Check the rail position
Allow for the 22.5 × 90 × 100 mm housing on TS35/7.5 or TS35/15 rail. The drawing dimensions exclude the cable bend and working space.
MDR-10 is a slim line DIN rail Class I switching power supply.
Designed with a fully isolated plastic case to prevent user contact and the risk of shock.Featuring up to 88% efficiency this series can be cooled using only free air convection up to 60°C which significantly increases the reliability and lifetime of the power supply.Other standard features include its low no-load power consumption, to save energy, short circuit, overload, and over voltage protections, and DC OK relay contact with LED indicator for monitoring the PSU status.If you have any questions, please do not hesitate to contact us at Email: [email protected]
Compare four low-current DC outputs for sensing and indication in a 22.5 mm rail position.
| Parameter | MDR-10-5 | MDR-10-12 | MDR-10-15 | MDR-10-24 |
|---|---|---|---|---|
| DC output voltage and current | 5 V · 0–2 A | 12 V · 0–0.84 A | 15 V · 0–0.6 A | 24 V · 0–0.42 A |
| Efficiency | 77% | 81% | 82% | 84% |
| Ripple and noise | 80 mV p-p | 120 mV p-p | 120 mV p-p | 150 mV p-p |
| Line regulation | ±1% | ±1% | ±1% | ±1% |
| Load regulation | ±1% | ±1% | ±1% | ±1% |
| DC voltage adjustment | ±2% | ±1% | ±1% | ±1% |
| 5 V signal: minimum R | 200 Ω | 1.5 kΩ | 2 kΩ | 3.9 kΩ |
| LED example: minimum R | 1 kΩ | 2.4 kΩ | 3 kΩ | 4.7 kΩ |
| Relay example: minimum RL | 120 Ω | 700 Ω | 700 Ω | 1.2 kΩ |
| AC input | 85–264 VAC | |||
| DC input | 120–370 VDC | |||
| Dimensions (W × H × D) | 22.5 × 90 × 100 mm | |||
| Input frequency | 47–63 Hz | |||
| Cold-start inrush | 35 A at 115 VAC; 70 A at 230 VAC | |||
| Overload protection | 105–160%; output cuts off and recovers automatically. | |||
| Overvoltage protection | 120–140%; output shuts down. Cycle input power to recover. | |||
| Setup / rise at full load | 500 / 30 ms at 230 VAC; 1000 / 30 ms at 115 VAC. | |||
| Hold-up time | Not specified. | |||
| Withstand voltage (1 min) | Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV. | |||
| Insulation resistance | 100 MΩ at 500 VDC: input/output, input/FG and output/FG. | |||
| Working temperature | −10 °C to +50 °C | |||
| Mounting rail | TS35/7.5 or TS35/15 | |||
| Unit weight | 0.17 kg | |||
| Packing | 45.5 × 31.5 × 23 cm / 90 pcs / 16 kg | |||
| Model | Output | Current | Efficiency |
|---|---|---|---|
| MDR-10-5 | 5 V | 0–2 A | 77% |
| MDR-10-12 | 12 V | 0–0.84 A | 81% |
| MDR-10-15 | 15 V | 0–0.6 A | 82% |
| MDR-10-24 | 24 V | 0–0.42 A | 84% |
| Ripple and noise | 80 mV p-p |
|---|---|
| Line regulation | ±1% |
| Load regulation | ±1% |
| DC voltage adjustment | ±2% |
| 5 V signal: minimum R | 200 Ω |
| LED example: minimum R | 1 kΩ |
| Relay example: minimum RL | 120 Ω |
| Ripple and noise | 120 mV p-p |
|---|---|
| Line regulation | ±1% |
| Load regulation | ±1% |
| DC voltage adjustment | ±1% |
| 5 V signal: minimum R | 1.5 kΩ |
| LED example: minimum R | 2.4 kΩ |
| Relay example: minimum RL | 700 Ω |
| Ripple and noise | 120 mV p-p |
|---|---|
| Line regulation | ±1% |
| Load regulation | ±1% |
| DC voltage adjustment | ±1% |
| 5 V signal: minimum R | 2 kΩ |
| LED example: minimum R | 3 kΩ |
| Relay example: minimum RL | 700 Ω |
| Ripple and noise | 150 mV p-p |
|---|---|
| Line regulation | ±1% |
| Load regulation | ±1% |
| DC voltage adjustment | ±1% |
| 5 V signal: minimum R | 3.9 kΩ |
| LED example: minimum R | 4.7 kΩ |
| Relay example: minimum RL | 1.2 kΩ |
| AC input | 85–264 VAC |
|---|---|
| DC input | 120–370 VDC |
| Dimensions (W × H × D) | 22.5 × 90 × 100 mm |
| Input frequency | 47–63 Hz |
| Cold-start inrush | 35 A at 115 VAC; 70 A at 230 VAC |
| Overload protection | 105–160%; output cuts off and recovers automatically. |
| Overvoltage protection | 120–140%; output shuts down. Cycle input power to recover. |
| Setup / rise at full load | 500 / 30 ms at 230 VAC; 1000 / 30 ms at 115 VAC. |
| Hold-up time | Not specified. |
| Withstand voltage (1 min) | Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV. |
| Insulation resistance | 100 MΩ at 500 VDC: input/output, input/FG and output/FG. |
| Working temperature | −10 °C to +50 °C |
| Mounting rail | TS35/7.5 or TS35/15 |
| Unit weight | 0.17 kg |
| Packing | 45.5 × 31.5 × 23 cm / 90 pcs / 16 kg |
22.5 × 90 × 100 mm (W × H × D)
Housing: 22.5 mm wide × 90 mm high.
Housing depth: 100 mm. Allow extra room for field wiring.
35 mm rail width. Fits TS35/7.5 or TS35/15.
Terminal groups: 1 and 2 — AC input; 3 — ground; 4 — DC positive; 5 — DC negative; 6 — DC OK. Follow the markings on the actual unit. Do not infer DC-input polarity from the AC labels.
DC OK is a signal terminal. The signal, LED and external relay examples use different minimum resistances; the relay example is not an internal dry-contact rating.
The 15 V model supplies 0–0.6 A. A sensor that requires more than 0.6 A at startup needs a different selection.
The MDR-10 brings a regulated DC branch and external signal circuits to the rail. Choose the output from the load label, then use its own column for current, ripple and efficiency.
| Feature | What to check |
|---|---|
| Voltage selection | Choose a fixed output suffix before comparing current ranges. |
| Status monitoring | DC OK is a signal terminal. The signal, LED and external relay examples use different minimum resistances; the relay example is not an internal dry-contact rating. |
| Service access | Allow for the 22.5 × 90 × 100 mm body plus wiring and access to the voltage trim. |
| Power budget | The 15 V model supplies 0–0.6 A. A sensor that requires more than 0.6 A at startup needs a different selection. |
The photo identifies one specimen; electrical data on this page come from the WEHO model sheet.
Illustrative scenes only; the waveform is not a product test result.

