Reserve space on the rail
The sheet lists 40 × 125.2 × 113.5 mm. Check terminal access and cable bends separately; the enclosure dimension is not an installation clearance.
NDR-120 is a single-output DIN-rail switching power supply with separate 12V, 15V, 24V and 48V models. The specified input range is 85–264VAC or 120–370VDC, with 47–63Hz AC input. Working temperature is -10°C to +50°C. Check the selected output rating and installation conditions before ordering.
If you have any questions, please do not hesitate to contact us at Email: [email protected]
Choose 12 V, 15 V, 24 V or 48 V for a 120 W-class DIN rail supply. Each suffix identifies a separate output version.
| Parameter | NDR-120-12 | NDR-120-15 | NDR-120-24 | NDR-120-48 |
|---|---|---|---|---|
| DC output voltage and current | 12 V · 0–10 A | 15 V · 0–8 A | 24 V · 0–5 A | 48 V · 0–2.5 A |
| Efficiency | 86% | 88% | 88% | 89% |
| Ripple and noise | 100 mV p-p | 120 mV p-p | 120 mV p-p | 150 mV p-p |
| Line regulation | ±0.5% | ±0.5% | ±0.5% | ±0.5% |
| Load regulation | ±0.5% | ±0.5% | ±0.5% | ±0.5% |
| DC voltage adjustment | ±10% | ±10% | ±10% | ±10% |
| AC input | 85–264 VAC | |||
| DC input | 120–370 VDC | |||
| Dimensions | 40 × 125.2 × 113.5 mm | |||
| Family power class | 120 W (single output) | |||
| Input frequency | 47–63 Hz | |||
| Cold-start inrush | 30 A at 115 VAC; 60 A at 230 VAC | |||
| Overload protection | 105–150%: output cutoff; automatic recovery. | |||
| Overvoltage protection | 120–140%: output shuts down. Reapply power to recover. | |||
| Setup / rise / hold-up | 1200 / 60 / 60 ms at 230 VAC, full load. | |||
| Withstand voltage | Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV; 1 minute. | |||
| Insulation resistance | Input/output, input/FG and output/FG: 100 MΩ at 500 VDC. | |||
| Working environment | −10 to +50 °C | |||
| Unit weight | 0.6 kg | |||
| Packing | 45.5 × 35 × 26 cm | |||
| Model | Output | Current | Efficiency |
|---|---|---|---|
| NDR-120-12 | 12 V | 0–10 A | 86% |
| NDR-120-15 | 15 V | 0–8 A | 88% |
| NDR-120-24 | 24 V | 0–5 A | 88% |
| NDR-120-48 | 48 V | 0–2.5 A | 89% |
| Ripple and noise | 100 mV p-p |
|---|---|
| Line regulation | ±0.5% |
| Load regulation | ±0.5% |
| DC voltage adjustment | ±10% |
| Ripple and noise | 120 mV p-p |
|---|---|
| Line regulation | ±0.5% |
| Load regulation | ±0.5% |
| DC voltage adjustment | ±10% |
| Ripple and noise | 120 mV p-p |
|---|---|
| Line regulation | ±0.5% |
| Load regulation | ±0.5% |
| DC voltage adjustment | ±10% |
| Ripple and noise | 150 mV p-p |
|---|---|
| Line regulation | ±0.5% |
| Load regulation | ±0.5% |
| DC voltage adjustment | ±10% |
| AC input | 85–264 VAC |
|---|---|
| DC input | 120–370 VDC |
| Dimensions | 40 × 125.2 × 113.5 mm |
| Family power class | 120 W (single output) |
| Input frequency | 47–63 Hz |
| Cold-start inrush | 30 A at 115 VAC; 60 A at 230 VAC |
| Overload protection | 105–150%: output cutoff; automatic recovery. |
| Overvoltage protection | 120–140%: output shuts down. Reapply power to recover. |
| Setup / rise / hold-up | 1200 / 60 / 60 ms at 230 VAC, full load. |
| Withstand voltage | Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV; 1 minute. |
| Insulation resistance | Input/output, input/FG and output/FG: 100 MΩ at 500 VDC. |
| Working environment | −10 to +50 °C |
| Unit weight | 0.6 kg |
| Packing | 45.5 × 35 × 26 cm |
40 × 125.2 × 113.5 mm

Side elevation from the model sheet; dimensions in mm.

Front elevation from the model sheet; dimensions in mm.

Top view from the model sheet; dimensions in mm.

