Din Rail Switching Power Supply EDR-240 240W 24V 48V Industrial AC to DC Power Supply

The WEHO EDR-240 series is a DIN-rail AC-DC power supply. Select the output version that matches the connected equipment and check the installation and operating requirements before use.

If you have any questions, please do not hesitate to contact us atEmail: [email protected]

EDR-240-24 · photographed sample

EDR-240 Single-Output DIN Rail Power Supply

Choose 24 V or 48 V for a 240 W-class DIN rail supply. Each suffix identifies a separate output version.

Select output voltage
Model
EDR-240-24EDR-240-48
DC output
24 V · 0–10 A48 V · 0–5 A
AC input
90–264 VAC
DC input
127–370 VDC
Efficiency
86%87.5%
Dimensions
63 × 125.2 × 113.5 mm

Specifications & models

ParameterEDR-240-24EDR-240-48
DC output voltage and current24 V · 0–10 A48 V · 0–5 A
Efficiency86%87.5%
Ripple and noise150 mV p-p150 mV p-p
Line regulation±0.5%±0.5%
Load regulation±1%±1%
DC voltage adjustment±10%±10%
AC input90–264 VAC
DC input127–370 VDC
Dimensions63 × 125.2 × 113.5 mm
Family power class240 W (single output)
Input frequency47–63 Hz
Cold-start inrush20 A at 115 VAC; 35 A at 230 VAC
Overload protection105–130%: output cutoff; automatic recovery.
Overvoltage protection115–140% of rated output power (sheet wording); output shuts down. Reapply power to recover. No voltage trip level is specified.
Setup / rise1500 / 100 ms at 230 VAC; 3000 / 100 ms at 115 VAC, full load. Hold-up time is not specified.
Withstand voltageInput/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV; 1 minute.
Insulation resistanceInput/output, input/FG and output/FG: 100 MΩ at 500 VDC, 25 °C and 70% RH.
Working environment−20 to +60 °C
Unit weight0.92 kg
Packing42.5 × 29 × 27.5 cm / 24 pcs / 22 kg
Output options
ModelOutputCurrentEfficiency
EDR-240-2424 V0–10 A86%
EDR-240-4848 V0–5 A87.5%
Additional model specifications
EDR-240-24
Ripple and noise150 mV p-p
Line regulation±0.5%
Load regulation±1%
DC voltage adjustment±10%
EDR-240-48
Ripple and noise150 mV p-p
Line regulation±0.5%
Load regulation±1%
DC voltage adjustment±10%
Common specifications
AC input90–264 VAC
DC input127–370 VDC
Dimensions63 × 125.2 × 113.5 mm
Family power class240 W (single output)
Input frequency47–63 Hz
Cold-start inrush20 A at 115 VAC; 35 A at 230 VAC
Overload protection105–130%: output cutoff; automatic recovery.
Overvoltage protection115–140% of rated output power (sheet wording); output shuts down. Reapply power to recover. No voltage trip level is specified.
Setup / rise1500 / 100 ms at 230 VAC; 3000 / 100 ms at 115 VAC, full load. Hold-up time is not specified.
Withstand voltageInput/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV; 1 minute.
Insulation resistanceInput/output, input/FG and output/FG: 100 MΩ at 500 VDC, 25 °C and 70% RH.
Working environment−20 to +60 °C
Unit weight0.92 kg
Packing42.5 × 29 × 27.5 cm / 24 pcs / 22 kg

Dimensions & technical notes

Mechanical dimensions

63 × 125.2 × 113.5 mm

Side elevation
EDR-240 side elevation from the WEHO drawing.

Side elevation from the model sheet; dimensions in mm.

Front elevation
EDR-240 front elevation from the WEHO drawing.

Front elevation from the model sheet; dimensions in mm.

Top view
EDR-240 top view from the WEHO drawing.

Top view from the model sheet; dimensions in mm.

Bottom view
EDR-240 bottom view from the WEHO drawing.

Bottom view from the model sheet; dimensions in mm.

TB1: 1 = FG; 2 = AC/N or DC −; 3 = AC/L or DC +.

TB2: 4 and 5 = −V; 6 and 7 = +V.

Product overview

Use EDR-240 where the panel needs one DC voltage. For example, EDR-240-24 provides 24 V at 0–10 A, while EDR-240-48 provides 48 V at 0–5 A. Compare the actual load profile, not the suffix alone.

Design features

FeatureWhat to check
Output selection24 V or 48 V; choose one version for the required DC rail.
Input and restartAt cold start the input draws 20 A at 115 VAC; 35 A at 230 VAC. This transient is not available to the DC load.
Cabinet environment−20 to +60 °C. Check the intended load at the actual ambient temperature.