Allow for the 22.5 × 90 × 100 mm housing on TS35/7.5 or TS35/15 rail. The drawing dimensions exclude the cable bend and working space.

For the MDR-10-5, verify the complete model suffix on the unit. With power isolated, check the full suffix and terminal markings on the unit being installed. A different output choice is a different version.

For MDR-10-24, the printed current range is 0–0.42 A. Add the branch loads that can start together; do not substitute input inrush for DC capacity.

The input inrush is 35 A at 115 VAC; 70 A at 230 VAC. Check the upstream protection at the corresponding input voltage, separately from output current.

For a balance specified for an external 5 V DC input, compare its peak current with the MDR-10-5 range (0–2 A). Confirm connector polarity and the permitted ripple before changing its supply.
Photo: Giovanna Canu, Francesca Cirisano, Sofia Gambaro, CNR-ICMATE · CC BY 4.0
A separate 12 V DC panel meter can display bath temperature from a matching probe. Check the meter’s input and current against MDR-10-12 (0–0.84 A); the bath heater needs its own supply.
Photo: Adimora chidinma · CC0 1.0
At a self-check station, an RFID reader identifies tagged books. For a separately powered 5 V DC reader, compare peak scanning current with MDR-10-5 (0–2 A). A USB-only reader still needs its specified host.
Photo: Löwenmaus27 · CC BY 4.0
For a 24 V DC selection panel, add the current of its input electronics and all indicators that can light together. Compare that total and startup demand with MDR-10-24 (0–0.42 A), excluding the vend motor and refrigeration.
Photo: Nelo Hotsuma · CC BY 2.0These photographs show where low-voltage loads are used. They do not show verified MDR-10 installations or imply endorsement. Match the actual component’s specified input before choosing a supply.
No. Each column identifies a separate single-output version. For example, MDR-10-12 is the 12 V model and MDR-10-24 is the 24 V model. The trim adjustment is not a voltage selector.
MDR-10-24 is specified at 0–0.42 A. Include simultaneous loads and startup demand when sizing the branch.
The MDR-10 datasheet specifies 85–264 VAC and 120–370 VDC. The 47–63 Hz frequency range applies to AC.
The housing measures 22.5 × 90 × 100 mm. The manufacturer drawing lists TS35/7.5 or TS35/15; reserve extra space for cable access.
DC OK is a signal terminal. The signal, LED and external relay examples use different minimum resistances; the relay example is not an internal dry-contact rating.
No. The sheet lists −10 °C to +50 °C as the working range; it does not establish full load at every ambient temperature. Check the actual enclosure conditions.
Overload cuts off output with automatic recovery. Overvoltage shuts down the output; cycle input power after the fault is cleared.
500 / 30 ms at 230 VAC; 1000 / 30 ms at 115 VAC. These are full-load setup and rise times. No separate hold-up value is printed.
35 A at 115 VAC; 70 A at 230 VAC are the two cold-start input conditions. Coordinate upstream protection for the actual input and number of supplies starting together.
MDR-10-12 lists 120 mV p-p. Check the ripple tolerance at the load as well as the DC current requirement.
Input/output: 1.5 kV; input/FG: 1.5 kV; output/FG: 0.5 kV. These one-minute withstand figures are not continuous operating voltages.
Give the full MDR-10 suffix, DC load and startup demand, installed rail and available space. A match in family wattage or cabinet width does not establish interchangeability.



This view shows MDR-10-5; the photographed unit does not change when another output is selected. Electrical specifications follow the MDR-10 datasheet.

A crop of the pictured specimen for identification, not a separate specification source.
Width and height are dimensioned on the front view.
Depth is dimensioned on the side view; it does not include field wiring.
Rail profile from the model sheet. Mounting types: TS35/7.5 and TS35/15.
Tell us how many units you need and where they will be delivered.