Bottom view from the model sheet; dimensions in mm.
TB1: 1 = FG; 2 = AC/N or DC −; 3 = AC/L or DC +.
TB2: 4 and 5 = −V; 6 and 7 = +V.
Use NDR-120 where the panel needs one DC voltage. For example, NDR-120-12 provides 12 V at 0–10 A, while NDR-120-48 provides 48 V at 0–2.5 A. Compare the actual load profile, not the suffix alone.
| Feature | What to check |
|---|---|
| Output selection | 12 V, 15 V, 24 V or 48 V; choose one version for the required DC rail. |
| Input and restart | At cold start the input draws 30 A at 115 VAC; 60 A at 230 VAC. This transient is not available to the DC load. |
| Cabinet environment | −10 to +50 °C. Check the intended load at the actual ambient temperature. |

The sheet lists 40 × 125.2 × 113.5 mm. Check terminal access and cable bends separately; the enclosure dimension is not an installation clearance.

TB1: 1 = FG; 2 = AC/N or DC −; 3 = AC/L or DC +. TB2: 4 and 5 = −V; 6 and 7 = +V. Verify the markings on the unit before connecting power.

−10 to +50 °C. Check the air temperature at the supply under the intended cabinet load. The temperature interval alone does not rate full output at its upper limit.

The sheet gives 30 A at 115 VAC; 60 A at 230 VAC. Compare the applicable input condition with upstream protection; these are not DC load-current ratings.

A carton sensor can trigger the applicator as the box reaches the head. Include the sensor and DC control inputs; size a print engine or pneumatic actuator separately. For an external 24 V DC input, compare total running and peak demand with NDR-120-24 (0–5 A).
Photo: Robert Luther — 4051 lpa.jpg · Public domain · Converted to WebP; full frame. Illustrative only; no endorsement or verified installation.
A bin-presence input can confirm that a tote has reached the retrieval station before the next transfer. The input module and sensors form a different load from the aisle crane. For an external 24 V DC input, compare total running and peak demand with NDR-120-24 (0–5 A).
Photo: Andreas Praefcke — Automatisches Kleinteilelager.jpg · CC BY 3.0 · Converted to WebP; full frame. Illustrative only; no endorsement or verified installation.
A height sensor can tell the film carriage where the top of a pallet load is. Check the sensor and carriage-control inputs rather than treating the turntable motor as a DC control load. For an external 24 V DC input, compare total running and peak demand with NDR-120-24 (0–5 A).
Photo: heb @ Wikimedia Commons — Pallet wrapper.jpg · CC BY-SA 3.0 · Resized and converted to WebP; full frame. Illustrative only; no endorsement or verified installation.
At a carrier terminal, an arrival switch can light an indicator for the attendant. Check the combined indicator and interface load; the air blower has its own supply. For an external 24 V DC input, compare total running and peak demand with NDR-120-24 (0–5 A).
Photo: Hustvedt — Bank pneumatic tubes.jpg · CC BY-SA 3.0 · Resized and converted to WebP; full frame. Illustrative only; no endorsement or verified installation.Application images are illustrations of possible DC loads, not customer installations or verified equipment pairings.
The WEHO sheet lists 12 V, 15 V, 24 V or 48 V. These are separate orderable versions, not four outputs from one supply.
NDR-120-24 is listed at 0–5 A. Include all loads that operate together; check startup demand separately.
The NDR-120 sheet lists 85–264 VAC at 47–63 Hz, or 120–370 VDC. State which supply will be present at the panel.
105–150%: output cutoff; automatic recovery. Overvoltage: 120–140%: output shuts down. Reapply power to recover.
The sheet lists 40 × 125.2 × 113.5 mm. Allow space for the cable bend and access to the terminal blocks.
Give the full suffix (for example, NDR-120-24), input source, running and startup current, cabinet temperature, quantity and destination.
The NDR-120 company datasheet specifies a working temperature of −10 to +50 °C. It does not give a load-versus-temperature curve for these output versions. Do not treat the upper ambient limit as a full-load rating.
For a continuous-duty installation, state the selected output, maximum cabinet temperature, mounting position and expected load when requesting a confirmed operating point.



NDR-120-24 is the photographed sample. Select the electrical version separately.

Mounting-side view from the NDR-120 image set. This angle does not identify an electrical suffix.

Side elevation from the model sheet; dimensions in mm.

Front elevation from the model sheet; dimensions in mm.

Top view from the model sheet; dimensions in mm.

Bottom view from the model sheet; dimensions in mm.