Installation & applications

Installation checks

Reserve space on the rail for EDR-240.

Reserve space on the rail

The sheet lists 63 × 125.2 × 113.5 mm. Check terminal access and cable bends separately; the enclosure dimension is not an installation clearance.

Identify the terminal blocks for EDR-240.

Identify the terminal blocks

TB1: 1 = FG; 2 = AC/N or DC −; 3 = AC/L or DC +. TB2: 4 and 5 = −V; 6 and 7 = +V. Verify the markings on the unit before connecting power.

Check cabinet temperature for EDR-240.

Check cabinet temperature

−20 to +60 °C. Check the air temperature at the supply under the intended cabinet load. The temperature interval alone does not rate full output at its upper limit.

Allow for input inrush for EDR-240.

Allow for input inrush

The sheet gives 20 A at 115 VAC; 35 A at 230 VAC. Compare the applicable input condition with upstream protection; these are not DC load-current ratings.

Application examples

Tape feeders run up to the moving head inside a surface-mount placement machine.

Watching component pickup

A vacuum switch can flag an empty nozzle after a component pickup. Size the low-voltage sensing and feeder-control circuits separately from the gantry motors and vacuum source. For an external 24 V DC input, compare total running and peak demand with EDR-240-24 (0–10 A).

Photo: Peripitus — Pick and place internals of surface mount machine.JPG · CC BY-SA 3.0 · Resized and converted to WebP; full frame. Illustrative only; no endorsement or verified installation.
The upper and lower tooling extend across a long hydraulic press brake on the factory floor.

Position feedback on a press brake

A position encoder can report backgauge travel as sheet is positioned for the next bend. Check the encoder interface and controller demand; hydraulic power and safeguarding stay separate. For an external 24 V DC input, compare total running and peak demand with EDR-240-24 (0–10 A).

Photo: GaspariniIndustries — High-tonnage press brake.jpg · CC BY-SA 4.0 · Converted to WebP; full frame. Illustrative only; no endorsement or verified installation.
A bridge-type coordinate measuring machine holds its probe over fixtures on a dark measuring table.

Capturing a probe contact

A touch-probe interface can register the instant the stylus contacts a part. Match the interface supply and noise requirements, not the CMM drive rating. For an external 24 V DC input, compare total running and peak demand with EDR-240-24 (0–10 A).

Photo: Blue tooth7 — Beyond CrystaC.jpg · CC BY-SA 3.0 · Resized and converted to WebP; full frame. Illustrative only; no endorsement or verified installation.
Two green compressor assemblies and insulated pipes stand in front of control panels in a refrigeration plant.

Annunciating refrigeration equipment status

A panel annunciator can show which compressor is running or awaiting service. Sum the indicator and relay-coil currents for the whole panel; the compressor motors are not on this branch. For an external 24 V DC input, compare total running and peak demand with EDR-240-24 (0–10 A).

Photo: Neurotronix — Sala de máquinas refrigeración.JPG · CC BY-SA 4.0 · Converted to WebP; full frame. Illustrative only; no endorsement or verified installation.

Application images are illustrations of possible DC loads, not customer installations or verified equipment pairings.

Frequently asked questions

Which outputs are available?

The sheet lists 24 V or 48 V. Select the suffix that matches the load; these are separate output versions.

What current does the 24 V version supply?

EDR-240-24 is listed at 0–10 A. Include all loads that operate together; check startup demand separately.

What input range should I specify?

The EDR-240 sheet lists 90–264 VAC at 47–63 Hz, or 127–370 VDC. State which supply will be present at the panel.

What happens after a fault?

105–130%: output cutoff; automatic recovery. Overvoltage: 115–140% of rated output power (sheet wording); output shuts down. Reapply power to recover. No voltage trip level is specified.

How should I check cabinet fit?

The sheet lists 63 × 125.2 × 113.5 mm. Allow space for the cable bend and access to the terminal blocks.

What information is useful for a quotation?

Give the full suffix (for example, EDR-240-24), input source, running and startup current, cabinet temperature, quantity and destination.

What equipment can the DC output serve?

A control-panel load such as an operator interface is a candidate only if its input voltage, running current and startup demand fit the selected version. The supply does not drive a complete production line by implication.

Why use a DIN rail unit?

Rail mounting groups the power supply with cabinet controls. Keep terminal access, space for wiring and air temperature in the layout.

Send Inquiry

Tell us how many units you need and where they will be delivered.

EDR-240-24 sample, oblique view.
EDR-240-24 · photographed sample
Selected model
EDR-240-24EDR-240-48
DC output
24 V · 0–10 A48 V · 0–5 A