SP-3000-48 | SP-3000-60 | SP-3000-220 |
| DC voltage | 12V | 24V | 30V | 36V | 48V | 60V | 220V |
| Rated current | 130A | 125A | 100A | 83.3A | 62.5A | 50A | 13.6A |
| Current range | 0-130A | 0-125A | 0-100A | 0-83.3A | 0-62.5A | 0-50A | 0-13.6A |
| Rated Power | 2700W | 3000W | |||||
| Ripple | 200mV | 200mV | 230mV | 260mV | 300mV | 500mV | 1000mV |
| Constant current optimum range | 6-15V | 12-24V | 15-30V | 18-36V | 24-48V | 30-60V | 110-220V |
| Rated voltage accuracy | ±1.0% | ||||||
| Line Regulation | ±1.0% | ||||||
| Load Regulation | ±1.0% | ||||||
| Startup&Rise Time | 1500mS,700mS/230VAC (Fully loaded) | ||||||
| Voltage range | 95-190VAC(Output Current 50%),195-265VAC(Output Curent 100%) | ||||||
| Frequency range | 45Hz-65Hz | ||||||
| Power Factor | PF≥0.99/230VAC (Fully loaded) | ||||||
| Efficiency(MAX) | 0.9 | 0.9 | 0.91 | 0.915 | 0.92 | 0.925 | 0.93 |
| AC Current | <18A | ||||||
| Leakage Current | <3.0mA/240VAC | ||||||
| Short Circuit | When the constant current is entered and the voltage is lower than 10%of the rated voltage,the output is shut down and locked after 1 second,and recovers after restarting. | ||||||
| Over current | The user can set the over-current value to delay the oufput for 5 seconds and then shut down the output,and then resume after restarting. | ||||||
| Overpressure | Users can set the overvoltage value to shut down the output voltage,and restore after restart. | ||||||
| Over temperature | Shut down the output,automatically recover or restart after the temperature drops. | ||||||
| Output voltage adjustment | 0-15V | 0-26.4V | 0-33V | 0-39.6V | 0-52.8V | 0-66V | 0-242V |
| Output constant current adjustment | 0-130A | 0-125A | 0-100A | 0-83.3A | 0-62.5A | 0-50A | 0-13.6A |
| 485 Communications | Parallel current sharing | ||||||
| Isolated auxiliary power supply | 12V 0.5A | ||||||
| Output remote switch | Default power on,high level power off(5V-12V) | ||||||
| Alarm signal output | Power Good Signal(Dry Contact≤36V,0.1A) | ||||||
| Operating temperature | -20-+60℃ | ||||||
| Operating humidity | -20-90% RH No condensation | ||||||
| Storage emperatureandhumidity | -40-+85℃,10-95%RHNo condensation | ||||||
| Vibration resistance | 10-500Hz,2G10Min/cycle,X、Y、 Ż60Min_ | ||||||
| Insulation resistance | Input to Output:100Mhms/500VDC/25°C/70%RH | ||||||
| Pressure resistance | I/P-O/P:2KVAC IP-FG:2KVAC O/P-FG:0.5KVAC | ||||||
| Size | 289×174×69mm | ||||||
| Net weight | 3.3 kg | ||||||
Overall Dimension(mm)